Laserfiche WebLink
• • <br /> 1. It should be stated how the 20% of the total cost of alterations ($120k per the submitted <br /> valuation) are being allocated towards accessible route upgrades (main floor only, other <br /> floors do not require an accessible route per IBC Section 1104.4). IEBC Section 305.7 <br /> 2. It should be verified that the shower on the basement level meets the criteria of a transfer <br /> shower as it was installed on or after 2007. IBC Section 1109.2 <br /> In order for the processing of your application to continue, it will be necessary to provide the <br /> Building Division with two new sets of revised construction documents reflecting the corrections <br /> requested. Please include a response letter which indicates how the corrections were resolved. <br /> All codes cited refer to the 2015 International Building Code (IBC), 2015 International Existing <br /> Building Code (IEBC), the 2015 International Fire Code (IFC), the 2015 International Mechanical <br /> Code (IMC), and/or the 2015 Washington State Energy Code (WSEC), as amended by the State <br /> of Washington and adopted by the City of Everett. The current IBC referenced standard for <br /> accessible design is the 2009 "Accessible and Usable Buildings and Facilities" (ICC/ANSI <br /> A117.1). Federal ADA regulations and standards may be more restrictive. <br /> These comments address building issues only. Additional revisions or additions may be required <br /> by other departments (such as Utilities, Traffic, Planning or Fire). All required submittals must <br /> be of sufficient detail and information to ensure that the proposed structure will be constructed <br /> in compliance with all adopted codes. <br /> Sincerely, <br /> Tony Lee <br /> Building Official <br /> It el. <br /> O 3200 Cedar Street © 425.257.8810 O tlee@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov <br />