Laserfiche WebLink
1. The building is identified on the drawings as construction type VB with minimum ten -foot clearance at all <br />sides from the property line or centerline of street. Per IBC Tables 601, 602 and section 705.8.1 exception 2, <br />opening limitations and protection do not appear to be required. <br />a. For all other rated partitions, floor assemblies, or floor -ceiling assemblies referenced on the set, please <br />either show the tested assembly number and construction requirements on the drawings. <br />We Concur — Ref. revised A712 for details <br />i 2. Projections into the setback do have to be rated per IBC 705.2.3 unless they are fully non-combustible: <br />please either show the tested assembly number and construction requirements on the drawings or detail <br />the construction of the projections (canopies) as non-combustible construction. <br />The projects (steel canopies) are fully non-combustible. <br />3. Automatic detection system should be shown on the drawings as a requirement, per EMC 16.76.035 and,IBC <br />section 907.5. <br />Fire Sprinklers & Fire Alarm are deferred submittals but have noted this on the life safety drawing G201 <br />4. Doors exiting from the assembly occupancy should be shown with panic hardware on the door schedule, per <br />IBC section 1010.1.10 as amended by the State of Washington. <br />We concur- Ref. A601 for updated door schedule <br />J 5. All doors from the restaurant should swing in the direction of egress, assuming that the occupant load <br />exceeds 49, per IBC section 1010.1.2.1. <br />We concur — Ref. revised A121 for details <br />6. Please indicate means of egress illumination and exit signs on the reflected ceiling plans, per IBC sections <br />1008.3.2, 1008.3.3, and 1013.1. Exit signs should clearly mark the exit access stairway path for both stairs, <br />per IBC 1019.3 item 1. <br />We concur— Ref. revised A122 for details <br />J <br />7. Raised character and braille exit signs should be shown on the drawings, per IBC section 1013.4. <br />We concur— Ref. revised A452 for details <br />Construction <br />1. Please identify the accessible means of egress in the code analysis and on the life safety drawings, per IBC <br />section 1009, and indicate directional signage per IBC section 1009.9 on the drawings. <br />We concur- Ref. revised G201 <br />J 2. Please indicate a two-way communication system at all elevator banks per IBC section 1009.8, as amended <br />by the State of Washington. <br />We concur- ref. revised A462, Elevator drawing notes: #5 <br />1 3. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating <br />ELECTRICAL ROOM or similar approved wording, per IBC K111.7. <br />We concur— ref. 1/A200 North Elevation and G201 <br />J 4. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet (1829 mm) wide, that contain <br />overcurrent devices, switching devices or control devices with exit or exit access doors, shall be equipped <br />with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. <br />Electrical is a deferred submittal and at this time, the level of the amperes is unknown. <br />ARCHITECTURE PLANNING INTERIOR DESIGN Jensen Fey <br />wwwienxenfevmm - 7730TrarvMv RMmnnd.WA9R052 - PHONE425.216.031R - FAx425.216.0329 <br />