Section 40 90 00 PROCESS CONTROL SYSTEM GENERAL PROVISIONS <br /> b. With rating for the environment installed. <br /> 9. Terminate all wiring on terminal strips, splicing wiring is not acceptable. <br /> 10. Wire that terminates on screw type terminals shall be provided with a <br /> spade or loop type end connector. <br /> 11. For all indicating transmitters that are mounted inside enclosures, provide <br /> a window in the enclosure so that the display can be viewed without <br /> opening the enclosure. <br /> 12. Instrumentation supplier shall provide installation inspection, calibration <br /> and training as required for proper installation. <br /> B. DOOR-SWITCHES <br /> 1. Provide door security switches at locations indicated on the Drawings. <br /> I 2. Install such that the switch contacts are closed when the door is closed. <br /> Magnetic type with contacts normally open held closed when door is <br /> closed. Switches shall have anodized finish and be furnished with 3-foot <br /> stainless steel armored cable. Sentrol 2500 series or accepted equal. <br /> 2.12 WIRE MARKERS: <br /> A. Field installed wire markers shall be T&B, SHRINK-KON HVM or accepted equal. <br /> 2.13 SPARE PARTS <br /> A. In addition to spare parts mentioned elsewhere in this section, the Contractor o tractor <br /> shall supply the following spare parts for use by the Owner. All spare parts shall <br /> be shipped with the equipment. <br /> 1. Qty 1 spare (non-installed) PLC input and output card of each type used. <br /> 2. Qty 1 spare power supply of each type and rating used. <br /> 3. Qty 1 Relay of each type used or 10 % whichever is the greater amount. <br /> 4. Qty 2 lamps of each type used or 100% whichever is the greater amount. <br /> 5. Qty 200% spare fuses (two spare fuses for each fuse supplied). <br /> 6. Provide 5 spare nameplates 3" square or less with 20 letters 1/2" or less <br /> to be specified by the Owner. <br /> 7. Qty 1 Copy of final PLC program on a thumb drive. <br /> I <br /> I <br /> I <br /> City of Everett 40 90 00-13 January 2022 <br /> Evergreen Pump Station Modifications <br /> UP3747-3 <br /> Issued for Bid <br />