Mr. Sanjeev Sharma <br />Z Realty Plus <br />Plan Check Number: B2006-012, First Building Review <br />August 28, 2020 <br />Gravity System: <br />6. Wood Note 30(A) specifies minimum nailing requirements per IBC Table 2304.1.10.1. Details <br />for the construction of built-up members should be provided, including but not limited beams, <br />headers, stair stringers, and posts. See IBC Section 107.2.1. <br />7. The design for the stairways does not appear to be provided. Framing details should be <br />included. Calculations substantiating the design of the stringers should be submitted for <br />review. See IBC Sections 1603.1 and 1604.1. <br />8. The structural calculations for the gravity system are incomplete. It does not appear that all <br />beams are evaluated. Design of the built-up posts is not included. Additional calculations <br />substantiating the gravity framing should be submitted for review. See other comments below <br />addressing combined gravity and seismic lading. See IBC Sections 1604.1 and 1604.2. <br />Lateral System: <br />9. The wind lateral pressures are based on Exposure B. The building is located near open water <br />and should be designed for Exposure C or D. The wind design should be revised. See IBC <br />Section 1609.1 and ASCE 7-10 Section 26.7.3. <br />10. Wood Note 21 of the General Structural Notes on Sheet S3 indicates that the wood framing <br />includes hem -fir material. The capacity of the shear walls should be reduced per Table 4.3A <br />Footnote 3. See IBC Section 2306.1. <br />11. The structural calculations include wind and seismic shear calculations. However, the effective <br />tributary areas and resulting shear loads to each wall line at each level are not clear. Additional <br />documentation showing the load distribution to each wall and the resulting value should be <br />provided for review. See IBC Sections 1604.4. <br />12. Continuing with the previous comment, overturning calculations should be provided for each <br />individual wall section. It appears that multiple shear walls, particularly at the second story, <br />require holdowns. Calculations substantiating the vertical reactions at the wall ends should be <br />submitted for review. The calculations should consider the load combinations of ASCE 7-10 <br />Section 12.4.2.3 Equations (7) and (8) including vertical effects per Section 12.4.2.2. Where <br />holdowns are required, they should be continuous to the foundation or developed into the <br />framing below. Discontinous holdowns should be designed using overstrength as discussed in <br />the following comment below. See IBC Section 1604.1 and 2306.1, and AWC SDPWS-15 <br />Section 4.3.6.4.2. <br />13. The building includes multiple shear walls that are not continuous to the foundation and are <br />partially or completely supported by beams and posts. This is a Type 4 Vertical Structural <br />Irregularity per ASCE 7-10 Table 12.3-2. The framing supporting the walls and the connections <br />between the walls and framing, connections interconnecting the supporting framing, and <br />connections to the foundations, should be designed including overstrength per Section 12.3.3.3. <br />This includes most of the framing supporting shear walls at the Upper Floor. The load <br />3200 Cedar Street © 425.257.8810 everetteps@everettwa.gov <br />Everett, WA 98201 425.257.8857 fax everettwa.gov/permits <br />Page 4 of 5 <br />