2015 Washington State Energyftde Compliance Forms for Commercial, R2 and R3 overAgLaries and all R1 - Page 7 of 20
<br />209 s Washinntnn State Fnemv Cnde Cmmnlinnne Fnrms for Cnmmercial Ruildinns including R2 & R3 over 3 stories and all R1 Revised January 2017
<br />Project Title: SnoPUD75BC Date 18/02/27
<br />The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
<br />Washington State Energy Code, Commercial Provisions.
<br />Applicable
<br />Code Section
<br />Code Provision
<br />Information Required - Must be in permit documents
<br />Location in
<br />Building Department
<br />( es,no,na)
<br />Documents
<br />Notes
<br />C403.2.4.10
<br />Group R2 / R3 dwelling
<br />For primary space conditioning system, indicate 5-2 programmable thermostats capable of two
<br />na
<br />C403.2.4.11
<br />units, Group R2 sleeping
<br />setback periods per day; for all thermostats indicate purpose (heating only, cooling only, or
<br />units
<br />both), required temperature range and at minimum a 10°F deadband; or exception taken
<br />Indicate method of ventilation air delivery (natural or mechanical) for each zone
<br />If mechanically delivered, indicate that systems are configured to provide not more than 150:/
<br />NA
<br />C403.2.6
<br />Ventilation
<br />of, but at least the minimum required volume of outdoor air to each zone per IMC, ASHRAE
<br />C403.2.11.4
<br />62.1 or other applicable code (WAC, OSHA, etc); or exception taken
<br />If delivered via natural ventilation, identify required elements per IMC including minimum
<br />openable area to the outdoors or qualifying adjoining spaces
<br />Identify spaces > 500 sf with occupant load > 25 people/1,000 sf per IMC; for each space
<br />indicate whether it is served by an HVAC system with total design OSA > 3,000 cfm, and / or
<br />na
<br />C403.2.6.2
<br />Demand controlled
<br />the system has airside economizer or automatic modulating OSA damper; indicate OSA
<br />ventilation
<br />controls are configured to provide demand controlled ventilation or provide supporting
<br />documentation for applied exception
<br />For gyms, classrooms, auditoriums and conference rooms > 500 sf, indicate occupancy -based
<br />na
<br />C403.2.6.3
<br />Occupancy sensors
<br />OSA control when space is unoccupied and method (closes OSA damper or shuts -off
<br />equipment); or alternate means provided to automatically reduce OSA when space is partially
<br />occupied
<br />C403.2.6.4
<br />Enclosed loading dock
<br />For enclosed loading docks, indicate ventilation / exhaust system method of activation (gas
<br />na
<br />C403.2.6.4.1
<br />ventilation
<br />detection system for CO and NO2, or occupancy sensors), and control method (staged or
<br />modulating)
<br />C403.2.6.4
<br />Enclosed parking garage
<br />For enclosed parking garages, indicate ventilation / exhaust system activated by gas detection
<br />na
<br />C403.2.6.4.2
<br />ventilation
<br />system for CO and NO2, and control method (staged or modulating); or exception taken
<br />Provide calculations that show a balanced accounting of total kitchen exhaust (include all
<br />hoods) with % of: supply air, transfer air from adjacent spaces, and make-up air; if applicable,
<br />indicate that direct make-up air to each hood does not exceed 10%of hood exhaust
<br />na
<br />C403.2.7.1
<br />Kitchen exhaust hoods
<br />For kitchens with total hood exhaust exceeding 2,000 cfm, indicate exhaust air rate per Table
<br />C403.2.7.1 and compliance method (DCV, energy recovery, or transfer air that would
<br />otherwise be exhausted)
<br />na
<br />C403.2.7.2
<br />Laboratory exhaust systems
<br />Refer to Systems Requiring Energy Recovery for requirements
<br />Variable flow capacity -
<br />For HVAC fan motors >_ 7.5 hp, indicate method of variable flow control (VSD, or equivalent
<br />na
<br />C403.2.13
<br />HVAC system fans
<br />control method that reduces design air volume by 50 / at 1/3 static design pressure); note
<br />exception taken
<br />DX air handler variable
<br />For DX air handlers with economizer and cooling capacity;?: 65,000 Btu/h, indicate number of
<br />cooling stages provided and method (multiple compressors and / or variable speed
<br />na
<br />C403.3.1
<br />cooling control
<br />compressors); indicate minimum displacement (capacity reduction) as % of full load
<br />(Under Integrated
<br />Indicate control method (cooling capacity controlled in response to space temperature, space
<br />Economizer)
<br />temperature controlled by modulating supply airflow, or both)
<br />For DX air handling units with cooling capacity>_ 65,000 Btu/h and evaporative and chilled
<br />water air handling units with fan>_ 0.25 hp; indicate whether system is single zone or multiple
<br />zone and related control method (cooling capacity controlled in response to space
<br />temperature, space temperature is controlled by modulating supply airflow, or both)
<br />For mechanical cooling systems (includes DX and chilled water coils) that control cooling
<br />capacity in response to space temperature - Provide a minimum of two stages of fan control;
<br />na
<br />C403.2.11.5
<br />Fan airflow control
<br />indicate minimum fan speed is 5 66% of full speed drawing <_ 40% of full speed fan power
<br />during periods of low cooling or ventilation only
<br />For other mechanical cooling systems (includes DX and chilled water coils) that control space
<br />temperature by modulating airflow (in lieu of, or in addition to, controlling capacity in response
<br />to space temperature) - Provide fan controls for modulating supply airflow; indicate minimum
<br />fan speed is <_ 50% of full speed drawing <_ 30% of full speed fan power during periods of low
<br />cooling or ventilation only; or exception taken
<br />Provide central and zone level DDC controls as required based on system application,
<br />na
<br />C403.2.4.12
<br />DDC system capabilities
<br />capacity or size thresholds and other qualification per Table C403.2.4.12.1
<br />Identify all DDC system input / output control points; indicate capability for trending and
<br />graphical display
<br />Ducting Systems
<br />C403.2.8.1
<br />Indicate on plans that all ductwork is constructed and sealed per IMC
<br />For OSA ductwork, also indicate on plans that ductwork meets air leakage requirements per
<br />NA
<br />C403.2.8.3
<br />Duct construction
<br />C402.5 and vapor retarder requirements per the IBC
<br />C403.2.8.3
<br />Duct pressure classifications
<br />Identify location of low, medium and high pressure ductwork on plans
<br />Ln
<br />C403.2.8.3.3
<br />High pressure duct leakage
<br />Indicate high pressure duct leakage testing requirements on plans; provide test results to
<br />test
<br />Ijurisdiction when completed
<br />
|