Laserfiche WebLink
10. Revise floor plan to show 2x6 furred walls on the interior of the basement. REVISED SHEET 3 & 6 <br />11. Provide note on drawings, "Insulate and weatherstrip crawl space access". REVISED SHEET 3 <br />12. Please remove references to the Ventilation and Indoor Air Quality Code (VIAQ) that no longer <br />exists. Update requirements to Chapter 15 of the IRC. REVISED SHEET 7 <br />13. Please provide building section drawing to show the existing construction at main floor and 2 x 6 <br />furring at the below grade walls in the new dwelling unit in the basement. Show all existing and <br />proposed blocking, fireblocking, joists (size and direction), rafters and plates. Show insulation in all <br />walls floors and ceiling, including R-10 insulation at headers in furred out walls. REVISED SHEET 6 <br />14. Provide minimum 1.5 "Energy Credits" per table 406.2 WSEC. Show requirements of credits chosen <br />on plans and floor plan. REVISED SHEET 7 <br />15. The Energy Certificate on sheet 7 shows Electric wall heaters with 92% AFUE and ducts insulated to <br />R-8. There are no ducts, and Electric heaters are not measured in Annual Fuel Utilization Efficiency <br />(HSPF or COP). REVISED SHEET 7 <br />16. Show location of heat pump exchange unit on the site plan. REVISED SHEET 1 <br />17. The energy credits shown on sheet 7, total 1.0 credits. R406.2 requires 1.5 credits for dwellings less <br />than 1500 square feet. Please revise table to show the total 1.5 credits required. <br />REVISED SHEET 7 <br />18. Specify which "Whole House Ventilation System" per section M1507.3.3 you will be using. Provide <br />the requirements of the whole house ventilation system you will be using, do not simply reference <br />the code section (whole house exhaust fan sone rating shall be 1.0 or less, not 1.5 as is shown on <br />drawing). REVISED SHEET 3 & 6 <br />19. Provide minimum 36-inch landing at all exterior entrance/exits and at the top and bottom of all <br />stairs. Landing shall be not more than 7-3/4" below the finished floor. Show on plans and site plan. <br />REVISED SHEET 3 <br />age 2 of 2 <br />