e ♦ . <br />9. The building appears to be incorporating unheated and unventilated space between Grids E-F. The building <br />shall meeting the ventilation and heating requirements of IBC Sections 1203.1 and 1204.1. The construction <br />drawings shall specify modifications to the existing systems or indicate new system components satisfying these <br />requirements. See IEBC Section 1011.1 and IBC Section 107.2.1. <br />The project is currently out for bid with mechanical heating and cooling of entire building. HVAC <br />system to be under a separate permit by Contractor, revised General Notes /A0.0. <br />10. The Finish Legend on Sheet A9.0 states that the south walls of Restrooms 114 and 115 shall be ceramic tile. <br />The east and west walls shall similarly be provided with a non -absorbent surface. See IBC Section 1210.2.2. <br />Finish Legend /A9.0 and 1 & 3 /A5.2 have been updated to indicate the on east and west walls too. <br />Please feel free to contact us if you anything needs further clarification. <br />Sincerely, <br />Joe Duzan <br />Cant Nychay Architecture PLLC <br />1105 North 38th I Seattle, WA 98103 1 206 545-9100 <br />7702 Moon Valley SE I North Bend, WA 98045 1 425 292-9776 <br />Gan ftchay.com <br />