View Ridge Community Church <br /> Plan Check Number: B1803-040, First Review <br /> May 25, 2018 <br /> 5. The project includes work that will be performed on the premises of fabricators'shops. Special <br /> inspections are required to be performed by the fabricators unless they are registered and <br /> approved to perform work without special inspections. The General Structural Notes on Sheet <br /> S-1 should be revised to list work being performed by approved fabricators. Work not being <br /> performed by approved fabricators should be added to the list of special inspections. See IBC <br /> Sections 1704.2.5, 1704.2.5.1, and Section 1704.5 Items 1 and 2. The following work shall be <br /> specified in the notes: <br /> a. Concrete reinforcement fabrication and bending (IBC Section 1705.3) <br /> b. Metal plate-connected wood trusses (IBC Sections 2303.4.6, and 2303.4.7). <br /> 6. Geotechnical observations should be performed for this project as recommended in the <br /> geotechnical report by Associated Earth Sciences, Inc., dated August 29, 2016, in Section 14.0 <br /> Project Design and Construction Monitoring A list of the required geotechnical observations <br /> should be provided in the General Structural Notes on Sheet S-1. See IBC Sections 107.1 and <br /> 107.2.1. The following is a summary based on a review of the construction drawings and the <br /> geotechnical report: <br /> a. Site grading (IBC Section 1804.4). <br /> b. Movement monitoring of adjacent structures (IBC Sections 1803.5.7 and 1804.1). <br /> c. Installation of permanent subsurface drainage system (IBC Section 1805.4) <br /> d. Placement and compaction of structural backfill (IBC Section 1803.4). <br /> 7. The structural drawings include work that has been deferred by the structural engineer. A <br /> statement of deferred submittals shall be added to the General Structural Notes on Sheet S-1 <br /> listing work designated as deferred submittals. The note shall include a statement requiring <br /> the engineer-of-record to review deferred submittals for conformance with the construction <br /> documents. See IBC Sections 107.2.1, 107.3.4, 107.3.4.1, and 107.4. The following is a <br /> summary based on a review of the construction documents: <br /> a. Metal plate-connected wood trusses (between Wall Lines C-D/2-3). <br /> b. Double laminated drag truss (at Wall Line C/2.3-2.7). <br /> 8. The"Design Criteria"section of the General Structural Notes on Sheet S-1 provides the <br /> earthquake design data. See IBC Sections 1603.1.5 and 1613.1. The following comments <br /> should be addressed: <br /> a. The data should identify the lateral force resisting system as wood-framed shear walls. <br /> b. The"Lateral Analysis"section of the structural calculations states an overstrength factor of <br /> 0=2.5. This should be included in the design data. <br /> c. Continuing with the previous comment, it appears W is based on ASCE 7-10 Table 12.2-1 <br /> and Footnote"g"allowing a 1/2-reduction for flexible diaphragms. The flexible diaphragm <br /> assumption should be stated in the data. <br /> 9. The"Foundations and Retaining Walls - Concrete" section of the General Structural Notes on <br /> Sheet S-1 specifies a concrete strength less than 4,500 psi. The project appears to include <br /> concrete elements that are exposed to freeze-thaw cycles, and qualify as Class F2 concrete per <br /> ACI 318-14 Table 19.3.1.1. Per ACI 318-14 Table 19.3.2.1, the minimum concrete strength for <br /> Class F2 concrete is 4,500 psi. The minimum concrete strength on Sheet S-1 should be revised <br /> as required. See IBC Section 1901.2. <br /> e8of12 <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425) 257-8810 • Fax(425) 257-8857 <br />