GENERAL REQUIREMENTS ACCESSIBILITY NOTES EGRESS NOTES FIRE PROTECTION NOTES <br /> 1. THE DRAWINGS ARE INTENDED TO ONLY PARTIALLY DESCRIBE THE SCOPE OF 1. ACCESSIBLE ROUTES SHALL BE PROVIDED FROM ACCESSIBLE PARKING, PASSENGER 1. THE WIDTH OF STAIRWAYS SHALL NOT BE LESS THAN 36 INCHES. 1.AN AUTOMATIC SPRINKLER SYSTEM MEETING THE REQUIREMENTS OF <br /> WORK FOR THE PROJECT. ANY WORK NOT SHOWN HERE, BUT REQUIRED BY CODE, OR LOADING ZONES AND PUBLIC STREETS OR SIDEWALKS TO THE ACCESSIBLE BUILDING SECTION 903.3.1.1 FOR NFPA 13 SPRINKLER SYSTEMS SHALL BE INSTALLED <br /> THE SPECIFICATIONS, OR TO MAKE THE WORK COMPLETE, SHALL BE PROVIDED AS ENTRANCE.AN ACCESSIBLE ROUTE SHALL BE PROVIDED TO EACH ACCESSIBLE PORTION OF 2. STAIRWAYS SHALL HAVE A MINIMUM HEADROOM CLEARANCE OF 80 INCHES THROUGHOUT. QUICK-RESPONSE SPRINKLERS SHALL BE INSTALLED IN ALL <br /> PART OF THE WORK. THE BUILDING AND SHALL CONNECT EACH ACCESSIBLE LEVEL. MEASURED VERTICALLY FROM A LINE CONNECTING THE EDGE OF THE NOSINGS. DWELLING UNITS. SPRINKLER SYSTEMS PROTECTING DWELLING UNITS SHALL BE <br /> WET PIPE SYSTEMS PER IBC 903.3.2. SPRINKLERS IN LIVE/WORK UNITS SHALL BE <br /> 2. REFER TO THE LIST OF ABBREVIATIONS FOR COMMON ABBREVIATIONS USED IN 2.AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE BUILDING ENTRANCES 3. STAIR RISER HEIGHTS SHALL BE 7 INCHES MAXIMUM AND 4 INCHES MINIMUM. STAIR DESIGNED FOR OH2 OCCUPANCY HAZARD. PLASTIC SPRINKLER PIPE SHALL NOT <br /> THE DRAWINGS. IF AN ABBREVIATION IS NOT ON THE LIST, OR NOT COMMONLY USED, WITH THE PRIMARY ENTRANCE OF EACH DWELLING UNIT AND WITH THE EXTERIOR AND TREAD DEPTHS SHALL BE 11 INCHES MINIMUM. BE USED IN LIVE/WORK AREAS. <br /> REFER TO THE ARCHITECT FOR CLARIFICATION. INTERIOR SPACES THAT SERVE THE UNITS. <br /> 4. STAIR TREADS AND RISERS SHALL BE OF UNIFORM SIZE AND SHAPE. THE 2. THE SPRINKLER SYSTEM SHALL BE MONITORED BY A CENTRAL STATION <br /> 3. IT IS THE INTENT OF THE DOCUMENTS THAT ALL WORK COMPLIES WITH THE 3. CONTROLS, OPERATING MECHANISMS AND HARDWARE INTENDED FOR OPERATION BY TOLERANCE BETWEEN THE LARGEST AND SMALLEST RISER OR BETWEEN THE LARGEST SERVICE APPROVED BY THE LOCAL GOVERNING AGENT. <br /> LOCAL ADOPTED BUILDING CODE, MECHANICAL CODE, ELECTRICAL CODE, THE OCCUPANT, LOCATED IN ACCESSIBLE SPACES OR ALONG ACCESSIBLE ROUTES SHALL AND SMALLEST TREAD SHALL NOT EXCEED 0.375 INCH IN ANY FLIGHT OF STAIRS. <br /> ENERGY CODE, FIRE CODE, LAND USE AND ZONING CODE, VENTILATION AND INDOOR BE ACCESSIBLE. 3. FIRE HOSE THREADS USED IN CONJUNCTION WITH AUTOMATIC SPRINKLER <br /> AIR QUALITY CODE, AND ANY/ALL OTHER APPLICABLE LOCAL, STATE,AND NATIONAL CODES 5. STAIRWAYS SHALL HAVE HANDRAILS ON EACH SIDE. HANDRAILS SHALL BE OF A SYSTEMS AND STANDPIPE SYSTEMS SHALL BE COMPATIBLE WITH FIRE <br /> AND ORDINANCES IN EFFECT AT THE DATE OF PERMIT SUBMITTAL. NOTHING IN THESE 4. INTERIOR AND EXTERIOR SIGNS IDENTIFYING PERMANENT ROOMS AND SPACES SHALL UNIFORM HEIGHT, BETWEEN 34"AND 38"ABOVE THE STAIR-TREAD NOSING PER IBC DEPARTMENT HOSE THREADS. <br /> DRAWINGS SHALL BE CONSTRUED TO GRANT APPROVAL FOR ANY CODE VIOLATION. ANY BE TACTILE. 1012.2. HANDRAILS SHALL BE CONTINUOUS. <br /> ERRORS,OMISSIONS, OR NON-COMPLIANCE WITH GOVERNING CODES SHALL BE BROUGHT TO 4. STANDPIPE SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SECTION <br /> THE ATTENTION OF THE ARCHITECT IMMEDIATELY. 5. DIRECTIONAL AND INFORMATIONAL SIGNS OTHER THAN BUILDING DIRECTORIES SHALL 6. HANDRAILS ARE TO BE GRASPABLE, WITH A DIAMETER BETWEEN 1 1/4 INCHES AND 2 905, NFPA 14,AND RULES PROMULGATED BY THE BUILDING AND FIRE CODE <br /> CONTAIN VISUAL CHARACTERISTICS COMPLYING WITH ICC A117.1. INCHES OR SHALL PROVIDE EQUIVALENT GRASPABILITY. IF THE HANDRAIL IS NOT OFFICIALS. <br /> 4. BEFORE STARTING EACH PORTION OF THE WORK, THE CONTRACTOR SHALL CIRCULAR, IT SHALL HAVE A PERIMETER DIMENSION BETWEEN 4 INCHES AND 6 1/4 <br /> CAREFULLY STUDY AND COMPARE THE VARIOUS DRAWINGS AND OTHER CONTRACT 6. REQUIRED ACCESSIBLE ELEMENTS SHALL BE IDENTIFIED BY THE INTERNATIONAL INCHES WITH A MAX. CROSS-SECTION DIMENSION OF 2 1/4 INCHES AND A MIN. EDGE 5. CLASS I STANDPIPES SHALL BE PROVIDED THROUGHOUT. HOSE <br /> DOCUMENTS RELATED TO THAT PORTION OF THE WORK,AS WELL AS OWNER PROVIDED SYMBOL OF ACCESSIBILITY PER IBC 1110.1. THESE AREAS INCLUDE, BUT ARE NOT LIMITED RADIUS OF 0.01 INCH. CONNECTIONS SHALL BE PROVIDED IN THE FOLLOWING LOCATIONS:AT EACH <br /> INFORMATION, SHALL TAKE FIELD MEASUREMENTS OF ANY EXISTING TO, ACCESSIBLE PARKING SPACES (IF > 4), ACCESSIBLE AREAS OF REFUGE,ACCESSIBLE INTERMEDIATE LEVEL BETWEEN FLOORS IN EVERY STAIRWAY; AT EACH SIDE OF <br /> CONDITIONS RELATED TO THAT PORTION OF THE WORK AND SHALL OBSERVE ANY ENTRANCES WHERE ALL ENTRANCES ARE NOT ACCESSIBLE,AND UNISEX TOILETS AND 7. HANDRAILS SHALL BE CONTINUOUS BETWEEN FLIGHTS, OR THEY SHALL RETURN TO THE WALL ADJACENT TO A HORIZONTAL EXIT OPENING; IN EVERY EXIT <br /> CONDITIONS AT THE SITE AFFECTING IT. ANY ERRORS, INCONSISTENCIES OR BATHING ROOMS. A WALL OR THE WALKING SURFACE. AT THE TOP OF A STAIRWAY, HANDRAILS MUST PASSAGEWAY AT THE ENTRANCE INTO OTHER PARTS OF THE BUILDING; ON THE <br /> _ OMISSIONS SHALL BE REPORTED PROMPTLY TO THE ARCHITECT. EXTEND HORIZONTALLY 12 INCHES BEYOND THE TOP RISER. AT THE BOTTOM OF THE ROOF ADJACENT TO STAIR OPENINGS; OTHER REMOTE LOCATIONS AS SPECIFIED <br /> 7. INTERIOR AREAS OF REFUGE AND EXTERIOR AREAS OF ASSISTED RESCUE SHALL BE STAIRWAY, HANDRAILS MUST CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD IN IBC 905.4. STANDPIPE LOCATIONS SHALL BE VERIFIED WITH THE BUILDING AND <br /> 5. DO NOT SCALE THE DRAWINGS. THE CONTRACTOR SHALL USE DIMENSIONS PROVIDED WITH TWO-WAY COMMUNICATION SYSTEM TO A CENTRAL CONTROL POINT. IF BEYOND THE BOTTOM RISER. EXTENSIONS NOT REQUIRED ON STAIRWAYS THAT ARE FIRE CODE OFFICIALS PRIOR TO INSTALLATION. <br /> SHOWN ON THE DRAWINGS AND ACTUAL FIELD MEASUREMENTS. IF DISCREPANCIES CONTROL POINT NOT CONSTANTLY ATTENDED,AREA OF REFUGE SHALL ALSO HAVE NOT PART OF A REQUIRED MEANS OF EGRESS. <br /> ARE FOUND, THE ARCHITECT SHALL BE NOTIFIED AT ONCE. CONTROLLED ACCESS TO A PUBLIC TELEPHONE SYSTEM. 6. STANDPIPES SHALL BE INTERCONNECTED IN ACCORDANCE WITH NFPA 14. <br /> 8. GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING SURFACES THAT ARE IBC 905.4.2. STANDPIPES SHALL HAVE ISOLATION VALVES AND SHALL HAVE A <br /> 6. DIMENSIONS ARE SHOWN TO THE FACE OF CONCRETE, FACE OF STUD AT 8. TWO-WAY COMMUNICATION SYSTEM SHALL HAVE BOTH AUDIBLE AND VISUAL SIGNALS MORE THAN 30"ABOVE THE FLOOR OR GRADE BELOW AND AS SHOWN IN THE TWO-WAY FIRE DEPARTMENT CONNECTION VISIBLE AND ACCESSIBLE FROM THE <br /> EXTERIOR WALLS, FACE OF STUD WALL AT INTERIOR WALLS,AND EDGE OF ROUGH AND INSTRUCTIONS POSTED ADJACENT TO THE SYSTEM CONTROLS. INSTRUCTIONS SHALL DRAWINGS. STREET NEAR THE SPRINKLER SYSTEM FIRE DEPT. CONNECTION. <br /> OPENINGS, UNLESS DETAILED OR NOTED OTHERWISE ON DRAWINGS. REFER TO THE INSTRUCT HOW TO USE TWO-WAY COMMUNICATION SYSTEM, DIRECT USERS TO OTHER <br /> ARCHITECT IF CLARIFICATION IS NEEDED. MEANS OF EGRESS, INFORM USERS HOW TO SUMMON ASSISTANCE,AND STATE THAT 9. HANDRAIL ASSEMBLIES AND GUARDS SHALL BE DESIGNED AND CONSTRUCTED TO 7. THE OWNER SHALL BE RESPONSIBLE FOR PRODUCING A FIRE EMERGENCY <br /> PERSONS ABLE TO USE STAIRS SHOULD DO SO ASAP, UNLESS ASSISTING OTHERS. THE STRUCTURAL LOADING CONDITIONS SET FORTH IN IBC 1607.8.1 GUIDE. THIS GUIDE SHALL DESCRIBE THE LOCATION, FUNCTION AND USE OF FIRE <br /> 7. REPETITIVE FEATURES NOT INDICATED IN THE DRAWINGS EVERYWHERE THEY PROTECTION EQUIPMENT AND APPLIANCES ACCESSIBLE TO RESIDENTS, <br /> OCCUR SHALL BE PROVIDED AS IF DRAWN IN FULL. 9. REQUIREMENTS FOR DWELLING UNITS: 10. GUARDS SHALL FORM A PROTECTIVE BARRIER NO LESS THAN 42" HIGH. INCLUDING FIRE ALARM SYSTEMS, SMOKE ALARMS, AND PORTABLE FIRE <br /> a. THE ACCESSIBLE PRIMARY ENTRANCE SHALL BE ON AN ACCESSIBLE ROUTE FROM EXTINGUISHERS. THE GUIDE SHALL ALSO INCLUDE AN EMERGENCY EVACUATION <br /> 8. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY,AND WHAT IS REQUIRED BY PUBLIC AND COMMON AREAS. WITHIN THE UNIT,AT LEAST ONE ACCESSIBLE ROUTE SHALL 11. OPEN GUARDS SHALL BE DESIGNED AND CONSTRUCTED SO THAT A 4" DIAMETER PLAN FOR EACH DWELLING UNIT. THE EMERGENCY GUIDE SHALL BE REVIEWED <br /> ONE SHALL BE AS BINDING AS IF REQUIRED BY ALL. IN CASE OF DISCREPANCY, REFER CONNECT ALL SPACES AND ELEMENTS. THE ACCESSIBLE ROUTE SHALL HAVE A CLEAR SPHERE CANNOT PASS THROUGH ANY OPENING UP TO A HEIGHT OF 34". FROM 34"TO AND APPROVED BY THE FIRE CODE OFFICIAL. A COPY OF THE EMERGENCY GUIDE <br /> TO THE ARCHITECT FOR CLARIFICATION. WIDTH OF AT LEAST 36 INCHES, EXCEPT THAT SEGMENTS LESS THAN 24 INCHES IN LENGTH 42",AN 8" DIAMETER SPHERE SHALL NOT PASS. SHALL BE GIVEN TO EACH TENANT PRIOR TO INITIAL OCCUPANCY. <br /> MAY HAVE A CLEAR WIDTH OF 32 INCHES. <br /> 9. THE CONTRACTOR SHALL VERIFY THE DIMENSIONS REQUIRED FOR ALL 12. INTERIOR VERTICAL EXIT ENCLOSURES CONNECTING MORE THAN 3 STORIES SHALL 8. FIRE EXTINGUISHERS WITH A MINIMUM 2-A RATING SHALL BE LOCATED WHERE <br /> EQUIPMENT, APPLIANCES, FIXTURES, CABINETS, DUCTWORK, AND OPENINGS BEFORE b. IN TYPE A UNITS, TURNING SPACES SHALL BE REQUIRED IN ALL ROOMS, WITH THE HAVE STAIRWAY SIGNAGE AT EACH FLOOR LANDING. THE SIGN SHALL BE LOCATED 5 SHOWN ON PLANS,AND SUCH THAT NO AREA IN THE BUILDING IS MORE THAN 75 <br /> FRAMING BEGINS. THE CONTRACTOR SHALL COORDINATE WITH THE EXCEPTION OF BATHROOMS IN A UNIT THAT ALREADY HAS AT LEAST ONE BATHROOM FEET ABOVE THE FLOOR LANDING AND BE READILY VISIBLE WHEN THE DOORS ARE IN FEET TRAVEL DISTANCE FROM A FIRE EXTINGUISHER. THE FIRE EXTINGUISHERS <br /> SUBCONTRACTORS OF ALL TRADES TO VERIFY THE SIZES AND LOCATIONS OF MEETING ALL THE REQUIREMENTS OF ANSI 1003.11. TURNING SPACE SHALL BE EITHER A BOTH OPEN AND CLOSED POSITIONS. SHALL BE LOCATED IN CONSPICUOUS LOCATIONS ALONG NORMAL PATHS OF <br /> OPENINGS THROUGH THE FLOORS, WALLS, CEILINGS AND ROOFS FOR DUCTS, PIPES, CIRCULAR OR T-SHAPED SPACE. CIRCULAR SPACE SHALL BE 60" IN DIAMETER. T-SHAPED TRAVEL. THEY SHALL NOT BE OBSTRUCTED OR OBSCURED FROM VIEW. IN <br /> CONDUITS, AND EQUIPMENT. THE CONTRACTOR SHALL COORDINATE THE LOCATION SPACE SHALL FIT WITHIN A 60"X 60" SQUARE, WITH THE WIDTH OF EACH ARM AND BASE 13. STAIRWAY SIGNS SHALL DESIGNATE THE FLOOR LEVEL, THE TERMINUS OF THE TOP RESIDENTIAL CORRIDORS, FIRE EXTINGUISHERS SHALL BE HOUSED IN UNLOCKED <br /> AND INSTALLATION OF WOOD BACKING, BLOCKING, FURRING AND STRIPPING AS 36" MINIMUM. AND BOTTOM OF THE STAIR ENCLOSURE, THE IDENTIFICATION OF THE STAIR, THE CABINETS. IN GARAGES, FIRE EXTINGUISHERS SHALL BE MOUNTED ON SECURE <br /> REQUIRED FOR THE INSTALLATION AND ATTACHMENT OF WORK OF ALL TRADES. STORY AND DIRECTION TO THE EXIT DISCHARGE, WHETHER THERE IS ROOF ACCESS HANGERS OR BRACKETS. SEE FLOOR PLANS FOR LOCATIONS. <br /> c. THE PRIMARY ENTRANCE DOOR TO ALL UNITS SHALL HAVE MANEUVERING FOR FIRE DEPARTMENT,AND WHETHER THE ROOF IS ACCESSED BY ROOF HATCH. <br /> 10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SYSTEMS, INCLUDING, BUT CLEARANCES COMPLYING WITH ANSI 404, ICC A117.1. 9. A SINGLE, MANUAL AND AUTOMATIC FIRE ALARM SYSTEM THAT ACTIVATES THE Permit Set <br /> NOT LIMITED TO, MECHANICAL, PLUMBING, AND ELECTRICAL WORK. WORK SHOWN ON 14. EXIT SIGNS ARE REQUIRED AT EACH EXIT, EXIT ACCESS DOOR, AND ALONG THE OCCUPANT NOTIFICATION SYSTEM SHALL BE DESIGNED, <br /> THE DRAWINGS IS INTENDED TO ILLUSTRATE THE GENERAL DESIGN INTENT, SCOPE, d. IN TYPE A UNITS, ALL DOORWAYS INTENDED FOR PASSAGE SHALL HAVE ACCESS TO THE EXIT. NO POINT IN AN EXIT ACCESS CORRIDOR SHALL BE MORE THAN INSTALLED,AND MAINTAINED IN ACCORDANCE WITH THE REQUIREMENTS OF IFC B1804-011 <br /> AND LOCATION OF WORK. ALL WORK NOT SPECIFICALLY DRAWN, BUT REQUIRED FOR MANEUVERING CLEARANCES COMPLYING WITH ANSI 404, ICC A117.1. BATHROOMS IN A 100 FEET FROM THE NEAREST VISIBLE EXIT SIGN. EXIT SIGNS SHALL BE VISIBLE FROM SECTION 907 AND NFPA 72. <br /> - A COMPLETE, LEGAL,AND FUNCTIONING SYSTEM, SHALL BE PROVIDED AS PART OF UNIT THAT ALREADY HAS AT LEAST ONE BATHROOM MEETING ALL THE REQUIREMENTS OF ANY DIRECTION OF EGRESS TRAVEL,AND SHALL BE ILLUMINATED AT ALL TIMES. <br /> THE WORK. ANSI 1003.11 DO NOT HAVE TO COMPLY WITH THE MANEUVERING CLEARANCES ON THE 10. SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING LOCATIONS: ON THE <br /> BATHROOM SIDE OF THE DOOR. 15. TACTILE EXIT SIGNS SHALL BE PROVIDED ADJACENT TO EACH DOOR TO AN EGRESS CEILING OR WALL OUTSIDE OF EACH SEPARATE SLEEPING AREA IN THE <br /> 11. THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND STAIRWAY, EXIT PASSAGEWAY AND THE EXIT DISCHARGE COMPLYING TO ICC A117.1. IMMEDIATE VICINITY OF BEDROOMS, IN EACH ROOM USED FOR SLEEPING <br /> GOVERNMENTAL FEES, LICENSES AND INSPECTIONS NECESSARY FOR PROPER e. CHANGES IN LEVEL OF 1/4" OR LESS ARE PERMITTED TO BE VERTICAL. CHANGES IN PURPOSES, AND IN EACH STORY WITHIN A DWELLING UNIT. SMOKE ALARMS <br /> EXECUTION AND COMPLETION OF THE WORK, WITH THE EXCEPTION OF THE MASTER LEVEL BETWEEN 1/4"AND 1/2"SHALL BE BEVELED WITH A SLOPE OF 1:2. THRESHOLDS 16. PLACARDS READING "NOT AN EXIT" OR INDICATING THE USE OF THE SPACE BEYOND WITHIN AN INDIVIDUAL DWELLING UNIT SHALL BE INTERCONNECTED SUCH THAT REGISTERED <br /> USE PERMIT AND THE BUILDING PERMIT. SHALL NOT BE GREATER THAN 1/2" EXCEPT THAT THEY MAY BE 3/4"AT EXTERIOR SLIDING ARE REQUIRED AT ALL DOORWAYS, PASSAGEWAYS AND STAIRWAYS WHICH MAY BE THE ACTIVATION OF ONE ALARM WILL ACTIVATE ALL THE ALARMS IN THE INDIVIDUAL ARCHITECT <br /> DOORS. MISTAKEN FOR EXITS. REFER TO PLANS FOR EXIT SIGN LOCATIONS. UNIT. IFC 907.2.10. No.8013 <br /> 12. PRIOR TO THE COMMENCEMENT OF ANY CONSTRUCTION OR SITE DEVELOPMENT <br /> ACTIVITY, THE CONTRACTOR SHALL SCHEDULE PRE-CONSTRUCTION MEETINGS WITH f. IN TYPE A UNITS, LIGHTING CONTROLS, ELECTRICAL SWITCHES AND RECEPTACLE 17. THE MEANS OF EGRESS SHALL BE ILLUMINATED AT ALL TIMES AND AT EVERY POINT 11. SMOKE ALARMS SHALL BE POWERED BY THE BUILDING'S WIRING AND SHALL BE <br /> THE CITY OF SEATTLE DPD, SEATTLE CITY LIGHT,AND SEATTLE DEPARTMENT OF OUTLETS, ENVIRONMENTAL CONTROLS,APPLIANCE CONTROLS, OPERATING HARDWARE IN THE MEANS OF EGRESS. REFER TO LIGHTING NOTES FOR SPECIFIC REQUIREMENTS. EQUIPPED WITH A BATTERY BACKUP. PER IFC 907.3.2.3.AND NFPA 72. AN AUTOMATIC Joshua S.Scott <br /> TRANSPORTATION. FOR OPERABLE WINDOWS, PLUMBING FIXTURE CONTROLS,AND USER CONTROLS FOR 18. PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT ENCLOSURE ARE SMOKE DETECTION SYSTEM (PER IFC 907.2.9.3)THAT ACTIVATES THE OCCUPANT STATE OF WASHINGTON <br /> SECURITY OR INTERCOM SYSTEMS SHALL BE PROVIDED WITH A CLEAR FLOOR SPACE AND PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS AND MECHANICAL SYSTEMS SERVING NOTIFICATION SYSTEM (IFC 907.2.11) IN ACCORDANCE WITH SECTION (IFC)907.5 <br /> 13. PRIOR TO THE COMMENCEMENT OF ANY CONSTRUCTION OR SITE DEVELOPMENT BE PLACED WITHIN ONE OF THE REACH RANGES SPECIFIED IN SECTION 308, ICC A117.1. THEY THE EXIT ENCLOSURE. PENETRATIONS MUST BE PROTECTED. SHALL BE INSTALLED IN GROUP R-2 COLLEGE AND UNIVERSITY BUILDINGS IN THE <br /> ACTIVITY, THE CONTRACTOR AND/OR ARCHITECT SHALL SCHEDULE A PRECONSTRUCTION SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, FOLLOWING LOCATIONS: <br /> MEETING WITH THE PROJECT TEAM MEMBERS FOR THE PURPOSE OF PINCHING, OR TWISTING OF THE WRIST. THE MAXIMUM FORCE REQUIRED TO ACTIVATE THE 19. EQUIPMENT IS PROHIBITED IN EXIT ENCLOSURES EXCEPT FOR EQUIPMENT 1. COMMON SPACES OUTSIDE OF DWELLING AND SLEEPING UNITS. <br /> ANSWERING INITIAL QUESTIONS, CLARIFYING AREAS OF CONCERN,AND FORMALIZING A PARTS SHALL BE 5 POUNDS. NECESSARY FOR INDEPENDENT PRESSURIZATION, LIGHTING OF THE EXIT ENCLOSURE, 2. LAUNDRY ROOMS, MECHANICAL EQUIPMENT ROOMS, AND STORAGE RMS. <br /> CONSTRUCTION ADMINISTRATION PROCESS. THE MEETING(S) SHALL INCLUDE THE SPRINKLER PIPING, STANDPIPES, ELECTRICAL EQUIPMENT FOR FIRE DEPARTMENT 3. ALL INTERIOR CORRIDORS SERVING SLEEPING OR DWELLING UNITS. <br /> ARCHITECT, GENERAL CONTRACTOR, OWNER, LANDSCAPE ARCHITECT, STRUCTURAL g. IN TYPE B UNITS, LIGHTING CONTROLS, ELECTRICAL SWITCHES AND RECEPTACLE COMMUNICATION AND SPRINKLER MONITORING, AND UNIT HEATERS REQUIRED TO <br /> ENGINEER, CIVIL ENGINEER, GEOTECHNICAL ENGINEER,AND WATER INTRUSION OUTLETS, ENVIRONMENTAL CONTROLS,AND USER CONTROLS FOR SECURITY OR INTERCOM PROTECT FIRE PROTECTION EQUIPMENT FROM FREEZING. REQUIRED SMOKE ALARMS IN DWELLING UNITS AND SLEEPING UNITS SHALL BE <br /> CONSULTANT. SYSTEMS SHALL BE PROVIDED WITH A CLEAR FLOOR SPACE AND BE PLACED WITHIN ONE INTERCONNECTED WITH THE FIRE ALARM SYSTEM IN ACCORDANCE WITH NFPA 72. <br /> OF THE REACH RANGES SPECIFIED IN ANSI 308, ICC A117.1. LISTED SINGLE-AND MULTIPLE-STATION SMOKE ALARMS COMPLYING WITH UL 217 <br /> SITE NOTES FIRE RESISTIVE RATED CONSTRUCTION NOTES SHALL BE INSTALLED IN ACCORDANCE WITH SECTIONS 907.2.11.1 THROUGH 907.2.11.4 <br /> h. "CLEAR FLOOR SPACE" IS MIN. 30"X48" PER ANSI 305.3. AND NFPA 72. <br /> 1. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF EXISTING SITE CONDITIONS, 1. THROUGH PENETRATIONS IN FIRE-RESISTANCE-RATED WALLS SHALL BE <br /> DISTANCES, AND TOPOGRAPHIC CONTOURS. SITE CONDITIONS SHOWN ARE FROM i. OPERABLE PARTS SHALL BE PLACED BETWEEN 15"AND 48"ABOVE THE FLOOR IN AN PROTECTED. THEY SHALL BE INSTALLED AS TESTED IN AN APPROVED FIRERESISTANCE- 12. MANUAL FIRE ALARM BOXES SHALL BE LOCATED NOT MORE THAN 5 FEET <br /> OWNER-PROVIDED INFORMATION, SURVEYS BY OTHERS,AND PUBLIC RECORDS. THE AREA WITH UNOBSTRUCTED FORWARD OR SIDE REACH. WHEN THERE IS AN OBSTRUCTION RATED ASSEMBLY OR PROTECTED WITH AN APPROVED PENETRATION FROM THE ENTRANCE TO EACH EXIT AT EVERY FLOOR LEVEL. THE TRAVEL <br /> ARCHITECT IS NOT RESPONSIBLE FOR THE ACCURACY OF THE SURVEY OR EXISTING OF 24" MAX WIDTH AND 34"MAX HEIGHT, THE OPERABLE PARTS SHALL BE NO HIGHER THAN FIRESTOP SYSTEM. DISTANCE TO THE NEAREST BOX SHALL NOT EXCEED 200 FEET. THE HEIGHT TO <br /> SITE INFORMATION. 46"ABOVE THE FLOOR. WHEN THERE IS AN OBSTRUCTION OF 25" MAX WIDTH IN A SPACE THE ACTIVATING HANDLE OR LEVER OF THE BOX SHALL BE BETWEEN 42 AND 48 <br /> ALLOWING A FORWARD APPROACH, THE OPERABLE PARTS SHALL BE NO HIGHER THAN 44" 2. LISTED ELECTRICAL BOXES MAY BE INSTALLED IN FIRE-RESISTANCE-RATED WALLS INCHES ABOVE THE FLOOR. IFC 907.4. <br /> 2. THE CONTRACTOR SHALL VERIFY THE LOCATIONS OF ALL UTILITIES BEFORE ABOVE THE FLOOR. PROVIDED THEY HAVE BEEN TESTED AND ARE INSTALLED IN ACCORDANCE WITH THE <br /> BEGINNING CONSTRUCTION BY RETAINING A UTILITY LOCATION SERVICE AND MARKING ANSI 308, ICC A117.1. INSTRUCTIONS INCLUDED IN THE LISTING. OUTLETS ON OPPOSITES SIDE OF THE 13.ANNUNCIATOR PANELS SHALL BE LOCATED INSIDE THE BUILDING AT THE MAIN ., <br /> ALL UNDERGROUND UTILITY LOCATIONS. ANY UTILITY LOCATIONS SHOWN ON THE WALL SHALL BE SEPARATED BY 24" HORIZONTALLY, SOLID FIREBLOCKING, LISTED ENTRANCE.ALARM PANELS AND ANNUNCIATORS SHALL NOT OBSTRUCT EXITING. <br /> DRAWINGS ARE BASED ON AVAILABLE RECORDS AND ARE SHOWN FOR CONVENIENCE j. BATHROOMS REQUIRE CLEAR FLOOR SPACES, CLEARANCES AROUND, BETWEEN, AND PUTTY PADS, OR OTHER LISTED MATERIALS AND METHODS. IFC 907.8.1. <br /> ONLY. UTILITIES MAY BE PRESENT BUT NOT SHOWN ON THE DRAWINGS. CARE SHOULD ADJACENT TO FIXTURES, REINFORCING FOR GRAB BARS, AND OTHER ITEMS SHOWN IN THE <br /> BE TAKEN TO AVOID DAMAGE TO EXISTING UTILITIES. THE CONTRACTOR SHALL DRAWINGS. THE CONTRACTOR OR OWNER SHALL NOT MAKE DIMENSIONAL CHANGES TO 3. PENETRATIONS OF A FLOOR, FLOOR/CEILING ASSEMBLY OR THE CEILING 14. VISIBLE ALARM NOTIFICATION APPLIANCES SHALL BE PROVIDED IN PUBLIC <br /> COORDINATE CONNECTION LOCATIONS AND ELEVATIONS WITH THE UTILITY COMPANIES. ANY BATHROOM WITHOUT THE APPROVAL OF THE ARCHITECT. MEMBRANE OF A ROOF/CEILING MEMBRANE SHALL BE ENCLOSED BY SHAFTS IN AND COMMON AREAS. ALL DWELLING UNITS SHALL BE PROVIDE WITH THE <br /> RELOCATION OF UTILITIES, IF NECESSARY, SHALL BE THE RESPONSIBILITY OF THE ACCORDANCE WITH IBC SECTION 707. CAPABILITY TO SUPPORT VISIBLE ALARM NOTIFICATION IN ACCORDANCE WITH <br /> CONTRACTOR. k. SHOWER COMPARTMENTS AND WALLS ABOVE BATHTUBS WITH INSTALLED ICC/ANSI 117.1.AUDIBLE ALARM NOTIFICATION SYSTEMS SHALL HAVE A DISTINCT <br /> SHOWER HEADS SHALL BE FINISHED WITH A SMOOTH, NONABSORBENT SURFACE TO A 4. CAN LIGHTS IN FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL BE SOUND AND SHALL BE LOUD ENOUGH TO PROVIDE A SOUND-PRESSURE LEVEL AT <br /> 3. THE CONTRACTOR SHALL EXECUTE AND COMPLETE ALL WORK ON ADJACENT HEIGHT OF NOT LESS THAN 70 INCHES ABOVE THE DRAIN INLET. BUILT-IN TUBS WITH BOXED ON FOUR SIDES AND TOP WITH 5/8" GYPSUM WALLBOARD. HVAC FANS OR LEAST 15 DECIBELS (DBA)ABOVE THE MAX SOUND LEVEL. IFC 907.10 <br /> PROPERTIES AND PUBLIC RIGHTS-OF-WAY THAT IS REQUIRED BY CONSTRUCTION SHOWERS SHALL HAVE WATERPROOF JOINTS BETWEEN THE TUB AND ADJACENT DIFFUSERS SHALL BE BOXED ON FOUR SIDES AND TOP WITH 5/8"GYPSUM WALLBOARD. <br /> EASEMENT AGREEMENTS WITH NEIGHBORING PROPERTY OWNERS, PRIVATE WALL. SBC 1210.3, 1210.4. DUCTS SHALL BE WRAPPED W/1 1/2" HIGH-DENSITY MINERAL FIBER OR 3 1/2" 15. CARBON MONOXIDE ALARMS SHALL BE INSTALLED IN ALL GROUP R OCCUPANCIES <br /> CONTRACT DOCUMENTS WITH THE SEATTLE DEPARTMENT OF TRANSPORTATION, FIBERGLASS, SECURED IN PLACE FOR AT LEAST 10' FROM OPENING. PER WA STATE AMENDMENT 908.7 <br /> STREET USE PERMITS, OR ANY OTHER AGREEMENT OR CONTRACT.ALL I. AS A FORMALDEHYDE REDUCTION MEASURE,ALL STRUCTURAL COMPONENTS <br /> IMPROVEMENTS AND REPAIRS TO SIDEWALKS, ALLEYS, STREETS AND NEIGHBORING SUCH AS SOFT PLYWOOD, PARTICLE BOARD, WAFER BOARD AND OSB SHALL BE 5. JOINTS INSTALLED IN OR BETWEEN FIRE-RESISTANCE-RATED WALLS, FLOORS OR SOUND TRANSMISSION NOTES <br /> PROPERTIES SHALL BE COORDINATED TO MINIMIZE THE IMPACT ON THE PUBLIC AND TO IDENTIFIED AS "EXPOSURE 1", "EXTERIOR", OR"HUD-APPROVED". FLOOR/CEILING ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES HALL BE ` <br /> MAINTAIN ACCESS TO NEIGHBORING PROPERTIES. THE CONTRACTOR SHALL MAKE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM HAVING THE SAME FIRE 1. AIR-BORNE SOUND: WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES <br /> ARRANGEMENTS AND SECURE NECESSARY PERMITS WHEN CONSTRUCTION REQUIRES m. INTERIOR WALL AND CEILING FINISHES SHALL BE CLASSIFIED IN ACCORDANCE RATING AS THE ASSEMBLY IN OR BETWEEN WHICH IT IS INSTALLED. SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR SERVICE <br /> STREET OR SIDEWALK CLOSURES. WITH ASTM E 84 WITH A MINIMUM OF CLASS C THROUGHOUT. CLASS C HAS A FLAME AREAS SHALL HAVE A SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 <br /> SPREAD INDEX OF 76-200 AND SMOKE-DEVELOPED INDEX OF 0-450. 6. OPENINGS IN FIRE-RESISTANCE-RATED WALLS SHALL BE PROTECTED, AND SHALL (45 IF FIELD TESTED). PENETRATIONS OR OPENINGS IN ONSTRUCTION # DATE DESCRIPTION <br /> 4. IF ANY HAZARDOUS MATERIAL, INCLUDING BUT NOT LIMITED TO ASBESTOS OR COMPLY WITH THE TESTING, INSTALLATION,AND LABELING REQUIREMENTS OF IBC ASSEMBLIES FOR PIPING, ELECTRICAL DEVICES, RECESSED CABINETS, <br /> POLYCHLORINATED BIPHENYL (PCB), IS ENCOUNTERED ON THE SITE BY THE <br /> n. BATHTUB ENCLOSURES SHALL NOT HAVE TRACKS INSTALLED ON THE RIM OF 715 AND NFPA 80. BATHTUBS, SOFFITS, OR HEATING,VENTILATING OR EXHAUST DUCTS SHALL BE <br /> CONTRACTOR, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE OWNER. THE BATHTUB. SEALED, LINED, INSULATED OR OTHERWISE TREATED TO MAINTAIN THE <br /> 5. PRIOR TO BEGINNING ANY DEMOLITION WORK, THE OWNER OR CONTRACTOR 7. PENETRATIONS BY AIR DUCTS AND AIR TRANSFER OPENINGS IN FIRE-RESISTANCERATED REQUIRED STC. UNIT ENTRY DOORS SHALL BE TIGHT FITTING TO THE FRAME AND <br /> SHALL SUBMIT A"NOTICE OF INTENT"TO THE PUGET SOUND CLEAN AIR AGENCY o. KITCHENS REQUIRE CLEAR FLOOR SPACES, CLEARANCES AROUND, BETWEEN, ASSEMBLIES SHALL COMPLY WITH IBC SECTION 716. SILL. UNIT ENTRY DOOR ASSEMBLIES SHALL HAVE A STC OF NOT LESS THAN 28. <br /> (PSCAA)AND FULFILL THEIR REQUIREMENTS. AND ADJACENT TO FIXTURES,APPLIANCES, CABINETS, COUNTERS AND WALLS, AND IBC 1207.2. <br /> OTHER ITEMS SHOWN IN THE DRAWINGS. THE CONTRACTOR OR OWNER SHALL NOT 8. FIREBLOCKING SHALL BE INSTALLED IN COMBUSTIBLE CONCEALED LOCATIONS AS DEVELOPMENT <br /> 6. NEW WATER MAINS, FIRE HYDRANTS,AND TEMPORARY FIRE DEPARTMENT MAKE DIMENSIONAL CHANGES TO ANY KITCHEN WITHOUT THE APPROVAL OF THE SPECIFIED IN SECTION 717.ACCEPTABLE FIREBLOCKING MATERIALS ARE DESCRIBED 2. STRUCTURE-BORNE SOUND: FLOOR/CEILING ASSEMBLIES SEPARATING <br /> ACCESS SHALL BE INSTALLED, INSPECTED, AND APPROVED BY THE FIRE DEPARTMENT ARCHITECT. IN 717.2.1. FIREBLOCKING SHALL BE INSTALLED IN STUD WALLS, INCLUDING FURRED DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR SERVICEA REAS 1830 BICKFORD AVE, <br /> PRIOR TO THE COMMENCEMENT OF COMBUSTIBLE CONSTRUCTION. WALLS,VERTICALLY AT THE CEILING AND FLOOR LEVELS, AND HORIZONTALLY AT 10' SHALL HAVE AN IMPACT INSULATION CLASS (ICC) RATING OF NOT LESS THAN SUITE 201 <br /> - p. IN TYPE A UNITS, WASHING MACHINES AND CLOTHES DRYERS REQUIRE A CLEAR INTERVALS. FIREBLOCKING SHALL ALSO BE INSTALLED AT CONNECTIONS BETWEEN 50 (45 IF FIELD TESTED) SNOHOMISH, WA 98290 <br /> INTERIOR ENVIRONMENT FLOOR SPACE, POSITIONED FOR PARALLEL APPROACH, CENTERED ON EACH VERTICAL STUD WALL SPACES AND THE HORIZONTAL SPACES CREATED BY A SERIES 206.755.1290 <br /> APPLIANCE. ALL OPERABLE PARTS SHALL COMPLY WITH SECTION 309, ICC A117.1, OF JOISTS;AT CONNECTIONS BETWEEN VERTICAL AND HORIZONTAL SPACES AT 3. JOINTS IN THE PERIMETER OF WALLS OR FLOOR/CEILING ASSEMBLIES <br /> 1. OCCUPIABLE SPACES, HABITABLE SPACES, AND CORRIDORS SHALL HAVE A INCLUDING THE REACH RANGES SPECIFIED IN ANSI 308, ICC A117.1. TOP LOADING SOFFITS, DROPPED CEILINGS, ETC;AT CEILING AND FLOOR OPENINGS AROUND PIPES, SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR SERVICE <br /> CEILING HEIGHT OF NOT LESS THAN 7-6". BATHROOMS, TOILET ROOMS, KITCHENS, MACHINES SHALL HAVE THE DOOR TO THE LAUNDRY COMPARTMENT 36" MAX ABOVE DUCTS, ETC; BETWEEN EXTERIOR WALL FINISHES AND ARCHITECTURAL TRIM. AREAS SHALL BE ACOUSTICALLY SEALED WITH A PERMANENT RESILIENT <br /> STORAGE ROOMS AND LAUNDRY ROOMS SHALL BE PERMITTED TO HAVE A CEILING THE FLOOR. FRONT LOADING MACHINES SHALL HAVE THE BOTTOM OF THE OPENING MATERIAL APPROVED FOR SUCH PURPOSE. CONDUITS, DUCTS, PIPES AND <br /> HEIGHT OF NOT LESS THAN 7'-0". TO THE LAUNDRY COMPARTMENT BETWEEN 15"AND 34"ABOVE THE FLOOR. 9. DRAFTSTOPPING IS NOT REQUIRED,AS THE BUILDING IS SPRINKLERED PER IBC VENTS WITHIN SUCH WALL OR FLOOR/CEILING ASSEMBLIES CAUSING VIBRATION <br /> 903.3.1.1. IBC 717.3.2. SHALL BE REASONABLY ISOLATED FROM THE BUILDING CONSTRUCTION AT 1020 North Broadway <br /> 2. PROVIDE AN ATTIC ACCESS OPENING AT ALL ATTIC SPACES AT LEAST 30" HIGH. q. IN TYPE B UNITS, WASHING MACHINES AND CLOTHES DRYERS REQUIRE A CLEAR POINTS OF SUPPORT.ALL OPENINGS THROUGH WHICH SUCH ITEMS PASS SHALL Everett, WA 98403 <br /> THE ACCESS OPENING SHALL BE A MINIMUM OF 20"X 30"WITH AT LEAST 30" OF FLOOR SPACE, POSITIONED FOR PARALLEL APPROACH, CENTERED ON EACH 10. REFER TO EGRESS NOTES, INTERIOR ENVIRONMENT NOTES, DOOR NOTES, WALL HAVE THE EXCESS OPENING FULLY SEALED. IBC 1207.3. <br /> HEADROOM AT OR ABOVE THE OPENING. APPLIANCE. IF NECESSARY FOR GREATER ACCESSIBILITY, THE CLOSET DOORS MAY TYPES, AND DETAILS FOR ADDITIONAL REQUIREMENTS RELATED TO FIRE-RESISTANCE <br /> BE REMOVED AND THE RATED CONSTRUCTION 4. ELECTRICAL OUTLET BOXES AND OTHER WALL PENETRATIONS SHALL NOT BE <br /> 3. PROVIDE AN 18"X 24" MINIMUM ACCESS OPENING AT ALL CRAWL SPACES. PLACED BACK-TO-BACK AND SHALL BE OFFSET BY NOT LESS THAN 12 INCHES FROM <br /> OUTLETS IN THE OPPOSITE WALL SURFACE. THE BACK AND SIDES OF BOXES SHALL BE GENERAL NOTES <br /> 4. PUBLIC RESTROOM FLOORS SHALL HAVE A SMOOTH, HARD, NONABSORBENT SEALED WITH 1/8" RESILIENT SEALANT AND BACKED BY AT LEAST 2"THICK MATERIAL <br /> SURFACE EXTENDING UPWARD ONTO THE WALLS AT LEAST 6 INCHES PER SBC 1210.1. FIBER INSULATION. IBC 1207.3. <br /> WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, <br /> HARD, NONABSORBENT SURFACE TO A HEIGHT OF AT LEAST 4 FEET ABOVE THE 5. SPACES OR SHAFTS CONTAINING AIR CONDITIONING, REFRIGERATION OR <br /> FLOOR PER SBC 1210.2. VENTILATING EQUIPMENT, ELEVATOR MACHINERY, OR OTHER MECHANICAL <br /> EQUIPMENT SHALL BE SEPARATED BOTH VERTICALLY AND HORIZONTALLY FROM DATE: Issue Date <br /> 5. ACCESSORIES SUCH AS GRAB BARS, TOWEL BARS, PAPER DISPENSERS AND ADJOINING DWELLING UNITS BY CONSTRUCTION DESIGNED TO PROVIDE A <br /> SOAP DISHES, PROVIDED ON OR WITHIN WALLS, SHALL BE INSTALLED AND SEALED TO MINIMUM STC RATING OF 50. IBC 1207.6. <br /> PROTECT STRUCTURAL ELEMENTS FROM MOISTURE. <br /> 6. DESIGN AND MATERIALS FOR SOUND TRANSMISSION CONTROL SHALL NOT <br /> IMPAIR THE FIRE--RESISTANT INTEGRITY OF SEPARATING WALLS OR FLOOR/CEILING <br /> ASSEMBLIES. SHEET: <br /> AN . 02 <br />