1 <br /> Q8. Per Note 1 on Sheet E16 of the project plans, "Dimensions shown are <br /> nominal. Actual dimensions shall be determined by Controls Integrator per <br /> Section 40 90 00." The specification section referenced in this note does not I <br /> appear within the project specifications. Will the referenced section be <br /> released in a future addendum? <br /> RESPONSE: SECTION 40 90 00 HAS BEEN PROVIDED AS AN <br /> ATTACHMENT TO ADDENDUM 3. <br /> Q9. What wire is to go into conduits "C70" and "C71"? <br /> RESPONSE: DRAWING Ell HAS BEEN UPDATED TO PROVIDE THIS <br /> INFORMATION AND IS ATTACHED TO ADDENDUM 3. <br /> Q10. On drawing E6 we see (2) conduits drawn for wire notes "P4" & "P5" but the I <br /> schedule only calls for (1) conduit in each? Please advise? <br /> RESPONSE: DRAWING Ell HAS BEEN UPDATED TO PROVIDE THIS <br /> INFORMATION AND IS ATTACHED TO ADDENDUM 3. <br /> Q11. The pre-bid agenda calls for the signed addenda to be attached to the bid <br /> forms. However the addenda themselves do not have a signature page. <br /> Please advise how to proceed. <br /> RESPONSE: SECTION 00 25 /3 HAS BEEN REMOVED FROM THE <br /> SPECIFICATIONS. ADDENDA ARE NOT REQUIRED TO BE SIGNED AND <br /> ATTACHED TO THE BID. ADDENDA MUST BE ACKNOWLEDGED ON <br /> THE BID FORM(00 4/ 13) IN SECTION 1.05. THE PRE-BID MEETING <br /> AGENDA THAT WAS DISTRIBUTED AT THE MEETING AND INCLUDED <br /> WITH ADDENDUM 2 WAS IN ERROR REGARDING THE REQUIREMENT <br /> THAT ADDENDA BE SIGNED AND ATTACHED TO THE BID. ADDENDA <br /> ARE NOT REQUIRED TO BE SIGNED AND ATTACHED TO THE BID. <br /> Q12. Spec 26 13 00 Section 2.02A requires a Square D by Schneider Electric for <br /> the metal-enclosed interrupter switchgear. Is the City open to an alternate <br /> product? <br /> RESPONSE: THE CITY HAS A BRAND-NAME/STANDARDIZATION <br /> POLICY IN EFFECT THAT REQUIRES SQUARED BY SCHNEIDER <br /> ELECTRIC. THE BRAND SHALL BE AS SPECIFIED. <br /> Q13. What is the allowable surcharge loading on the retaining wall on the north side I <br /> of the site, behind the pump station? <br /> RESPONSE: THE RETAINING WALL HAS NOT BEEN EVALUATED AS <br /> PART OF THE DESIGN. NO INFORMATION IS CURRENTLY AVAILABLE <br /> FOR THE RETAINING WALL TO THE NORTH OF THE CITY'S PROPERTY. <br /> FOR THE EXISTING PUMP STATION BUILDING'S NORTH WALL, <br /> RECORD DRAWINGS DO NOT APPEAR TO SPECIFY A SURCHARGE <br /> LOADING ASSUMED IN THE ORIGINAL DESIGN; HOWEVER, A RECORD <br /> DRAWING SHOWING THE EXISTING PUMP STATION BUILDING'S <br /> Addendum 3 to Evergreen Pump Station Modifications(WO#UP3747-3) Page 14/17 <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425) 257-8800 • Fax(425)257-8882 <br />