• <br /> Egress: <br /> 5. The common path of egress travel to the exterior exits exceeds 75 feet for Room 11 and the adjacent rooms, with <br /> the longest paths occurring for Rooms 13 and 16. Two exits are required. The maximum exit access travel distance <br /> for an unsprinklered 8-occupancy building is 200 feet. The second route for both Rooms 13 and 16 exceeds the <br /> travel distance. Note that the route through the Reception Room 01 is not valid as a second path where the first <br /> path travels through Door 11A. The egress paths shall be revised. See IBC Tables 1006.2.1 and 1017.2,and IEBC <br /> Section 801.3. <br /> Response: Our understanding of the code is that the common path of egress is the maximum <br /> distance an occupant can travel before having two different exit path options,this is true for the exit <br /> path from both Room 13 and Room 16.According to the 2015 International Code Commentary the <br /> "common path of travel stops when the occupant has a choice of at least two exits, and overall travel <br /> distance stops when an occupant gets to the closest exit"(see attached page). Our understanding of <br /> the maximum travel distance is that it is only applied to the nearest exit. In our case both Room 13 <br /> and 16 are within 200'from their nearest exit. In the case of the travel path exiting to the south the <br /> side lobby is a rated exit enclosure, so the travel distance stops the doors leading to it.The diagram <br /> has been revised to more clearly show our interpretation of the code sections. We have also included <br /> the relevant section from the 2015 ICC Code Commentary with highlighted excerpts to support our <br /> methods attached to this letter. <br /> 6. The Occupancy and Exiting Diagram on Sheet A0.02 shall specify additional exit signs. Exit signs shall be provided <br /> at the following locations:north and south ends of Room 11,Door 018,Main Lobby exterior doors,Corridor south <br /> of the Main Lobby,hallway outside Interview Room 06, and the interior and exterior double doors at the south <br /> Lobby. Where existing exit signs occur, these shall be indicated on the plans. Intermediate exit signs shall include <br /> direction arrows where door signs are not readily visible. The lighting,including existing locations,shall specify a <br /> minimum 90-minute uninterrupted supply power per IBC Section 1013.6.3. See IBC Section 1013.1 and IEBC Section <br /> 801.3. <br /> Response: Exit signs have been added at the locations mentioned in your comment and a note <br /> regarding exit sign illumination power supply has been added on sheet A6.01. <br /> 7. Means of egress illumination shall be provided per IBC Section 1008. The lighting shall specify a minimum 90- <br /> minute uninterrupted supply power per IBC Section 1008.3.4. Where existing systems occur, they shall be indicated <br /> on the plans. See IEBC Section 801.3. <br /> Response: A note regarding egress illumination has been added on sheet A6.01. <br /> 8. The exterior landings for doorways serving an occupant load of 50 or more shall be provided with emergency <br /> lighting. The lighting shall specify a minimum 90-minute uninterrupted supply power per IBC Section 1008.3.4. See <br /> IBC Sections 1008.3.2 Item 5 and 1010.1.6. Where existing systems occur,they shall be indicated on the plans. See <br /> IEBC Section 801.3. <br /> Response: A note regarding emergency lighting at exterior landing for doorways has been added on <br /> sheet A6.01. <br /> 9. The Site Plan on Sheet A1.00 appears to show modifications to the existing sidewalk on the north side of the <br /> building. See IBC Sections 107.2.1 and 1102.1. The following comments shall be addressed: <br /> a. The extent of the modifications is not clear and shall be clarified on the site plan. Details for the sidewalk <br /> modifications should be provided. <br /> Response: Please see A1.00 for revised drawings and notes describing the work. The <br /> approach for accessibility for the parking lot has been modified to use curb cuts at each access aisle <br /> instead of the sloped walkway. <br /> b. The slopes and cross-slopes shall be specified in the drawings. See IBC Sections 1012.2 and 1012.3,and <br /> ICC A117.1-09 Sections 405.2 and 405.3. <br /> Response: Please detail 2/A1.00 describing the requirements for the curb cuts at each <br /> access aisle. <br /> c. The ramps shall specify a slip-resistant surface per IBC Section 1012.7.1. <br /> Response: See detail 2/A1.00 for curb cuts detail and call outs. <br /> d. Ramps with a rise exceeding 6 inches shall be provided with handrails per IBC Section 1012.8. <br /> Response: Because the sloped walkways have been removed and replaced with curb <br /> cuts this comment no longer applies. <br /> Project#B1903-041 — 1010 SE Everett Mall Way <br /> In <br />