S <br /> Mr. Mcllvain <br /> CRM Architects&Planners, Inc. <br /> Plan Check Number: B1805-010, First Review <br /> August 1, 2018 <br /> 19.The project includes steel-framed canopies per Detail 7/S7.0. See IBC Sections 1604.1 and <br /> 1604.4. The following comments should be addressed: See structural response letter <br /> a. Additional detailing for the blocking at the wall studs shall be provided. The size of the <br /> blocking and the minimum edge distances for the bolts shall be specified. The attachment <br /> of the blocking to the 2x6 joists shall be specified. <br /> b. Details specifying the construction of the plate connections to the blocking shall be <br /> provided. <br /> c. Calculations for the design of the studs and headers supporting the canopy shall be <br /> provided for review. The design shall consider load combinations per IBC Equations 16-10, <br /> 16-12, and 16-13. The directions of wind and snow loading, both on the roof and wall <br /> surfaces, shall be aligned to create the maximum loading condition. The design shall <br /> consider moments due to opposing trust loads in the canopy connections. The design shall <br /> consider combined flexural-axial or biaxial bending as occurs for the supporting members. <br /> d. Calculations for the design of the canopy connections to the wood studs shall be submitted <br /> for review. Calculations shall include the plate connections, bolts, blocking, and <br /> connections to the wood framing. The calculations shall include concurrent shear and <br /> torsion due to eccentric loading. The calculations shall verify that the torsion does not <br /> result in splitting of the studs due to perpendicular-to-grain loading. <br /> Lateral System: <br /> 20.The seismic base shear is based on a building weight of 150 kips. This value appears to be <br /> less than the dead load of the structure. Documentation substantiating the building weight <br /> should be submitted for review. See IBC Section 1613.1 and ASCE 7-10 Section 12.7.2. The <br /> dead load shall include, but is not limited to, the following: See structural response letter <br /> a. Wall weight for full height of walls that are oriented parallel to the direction of loading. <br /> b. Mechanical equipment on the roof per Sheets S3.0 or A5.1; see other comments on these <br /> weights. See ASCE 7-10 Section 12.7.2 Item 3. <br /> c. Weights for non-structural systems. The weight for the mechanical ducts alone should be 4 <br /> psf per ASCE 7-10 Table C3-1. <br /> d. Estimated interior finishes. If finishes are not known, a worst-case estimate shall be <br /> considered (e.g., heavy soffit ceiling, etc.). <br /> e. Exterior wall finishes. Note that the walls are finished with heavy stone and plaster <br /> facades. <br /> f. Interior partition walls. See ASCE 7-10 Section 12.7.2 Item 2. <br /> g. Canopies. <br /> 21.The structural calculations state that the wind base shear controls and the lateral system has <br /> been designed using this loading. The nominal capacities for wood diaphragms and shear <br /> walls for seismic loading are less than those for wind loading per AWC SDPWS-15 Tables 4.2A <br /> and 4.3A. Per the previous comment, the seismic loads may increase. The lateral design <br /> should be reviewed and revised as needed. See IBC Sections 1604.10 and 2306.1. See <br /> structural response letter <br /> 22.The calculation of the wind base shear is unclear. The calculations appear to include the <br /> procedures from Sections 27.2 and 28.2. The wind notes on Sheet SO.0 state that procedure <br /> per IBC Section 1609.6 has been used; calculations for this procedure do not appear to be� <br /> Page 8 off <br /> CITY OF EVERETT• 3200 Cedar Street• Everett, WA 98201 • (425) 257-8810 • Fax(425) 25 - 5-7— <br />