• S <br /> Page 2 <br /> 3. The EF-1B and EF-1C ducts on Sheet M2.02 pass down through the floor assembly to <br /> the First story. The duct penetration through the floor shall be constructed per IBC <br /> Section 717.6.1. <br /> RENSCH RESPONSE:I updated Key Note#2 on M2.02 to include specific requirements from IBC 717.6.1. <br /> 4. The ducts serving exhaust fans on Sheets M2.03 through M2.05 are required to be <br /> concealed in walls per IBC Section 717.6.1 Exception 1,as stated in Keynote 2. <br /> However,the keynote is only specified where each duct originates. The keynote is not <br /> specified for the ducts passing through the Fourth and Fifth stories on Sheets M2.04 <br /> and M2.05,respectively. The plans do not appear to show walls at the duct locations. <br /> The drawings should be revised to clarify how this requirement will be satisfied. See <br /> IBC Section 107.2.1. <br /> RENSCH RESPONSE:Please see updated plans:M2.04 and M2.05. I added key note#2 to each duct <br /> passing through the 4th and 5th floors. I added walls around each group of ducts with a call-out indicating <br /> a non-fire-resistance rated chase to satisfy the requirement in the exception to 717.6.1 where the ducts <br /> must be contained and located within a cavity of a wall. <br /> 5. The following comments should be addressed for the EF-1D and EF-1E ducts,and dryer <br /> ducts EH-2A through EH-2D,on Sheet M2.02: <br /> a. The ducts should be concealed in soffits per Keynote 1. See IBC Section <br /> 107.2.1. <br /> b. The ducts are closely-spaced and penetrating through a structural wall. It <br /> appears the wall may be constructed of unreinforced masonry. A detail for <br /> the penetrations,including but not limited to spacing requirements,opening <br /> edge distanced,and notes to avoid cutting steel reinforcement where present, <br /> shall be included in the drawings. Structural calculations may be required to <br /> substantiating that the penetrations do not impair the load-carrying capacity <br /> of the wall. See IBC Sections 107.2.1 and IEBC Sections 807.4 and 807.5. <br /> c. The ducts on Sheet M2.01 appear to penetrate the west exterior wall at an <br /> existing window opening. The construction of the penetrations should be <br /> clarified. A detail should be included as needed. If the penetrations occur <br /> through the existing structural systems,additional detailing and calculations <br /> may be required. See IBC Sections 107.2.1 and IEBCSections 807.4 and 807.5. <br /> RENSCH RESPONSE:The ducts passing through the corridor are called out appropriately in key note#4 on <br /> M2.02 as being concealed above a ceiling(as required by IBC 717.5.4 Exception#3,condition#4). <br /> The dryer exhaust ducts are not required to be in a soffit(they are individually vented,not classified as <br /> Type 2 dryers). <br /> All exterior wall terminations occur at infills of pre-existing windows(no structural details needed). The <br /> architect has been made aware of the requirements we talked about regarding fire-resistance ratings of <br /> the infilled windows;they will be responsible for ensuring all code requirements from the IBC are <br /> adhered to. <br />