Laserfiche WebLink
• • <br /> Everett Housing Authority <br /> Administrative Office Upgrades <br /> 03/24/20 <br /> Page 6 <br /> Energy: <br /> 14. Section 11/A40.01 shows the construction through the roof and walls for the elevator <br /> shaft. See IBC Section 107.2.1, and WSEC Section C503 and Table C402.1.3. The <br /> following comment should be addressed: <br /> a. The wall should specify minimum R-13 plus R-10ci insulation. The four-inch framing <br /> is sufficient for the R-13 insulation; the value should be specified. The continuous <br /> insulation is not included and should be specified. <br /> b. The roof should specify minimum R-38ci insulation. <br /> ANSWER; <br /> a. See revised section 11/A40.01 that includes notes regarding the inclusion <br /> of R-21 high density bait insulation within shaft walls. <br /> b. See revised section 11/A40.01 that includes notes regarding the inclusion <br /> of R38ci insulation. <br /> 15. The Reflected Ceiling Plan on Sheet A22.01 includes four new ceiling daylighting <br /> devices. The drawings should specify a maximum thermal rating of U=0.35 for the <br /> devices. See IBC Section 107.2.1 and WSEC Table C402.4. <br /> ANSWER: See revised Reflected Ceiling Plan on Sheet A22.01. Notes have <br /> been added to the new daylighting devices to specify a maximum thermal <br /> rating of 11=0,35 for the devices. <br /> 16.The Main Level Plan on Sheet A21.01 and the elevations on Sheet A31.01 include a new <br /> exterior curtain wall at Grid A.1-A.5/5.2-5.6. See IBC Section 107.2.1, and WSEC <br /> Section C503 and Table C402.1.3. The following comments should be address: <br /> a. The drawings should specify a maximum thermal rating of U=0.38 for the windows. <br /> b. The drawings should specify a maximum thermal rating of U=0.60 for the door. <br /> ANSWER; <br /> a. The new exterior curtain wall at Grid A.1 A,5/5,3-5,6 in simply provided to <br /> surround an exterior Porch area for staff to be outside the building. The <br /> area is open to the elements and does not create a tempered space. The <br /> glazing system is not an insulated system but a barrier to provide shelter <br /> from the wind. No thermal rating is required. <br /> b. As in Item a above the door is not part of an insulated glazing system. No <br /> thermal rating is required. <br /> Structural <br /> General: <br /> 1. Structural and geotechnical special inspections are required for this project. A statement <br /> on special inspections is provided in the"Special Inspection" section of the General <br /> Structural Notes on Sheet S00.01. The statement shall include a table listing each type <br />