Mr. Mark Thunberg <br />Snohomish County Property Management <br />Plan Check Number: B1802-011, First Review (Structural) <br />June 18, 2018 <br />5. Section 1.2.2 "Materials — Concrete" states that the design is based on light -weight concrete in <br />the composite decks. The "Concrete", "Composite Floor System", and "Steel Composite Deck" <br />sections of the General Notes on Sheet S-002 do not appear to specify light -weight concrete. <br />The notes should be reviewed and revised as needed. See IBC Section 107.2.1. <br />6. Section 2.1 "Materials" of the structural calculations states that the design of the lateral system <br />(i.e., concrete shear walls) is based on concrete strength of f'C=7,000 psi. The "Concrete" <br />section of the General Notes on Sheet S-002 states a strength of 6,000 psi. The structural <br />notes should be revised. See IBC Section 1901.5 Item 1. <br />7. Section 2.1 "Materials" of the structural calculations state that the reinforcing steel for the <br />"ties" shall be ASTM A706 Grade 80. The "Reinforcing Steel" section of the General Notes on <br />Sheet 5-002 specifies ASTM A615 Grade 60 reinforcement unless otherwise noted. The <br />"Special Ductile Quality Reinforcing Steel" section specifies A706 reinforcement, but does not <br />specify Grade 80. The concrete shear wall design on Sheets S-301 through S-311 does not <br />appear to specify Grade 80 reinforcement. The reinforcement qualifying as "ties" should be <br />clarified. The drawings should be revised to specify ASTM A706 Grade 80 reinforcement where <br />required. See IBC Section 1901.5 Item 2. <br />8. The "Reinforcing Steel" section of the General Notes on Sheet S-002 states that welding of <br />reinforcing bars is prohibited except where approved by the engineer. However, the drawings <br />specify welding in multiple locations including connections between collectors and concrete <br />shear walls. See Details 16/S-601 and 17/5-603 as examples. The note should be revised for <br />consistency with the drawings. The note should require that all welded reinforcement be ASTM <br />Grade A706 unless use of an alternate material is approved by the engineer. The note shall <br />require a mill test report for reinforcing bars not complying with ASTM A706 to verity <br />weldability. See IBC Section 1901.2 and ACI 318-14 Section 26.6.4.1(a). <br />9. Sheet 5-201 includes a 13'-6" dimension near Grid J/19.1 that appears intended to locate a <br />footing and column at Grid H.6/19.1. However, the dimension does not align with the footing <br />and column, and does not appear to correspond to any other structural elements. The <br />dimension should be revised and revised as needed. See IBC Section 1603.1. <br />10. Detail 17/5-603 shows a drag connection with (3) #6 bars connecting to an embedded angle. <br />The detail does not appear to specify a connection between the bars and angle. The detail <br />should be reviewed and revised as needed. See IBC Section 107.2.1. <br />11. The locations of the braced frames in Partial Plan 14/S-251 appears to be incorrect. The <br />frames appear intended to occur on grid lines per Partial Plan 19/S-251. In addition, the <br />Section 15/5-321 reference appears mislocated. The plan should be revised. See IBC Section <br />1603.1. <br />Page 3 of 11 <br />CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425) 257-8810 . Fax (425) 257-885 <br />