O 0 <br />Structural <br />General: <br />1. Section 1/A304 shows the wall studs extending to the underside of the pre -fabricated <br />trusses, which do not provide out -of -plane support for the walls. Studs are required to be <br />continuous to floor, ceiling, or roof diaphragms per IRC Section R602.3 unless designed by <br />acceptable engineering practice per Section R301.1.3. Note that the maximum roof <br />height of approximately 14 feet exceeds the story height of 11'-7" per Section R301.3(1) <br />and the allowable stud height of 10 feet for 2x4 framing per Table R602.3(5). <br />Response: The design of the north and south walls have been revised. The gable <br />trusses have been changed to scissor trusses and the stud wall has been framed to the <br />bottom chord of the trusses. The max stud height is = <br />2. Section 1/A303 specifies the roof framing as pre-engineered roof trusses. See IRC Section <br />106.1.1. The following comments should be addressed: <br />a. The spacing of the trusses should be specified. <br />Response: (See new sheet A105) Truss spacing noted <br />b. The construction drawings should specify the minimum required design loads for the <br />trusses, including but not limited to live, snow, and wind loading criteria. See IRC <br />Section R802.10.1. <br />Response: (See new sheet A105) Load requirements noted <br />c. The construction drawings should specify that the trusses include bracing per IRC <br />Section R802.10.3. <br />Response: (See new sheet A105) Bracing requirements noted <br />3. The minimum fastening requirements should be specified. See IRC Table R602.3(1). A <br />schedule should be provided including but not limited to: <br />a. Wall studs to top and bottom plates. <br />b. Top plate splices. <br />c. Built-up headers. <br />d. Header to supporting framing (e.g., king and jack studs). <br />e. Wall corners. <br />f. Roof sheathing. <br />g. Roof framing (i.e., 2x4 outriggers per Section 1/A304). <br />h. Roof trusses to wall framing. <br />i. Roof edge nailing. <br />j. Truss blocking at wall supports. <br />Response: Fastening schedule added to set on new sheet A600. <br />Foundation: <br />4. The drawings should specify a minimum concrete strength of 3,000 psi per IRC Table <br />R402.2 for foundations with moderate weather exposure. <br />Response: Foundation Plan added to set (sheet A101) with a note specifying the <br />concrete strength. Lf4 <br />Page 2 ~� <br />