REFLECTED CEILING PLAN
<br />i/ b = it u
<br />(1)
<br />NORTH
<br />NEW 2X2 ACT AND GRID
<br />NEW GWB - PAINT PT-1 UNO
<br />EXISTING OPEN CEILING TO REMAIN.
<br />NEW 2'x2' RECESSED LED LIGHT FIXTURE
<br />NEW B/S 2'x9' RECESSED LED LIGHT FIXTURE TO BE UPGRADED FOR EMERGENCY LIGHTING, LAYOUT
<br />SHOWN IS CONCEPTUAL ONLY.
<br />13
<br />CEILING MOUNTED LIGHT FIXTURE - MFR: SLV LIGHTING, 6" FLATZ, 3000K, SQUARE, LED 14W, WHITE,
<br />WET LOCATION
<br />(E)
<br />LED TRACK LIGHTING - MFR: WAC LIGHTING, WAC H 7011-930, FINISH: BLACK, TRACK: HALO MINIATURE
<br />�I
<br />SINGLE CIRCUIT TRACK, L650 SERIES, 90 DEGREE CORNERS: L904-L CONNECTOR, FINISH: BLACK (MB),
<br />CURRENT LIMITER ACUITY SILVER BULLET GR-2400 (E = UPGRADED TRACK LIGHTING FOR EMERGENCY"
<br />LIGHTING, LAYOUT SHOWN IS CONCEPTUAL ONLY.) 11'-6" LONG AND 8'-0" TRACKS -MOUNT TRACK
<br />HEADS AT 10' AFF. CONTACT: PLS, MEL ISSA MILLER, PHONE: 206-436-8834 AND EMAIL:
<br />MELISSAM@PLSWA,COM
<br />25 INCH LONG LED VANITY WALL SCONCE - MFR: DWELED, MODEL: WS-85624-AL, LEVEL LED VANITY -
<br />I
<br />BRUSHED CHROME,
<br />0
<br />EXISTING B/S ILLUMINATED EXIT SIGN
<br />$ (�)
<br />NEW B/S LIGHT SWITCH (D = DIMMER, M = MASTER, 3 = THREE WAY)
<br />O
<br />B/S RECESSED CAN LIGHT
<br />E/S RECESSED CAN LIGHT TO BE UPGRADED FOR EMERGENCY LIGHTING. LAYOUT SHOWN IS
<br />CONCEPTUAL ONLY,
<br />LED TAPE - MANUFACTURE: WAC LIGHTING LED-T24P-1-WT COLLECTION: WAC LIGHTING, SKU:
<br />-- _ LED-T24P-1-WT, UPC: 790576194219, FINISH: WHITE, COLOR TEMPERATURE: 3000K, LUMENS: 200, .EST.
<br />LIFE: 50,000 HOURS, VOLTAGE: 24V, SAFETY RATING: 'ETL DAMP,
<br />NEW B/S EXHAUST FAN
<br />1. THE REFLECTED CEILING PLAN INDICATES THE LOCATION OF CEILING HEIGHTS, LIGHT FIXTURES, SWITCH
<br />LOCATION9S, AND ASSOCIATED ITEMS, REFER TO ENGINEERING DRAWINGS FOR CIRCUITING, WIRING LAYOUT, AND
<br />ADDITIONAL INFORMATION, ALL MEP -FP DEVICE LOCATIONS NOT SHOWN ON DRAWINGS, OR IN CONFLICT WITH
<br />MEP/FP DRAWINGS, ARE TO BE COORDINATED WITH THE DESIGNER PRIOR TO INSTALLATION, IN THE EVENT OF
<br />DISCREPANCIES BETWEEN THE DESIGNER'S REFLECTED CEILING PLAN AND THE ENGINEERS' PLANS, IMMEDIATELY
<br />NOTIFY THE DESIGNER IN WRITING BEFORE ORDERING MATERIALS OR PROCEEDING WITH THE WORK,
<br />2. AFTER 30 DAYS FROM SUBSTANTIAL COMPLETION, INSPECT THE WORK AND ADJUST TILE NOT IN ALIGNMENT WITH
<br />OTHER CEILING TILES AND REPLACE MISSING OR DAMAGED UNITS.
<br />3. WITHIN A ROOM OR AREA, THE CONTRACTOR SHALL ESTABLISH A SINGLE FLOOR ELEVATION THAT IS TO BE USED
<br />AS THE ORIGIN FOR ALL NEW CEILING HEIGHTS ABOVE FINISHED FLOOR.
<br />4, VERIFY FIELD CONDITIONS AND LOCATIONS OF ALL MEP/FP AND STRUCTURAL ELEMENTS, CONTRACTOR TO
<br />COORDINATE THE WORK OF ALL TRADES NECESSARY TO MAINTAIN THE FINISHED CEILING HEIGHTS INDICATED,
<br />INSTALL DUCTWORK TIGHT TO UNDERSIDE OF BEAMS, WITH A SMALL SPACE TO AVOID VIBRATION. INSTALLATION
<br />AND/OR ALTERATION OF DUCTWORK, PIPING OR OTHER EQUIPMENT THAT WILL REQUIRE FASCIAS, SOFFITS AND
<br />OTHER TRANSITIONS IN CEILING HEIGHT SHALL BE REVIEWED WITH THE DESIGNER PRIOR TO PROCEEDING.
<br />5. CONTRACTOR TO PROVIDE COMPLETE COORDINATION DRAWINGS OF NEW WORK FOR THE DESIGNER'S AND
<br />ENGINEER'S REVIEW.
<br />6. MUL I IPLE SWITCHES AT ONE LOCATION SHALL BE GANGED TOGETHER WITHIN ONE COVER PLATE U.N.O..
<br />7. ALL FIXTURES AND DEVICES TO BE UNDERWRITERS LABORATORIES INC, (UL) LABELED.
<br />8. LIGHT FIXTURES, REGISTERS, RECESSED FIXTURES AND SIMILAR CEILING ELEMENTS, AND LIFE -SAFETY DEVICES
<br />SHALL BE LOCATED IN THE CENTER OF CEILING TILE IN BOTH DIRECTIONS AND SHALL ALIGN WITH ADJACENT
<br />FIXTURES, DEVICES OR HEADS IN A RUN OR ROW, U.N.O.
<br />9. FURNISH AND INSTALL ALL FIXTURES, ASSOCIATED TRIM, LAMPS, AND SEISMIC BRACING IN COMPLIANCE WITH THE
<br />BUILDING CODE,
<br />10, INSTALL LIGHT FIXTURES WITH PROTECTIVE FILM OR SIMILAR COVER OVER LOUVER, LENS, BAFFLE, AND EXPOSED
<br />SURFACES, TO AVOID FIXTURE SOILING OR DAMAGE DURING CONSTRUCTION. FIXTURES SHALL BE MAINTAINED
<br />CLEAN AND AS NEW,
<br />11. PROVIDE SUPPORT FOR LIGHT FIXTURES PER MANUFACTURERS REQUIREMENTS
<br />12. REFER TO ELECTRICAL DRAWINGS FOR EMERGENCY LIGHT FIXTURE LOCATIONS,
<br />13. PROVIDE CEILING ACCESS REQUIRED FOR EQUIPMENT AND SYSTEM MAINTENANCE WHERE APPLICABLE. MATCH
<br />ADJACENT CEILING FINISH U.N.O. SYSTEMS AND EQUIPMENT REQUIRING ACCESS SHALL BE LOCATED AT
<br />ACCESSIBLE CEILINGS - ADDITIONAL ACCESS PANELS NOT SHOWN ON DRAWINGS SHALL NOT BE INSTALLED IN
<br />GYPSUM BOARD CEILINGS WITHOUT PRIOR APPROVAL BY DESIGNER AND TENANT,
<br />14. COORDINATE SCHEDULING OF WORK WITH DATA/TELEPHONE INSTALLER, INSTALL CEILING TILES AFTER
<br />DATA/TELEPHONE CABLES HAVE BEEN INSTALLED.
<br />15. INSTALL CEILING TILES AFTER FINISH PAINTING TO MINIMIZE VOC ABSORPTION INTO THE CEILING TILES.
<br />I& PATCH ALL HOLES IN EXISTING FIREPROOFING TO RESTORE THE REQUIRED FIRE RATINGS OF THE EXISTING
<br />STRUCTURE,
<br />17. PAINT ALL EXPOSED DUCTWORK, PIPING AND ELECTRICAL CONDUIT WHITE, U.N.O.
<br />I& PAINT ALL EXPOSED UNDERSIDE OF CONCRETE SLABS, U.N.O.
<br />19. SWITCHES AND FACE PLATES SHALL BE WHITE .
<br />20. ALL LAMP COLOR TEMPERATURES TO BE CONSISTENT FOR ALL FIXTURE TYPES.
<br />201 SWITCH CAN LIGHTS, RECESSED PERIMETER LED TUBE LIGHTING AND EXHAUST
<br />FAN SEPARATELY. RECESSED PERIMETER LED TUBE LIGHTING TO BE ON A
<br />DIMMER.
<br />202 CREATE A SOFFIT WITH AN ALCOVE TO ACCOMMODATE LED TUB LIGHTING,
<br />AROUND PERIMETER OF ROOM.
<br />.✓ vV v.aLsr«
<br />rr �e �.r/r .siae vra�
<br />�- car3 11^R UG\L.3
<br />i'I.d IPAL VV,-@1 BJ
<br />35
<br />12
<br />420
<br />4"—,
<br />33
<br />37
<br />1,221
<br />®AJ
<br />3 U
<br />264
<br />12
<br />4
<br />48
<br />14
<br />2
<br />28
<br />�
<br />21
<br />1
<br />� 21
<br />TOTAL WATTS PROPOSED 2,002
<br />PROPOSED WATTAGE: IS 2,002 - WHICH IS LESS THAN THE ALLOWABLE WATTAGE PER 2018 NEC INTERIOR
<br />LIGHTING POWER C405.4.2 (TABLE C405.4.2(1) BUILDING AREA METHOD).
<br />Crested Crafie Interiors
<br />Design Studio
<br />f
<br />Des Moines, WA 98198
<br />WWW.CRESTEDCRANEINTERIORS.COM
<br />Client Venant:
<br />Designer:
<br />Roject Location'.
<br />OLYMPIC
<br />1 SE EVERETT MALL WAY, SUITE
<br />EVERETT, WA 98208
<br />Description: ate: No.
<br />PERMIT SET 02/15/2021
<br />NEW ENTRY DOOR REVISION 03/16/2021 L � �
<br />10194
<br />/ ��'TE/
<br />?1 A 611TEOTZJ
<br />AAIu9ELl;
<br />TTE �A�frIrTO