Laserfiche WebLink
• • <br /> Ms. Finsch <br /> Tiscareno Associates <br /> Plan Check Number: B1801-032, First Review <br /> March 13, 2018 <br /> c. The design load appears less than the forces resulting from the terrace area between Grids <br /> S-7 and S-10. Additional documentation on the design loads should be submitted for <br /> review. See also other comments regarding the terrace loads. See IBC Section 1604.1 <br /> d. The last beam at each end of the structure supports perpendicular framing at Level 4 and <br /> should be evaluated for additional loads. See IBC Section 1604.1. <br /> 25. Sheets S210a and S210b show PSL5-1/4 beams supporting the Level 4 walls and roof above. <br /> The spans at multiple locations exceed the 14'-8"design length considered on structural <br /> calculation page SC137. Calculations substantiating the beams for the increased lengths <br /> should be submitted for review. See IBC Section 1604.2. <br /> 26. Sheets S210a and S210b include a cantilever roof along Grid S-A/S-5 — S-S.1-2.1. The <br /> following comments should be addressed: <br /> a. Structural calculations pages SC136 and SC139 for the 4x10 and 2x10, respectively, <br /> consider a backspan of 10 feet. The backspan is 6 feet per the drawings. The calculations <br /> should be revised. See IBC Section 1604.2. <br /> b. The grade for the 2x10 is DFL #1. This material is not included in the schedule in the <br /> Wood Framing"section of the Structural General Notes on Sheet S003. See IBC Section <br /> 107.2.1 <br /> c. Calculations do not appear included for the support beams under the cantilever beams and <br /> should be submitted for review. See IBC Section 1604.1. <br /> d. Calculations do not appear included for the connections between the cantilever beams and <br /> the beam providing hold-down resistance, and the hold-down beam and the walls. <br /> Calculations and details for the connections should be submitted for review. It is <br /> recommended that the stability of the back-span consider Equation 16-10 with a 0.6-factor <br /> on the resisting weight (i.e., floor). See IBC Section 107.2.1 and 1604.1. <br /> 27. Sheet S210b shows a cantilevering roof structure at Grid S-A—S-A.6/S.1-2.1 — S.1-3. The <br /> following comments should be addressed: <br /> a. The framing appears incomplete and should be revised. See IBC Section 1603.1. <br /> b. The sizes for multiple beams and joists do not appear to be provided and should be <br /> specified. See IBC Section 1603.1. <br /> c. Calculations for the framing and connections in this area should be submitted for review. <br /> d. It is recommended that the stability of the back-spans consider Equation 16-10 with a 0.6- <br /> factor on the resisting weight (i.e., floor). <br /> 28. Sheets S208a, S208b, S209a, and S209b show single TJI210 framing at 12-inch spacing with <br /> nominal spans of 16 feet or greater at multiple locations. Structural calculation page SC144 <br /> requires two pieces of TJI210 at 16-inch spacing, or an effective spacing of 8 inches, for spans <br /> not exceeding 15'-8". Alternatively, page SC145 allows two pieces at 12-inch spacing. <br /> Calculations substantiating the single pieces for the spans and spacing shown should be <br /> submitted for review, or the drawings should be revised to match one of the configurations <br /> specified in the calculations. See IBC Section 1603.1 and 1604.2. <br /> 29.The floor plans for Levels 2, 3, 4, and the roof, specify the typical headers to be two 2x8 <br /> framing. The headers at multiple locations support perpendicular floor joists and roof trusses. <br /> 6of11 <br /> CITY OF EVERETT • 3200 Cedar Street • Everett,WA 98201 • (425) 257-8810 • Fax(425) 257-8857 <br />