Mr. Mcllvain <br /> CRM Architects&Planners, Inc. <br /> Plan Check Number: B1805-010, First Review <br /> August 1, 2018 <br /> 7. Sheet A1.1 specifies a total of 56 parking spaces. The minimum number of accessible parking <br /> spaces shall be 3 per IBC Table 1106.1. One additional space shall be provided. The space <br /> shall be provided with an access aisle per ICC A117.1-09 Section 502.4. An accessible route <br /> shall be provided between the aisle and the sidewalk per IBC Section 1104.1. See IBC Section <br /> 1101.2. A third accessible parking space has been added. With curb ramp connecting access <br /> aisle with accessible route. See site plan A1.1 and site access drawing A1.2 detail 4, <br /> Energy: <br /> 8. The building sections specify R-30 continuous rigid insulation above the roof deck. See Section <br /> B-B/A6.1 as an example. The roof shall be provided with a minimum insulation of R-38 per <br /> WSEC-15 Table C402.1.3. The drawings should be revised. References to R-30 have been <br /> revised to R-38. <br /> 9. The architectural drawings do not specify insulation for the exterior walls. The structural <br /> drawings only specify insulation in the parapets per Details 3/S3.0 and 2/S7.0. The typical wall <br /> stud spacing appears to be 16 inches. The architectural drawings should be revised to require <br /> a minimum insulation of R-21 in the walls. See WSEC-15 Table C402.1.3. Wall insulation has <br /> been noted to read R-21 drawings A6.1 and A6.3. <br /> 10.The architectural drawings do not specify insulation for the perimeter foundations. Detail <br /> 7/SF1.2 appears to indicate insulation with a note stating "INSULATION PER T24 <br /> REQUIREMENTS", which appears to be a reference to Title 24 of the California Energy Code. <br /> The foundation shall be insulated per the requirements of the WSEC. The insulation shall <br /> create a thermal break between the slab-on-grade and the exterior foundation if the insulation <br /> is located on the interior of the foundation. See WSEC-15 Section C402.2.6 and Table Table <br /> C402.1.3. Note has been Called out on A6.1 and A6.2. Structural drawings revised. <br /> 11. Sheet A7.1 specifies the exterior door and window elevations. See the WSEC-15. The <br /> following comments shall be addressed: <br /> a. The Type C door specifies an insulation value of R=2.38. The maximum factor for metal- <br /> framed operable doors is U=0.4 per Table C402.4, or a maximum of R=2.5. The <br /> specification shall be revised. Noted on the door and window elevations <br /> b. The Type A and B doors shall specify insulation values of maximum U=0.6 or minimum <br /> R=1.67 per Table C402.4. Noted on the door and window elevations <br /> c. The Type D and E doors shall specify insulation values of maximum U=0.37 or minimum <br /> R=2.7 per Table C402.1.4. Noted on the door and window elevations <br /> d. The windows shall specify insulation an value of maximum U=0.38 or minimum R=2.63 per <br /> Table C402.4. Doors type C have been eliminated by owner revision delta 1 and replaced <br /> with storefront and door 5. Maximum U values and Minimum R values have been added to <br /> door and window elevations. <br /> age 3 of, lZ <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425) 257-8810 • Fax (425) 257- <br />