Laserfiche WebLink
• May 23, 2018 <br /> Mr.Tony Lee <br /> Snohom'sh County Courthouse Renovation/Addition <br /> Page 6 8 <br /> 4) A two-way communication system should be shown at each landing of the elevator bank <br /> above or below the level of exit discharge in accordance with Section 1009.8.The system <br /> and direction requirements should also be shown. <br /> Response:Each elevator lobby in the addition does have two-way communications <br /> (intercom)that reports to master station located in new main entrance vestibule in the <br /> addition. We are not showing these in the existing building elevator lobbies. <br /> 5) Doors ST4-1, ST2-1,ST2-1A,ST1-B, 2400, 2221,3400, 4222, ST1-4A&4600a should be <br /> shown with panic hardware unless no lock or latch is provided.Section 1010.1.10 <br /> Response:Panic hardware(note#4 "Exit Device"in the Door Schedule Notes and Legend) <br /> for these doors have been added to the Door Schedule on sheets 1-601&1-602. <br /> 6) Door 4600B should swing in the direction of travel (even though it is not a required exit). <br /> Section1010.1 <br /> Response: The door swing has been changed. Refer to Sheet IF-104. <br /> • 7) The stairs to the Marshal Station should be shown with handrails(with extensions)on each <br /> side.Section 1011.11 <br /> Response: Due to the limited width and limited occupant load, this was considered an <br /> aisle in the main lobby Assembly space. In accordance with IBC 1029.16, stepped aisles <br /> require a handrail on one or both sides. <br /> 8) Braille exit signs complying with ICC A117.1 should be shown adjacent to each exit <br /> stairway and exit discharge.Section 1013.4 <br /> Response:Braille exit sign elevations, details and messages have been shown on revised <br /> detail Sheets IG-201 and IG-202. Sign location plans have been updated to show the <br /> placement of each sign at exits. <br /> 9) The guards shown in Detail 11 on Sheet L-312 should be shown to prevent the passage of <br /> a 4"sphere(to include a conservative amount of material deflection).Section 1015.4 <br /> Response: The cable infill rails will be spaced at 4"apart. Dimensions have been added to <br /> the detail to reflect this. <br /> 10)All (new)doors into Stair#2 should be shown as minimum 90-minute rated assemblies. <br /> Section 1023.4 <br /> Response:All of the doors going into Stair#2 are reworked for new hardware and/or <br /> relocated existing doors. <br /> • <br />