• May 23, 2018 <br /> Mr.Tony Lee <br /> Snohomish County Courthouse Renovation/Addition <br /> Page <br /> 4) It should be clarified if the existing building is currently provided with an emergency <br /> voice/alarm communication system as specified in Section 907.2.1.1. <br /> Response:Per earlier agreement with the City, new fire alarm system with voice/alarm <br /> annunciation will be provided in areas of the existing building that are being <br /> renovated/remodeled. Existing areas that are not being renovated/remodeled will not be <br /> upgraded to the new fire alarm system. The existing fire alarm system devices are to <br /> remain. The existing system will report to the new system. The existing system is not a <br /> voice communication system. <br /> 5) Wainscoting should be shown for the toilet rooms in elevations 17 & 18 on Sheet IQ-201. <br /> Section 1210.2.2 <br /> Response: Wainscoting is not required based on Exception #2. These toilet rooms do not <br /> have more than one water closet and are not accessible to the public. <br /> Construction <br /> 1) Listings for both the TGP Firelight Plus and Tyco sprinkler assemblies should be provided. <br /> The specific proposed product should be shown to be within the listing specifications for <br /> the proposed use and minimum fire-rating per code.Section 716.2 <br /> Response: The individual listings for each product are attached along with the Data Sheet <br /> on the use of these two products used together as an Alternate Means of Compliance in <br /> accordance with IBC 104.11. <br /> 2) A listing for WON doors should be provided. Section 703.2 <br /> Response:The listing for the Won-Door is attached. <br /> 3) Fire resistive listings and assembly details should be provided for the steel columns, <br /> beams, roof/ceiling and floor/ceiling assemblies.Sections 703.1& 704.1 <br /> a. Special inspection requirements should be noted on the plans for the sprayed fire- <br /> resistant materials. Section 1705.4 <br /> Response: UL assemblies have been included in the 100% CD set. Spray-on fireproofing is <br /> indicated on sheet GV-204. Intumescent coating is indicated on sheet GV-205. The roof <br /> assembly is indicated on sheet GV-205. The floor/ceiling assembly is indicated on sheet <br /> GV-204. <br /> 11111 <br />