SERIES FAN POWERED TERMINAL UNIT SCHEDULE
<br />MINIMUM
<br />MAXIMUM
<br />INLET
<br />FAN PERFORMANCE
<br />ELECTRIC HEATER PERFORMANCE
<br />PRIMARY AIR
<br />PRIMARY AIR
<br />SIZE
<br />MAX
<br />ECM
<br />ECM
<br />60 HERTZ
<br />MAX
<br />WEIGHT
<br />TAG
<br />MAKE & MODEL
<br />UNIT SIZE
<br />DESCRIPTION
<br />SERVES
<br />(CFM)
<br />(CFM)
<br />(INCHES)
<br />CFM
<br />HP
<br />FLA
<br />VOLTS PHASE
<br />Kul
<br />STAGES
<br />VOLTS
<br />PH
<br />AMPS
<br />MOCP
<br />CONTROL
<br />NOTES
<br />FPTU-1
<br />NAILOR D35SE
<br />2
<br />VARIABLE VOLUME
<br />LEVEL 1 EXTERIOR ZONES
<br />335
<br />335
<br />2
<br />6"0
<br />335
<br />VAR
<br />2.6
<br />277/1
<br />3.7
<br />2
<br />460/3
<br />4.7
<br />15
<br /><200
<br />DIGITAL
<br />1, 2, 3, 4
<br />FPTU-2
<br />NAIL OR D35SE
<br />2
<br />VARIABLE VOLUME
<br />LEVEL 1 EXTERIOR ZONES
<br />410
<br />410
<br />2
<br />6"0
<br />410
<br />VAR
<br />2.6
<br />277/1
<br />4.5
<br />2
<br />460/3
<br />5.7
<br />15
<br /><200
<br />DIGITAL
<br />1, 2, 3, 4
<br />FPTU-3
<br />NAILOR D35SE
<br />4
<br />VARIABLE VOLUME
<br />LEVEL 1 EXTERIOR ZONES
<br />610
<br />610
<br />4
<br />10"o
<br />610
<br />VAR
<br />4.2
<br />277/1
<br />6.8
<br />2
<br />460/3
<br />--6.5
<br />15
<br /><200
<br />DIGITAL
<br />1, 2, 3, 4
<br />FPTU-4
<br />NAILOR D35SE
<br />5
<br />VARIABLE VOLUME
<br />LEVEL 1 EXTERIOR ZONES
<br />950
<br />950
<br />5
<br />12"0
<br />950
<br />VAR
<br />5.6
<br />277/1
<br />10.5
<br />2
<br />460/3
<br />13.2
<br />20
<br /><200
<br />DIGITAL
<br />1, 2, 3, 4
<br />FPTU-5
<br />NAILOR D35SE
<br />4
<br />VARIABLE VOLUME
<br />LEVEL 1 EXTERIOR ZONES
<br />750
<br />750
<br />4
<br />10"o
<br />750
<br />VAR
<br />4.2
<br />1 277/1
<br />3.3
<br />2
<br />460/3
<br />10.4
<br />15
<br /><200
<br />DIGITAL
<br />1, 2, 3, 4
<br />FPTU-6
<br />NAILOR D35SE
<br />2
<br />VARIABLE VOLUME
<br />LEVEL 1 EXTERIOR ZONES
<br />300
<br />300
<br />2
<br />6"0
<br />300
<br />VAR
<br />2.6
<br />277/1
<br />3.3
<br />2
<br />460/3
<br />4.2
<br />15
<br /><200
<br />DIGITAL
<br />1, 2, 3, 4
<br />FPTU-7
<br />NAILOR D35SE
<br />4
<br />VARIABLE VOLUME
<br />LEVEL 1 EXTERIOR ZONES
<br />600
<br />600
<br />4
<br />10"o
<br />600
<br />VAR
<br />4.2
<br />277/1
<br />6.6
<br />2
<br />460/3
<br />6.4
<br />15
<br /><200
<br />DIGITAL
<br />1, 2, 3, 4
<br />FPTU®6
<br />NAILOR 035SE
<br />2
<br />VARIABLE VOLUME
<br />LEVEL 1 EXTERIOR ZONES
<br />500
<br />500
<br />2
<br />6"0
<br />500
<br />VAR
<br />2.6
<br />277/1
<br />5.5
<br />2
<br />460/3
<br />7.0
<br />15
<br /><200
<br />DIGITAL
<br />1, 2, 3, 4
<br />FPTU-9
<br />NAILOR D35SE
<br />5
<br />VARIABLE VOLUME
<br />LEVEL 1 EXTERIOR ZONES
<br />975
<br />975
<br />5
<br />12"0
<br />975
<br />VAR
<br />5.8
<br />277/1
<br />10,6
<br />2
<br />460/3
<br />13.6
<br />20
<br /><200
<br />DIGITAL
<br />1, 2, 3, 4
<br />FPTU10
<br />NAILOR D35SE
<br />4
<br />VARIABLE VOLUME
<br />LEVEL 1 EXTERIOR ZONES
<br />750
<br />750
<br />4
<br />10"o
<br />750
<br />VAR
<br />4.2
<br />277/1
<br />8.3
<br />2
<br />460/3
<br />10.4
<br />15
<br /><200
<br />DIGITAL
<br />1, 2, 3, 4
<br />FPTU-11
<br />NAILOR D35SE
<br />4 _
<br />VARIABLE VOLUME
<br />LEVEL 2 EXTERIOR ZONES
<br />735
<br />735
<br />4
<br />10"o
<br />735
<br />VAR
<br />4.2
<br />277/1
<br />6.1
<br />2
<br />460/3
<br />10.2
<br />15
<br /><200
<br />DIGITAL
<br />1, 2, 3, 4
<br />FPTU-12
<br />NAILOR D35SE
<br />2
<br />VARIABLE VOLUME
<br />LEVEL 2 EXTERIOR ZONES
<br />375
<br />375
<br />2
<br />62)0
<br />375
<br />VAR
<br />2.6
<br />277/1
<br />6.4
<br />2
<br />460/3
<br />8.0
<br />15
<br /><200_
<br />DIGITAL
<br />1, 2, 3, 4
<br />FPTU-13
<br />NAILOR D35SE
<br />5
<br />VARIABLE VOLUME
<br />LEVEL 2 EXTERIOR ZONES
<br />950
<br />950
<br />5
<br />12"0
<br />950
<br />VAR
<br />5.6
<br />277/1
<br />10.5
<br />2
<br />460/3
<br />13.2
<br />20
<br /><200
<br />DIGITAL
<br />1, 2, 3, 4
<br />FPTU— 14
<br />NAILOR D35SE
<br />4
<br />VARIABLE VOLUME
<br />LEVEL 2 EXTERIOR ZONES
<br />750
<br />750
<br />4
<br />10" o
<br />750
<br />VAR
<br />4.2
<br />277/1
<br />&3
<br />2
<br />460/3
<br />10.4
<br />20
<br /><200
<br />DIGITAL
<br />1, 2, 3, 4
<br />NOTES:
<br />1. EQUIPMENT MAY BE SUBSTITUTED FOR EQUAL OR
<br />BETTER MANUFACTURER.
<br />2. FAN POWERED TERMINAL UNITS ARE SERIES CONFIGURED
<br />AND SERVE EXTERNAL ZONES ONLY.
<br />3. HEATER SIZING BASED ON A AT-357.
<br />4. PROVIDE ALL EXHAUST FANS WITH 70% OR GREATER
<br />EFFICIENCY MOTORS OR ELECTRONICALLY COMMUTATED (ECM)
<br />MOTORS AS REQUIRED BY 2015 WSEC SECTION C405.8
<br />FOR FRACTIONAL HORSEPOWER FAN MOTORS THAT ARE
<br />1/12 HORSEPOWER AND LARGER.
<br />GAS PRV SCHEDULE
<br />EXHAUST FAN SCHEDULE
<br />INLET PRESS
<br />OUTLET PRESS
<br />PRV MAX
<br />INDIV LOAD
<br />CONK
<br />FAN PERFORMANCE
<br />ELECTRICAL DATA (60 HZ)
<br />-
<br />TAG
<br />MFR / MODEL
<br />SERVES_
<br />DESCRIPTION
<br />(PSIG)
<br />(IN W.C.)
<br />CAP (MBH)
<br />(MBTUH)
<br />SIZE
<br />(IN)
<br />NOTES
<br />- -
<br />PRV-1
<br />MAXITROL — 5L
<br />RTU-1
<br />NATURAL GASI
<br />2#
<br />14"
<br />425
<br />220
<br />3/4"
<br />1
<br />FLOW
<br />ESP
<br />FAN
<br />DRIVE
<br />MOTOR
<br />VOLTS
<br />PHASE
<br />FLA
<br />MOCP
<br />SOUND
<br />WEIGHT
<br />TAG
<br />MANUFACTURER AND MODEL
<br />DESCRIPTION
<br />APPLICATION
<br />(CFM)
<br />(IN WG)
<br />RPM
<br />(HP)
<br />-
<br />(dBA)
<br />(LBS)
<br />NOTES:
<br />PRV-2
<br />MAXITROL — 5L
<br />RTU-2
<br />NATURAL GAS
<br />2
<br />14"
<br />425
<br />220
<br />3/4"
<br />1
<br />EF-1
<br />GREENHECK G-060—VG
<br />ROOFTOP
<br />EXHAUST
<br />TOILET
<br />ROOM EXHAUST
<br />250
<br />0.5
<br />1,630
<br />DIRECT
<br />0.1
<br />115
<br />1
<br />1.3�
<br />15.0
<br />55
<br />2S
<br />1 2 4 6 7
<br />-
<br />PRV-3
<br />MAXITROL e 5L
<br />RTU-3
<br />NATURAL GAS
<br />2#
<br />14"
<br />425
<br />350
<br />3/4'y
<br />1
<br />EF-2
<br />GREENHECK G-090�-VG
<br />ROOFTOP
<br />EXHAUST
<br />TOILET
<br />ROOM EXHAUST
<br />350
<br />0.5
<br />1> 429
<br />DIRECT
<br />0.1
<br />115
<br />1
<br />1.35
<br />15.0
<br />52
<br />29
<br />2 39 4S 6 7
<br />1'
<br />PRV-4
<br />MAXITROL — 3L
<br />GWH— 1
<br />NATURAL GAS
<br />2#
<br />14"
<br />140
<br />76
<br />1 /2"
<br />1,
<br />2
<br />-
<br />Y 8
<br />EF-3
<br />GREENHECK G-099—VG
<br />ROOFTOP
<br />EXHAUST
<br />TOILET
<br />ROOM EXHAUST
<br />750
<br />0.7
<br />1,510
<br />DIRECT
<br />0.25
<br />115
<br />1
<br />2.65
<br />15.0
<br />59
<br />36
<br />1, 2, 3, 4, 6, 7
<br />EF-4
<br />GREENHECK G-090—VG
<br />ROOFTOP
<br />EXHAUST
<br />BREAK
<br />ROOM EXHAUST
<br />350
<br />0.5
<br />i ,429
<br />DIRECT
<br />0.1
<br />115
<br />1
<br />1.36
<br />15,0
<br />52
<br />29
<br />1, 2, 3, 5, 6, 7
<br />NOTES:
<br />TOTAL GAS LOAD
<br />= 666,000
<br />BTUH (617 CFH)
<br />7
<br />-
<br />1. VALVES MAY BE SUBSTITUTED. REFER TO APPROVED EQUIPMENT SUBMITTALS FOR FINAL SELECTIONS.
<br />2. VALVE IS NOT VENTED BUT RATHER FITTED WITH A VENT LIMITER PROVIDED BY THE MANUFACTURER, MAXITROL
<br />12AO9.
<br />NOTES:
<br />1.
<br />EQUIPMENT MAY BE SUBSTITUTED, REFER TO APPROVED
<br />EQUIPMENT
<br />SUBMITTALS
<br />FOR FINAL SELECTIONS.
<br />2.
<br />REFER TO ELECTRICAL DRAWINGS FOR MOTOR STARTER,
<br />DISCONNECT,
<br />AND POWERED CONVENIENCE OUTLET, AS APPLICABLE.
<br />3.
<br />PROVIDE EQUIPMENT SUPPORT SLEEPERS, GREENHECK GESS OR EQUAL.
<br />4.
<br />UNIT AVAILABLE FOR 24/7 OPERATION AND CONTROLLED
<br />VIA AN OCCUPANCY TIMER, ADJUSTABLE BY THE OWNER.
<br />5.
<br />FAN TO BE ACTIVATED BY WALL SWITCH WITH LABEL AT
<br />THE SWITCH
<br />INDICATING
<br />IT CONTROLS THE EXHAUST FAN.
<br />6.
<br />PROVIDE WITH CLASS 1 LOW LEAK MOTORIZED DAMPER
<br />AND TWO POSITION ACTUATOR AT BUILDING ENVELOPE EXHAUST DUCT PENETRATION PER 2015 WSEC
<br />C403.2.4.3.
<br />7.
<br />PROVIDE ALL EXHAUST FANS WITH 70% OR GREATER EFFICIENCY MOTORS
<br />OR ELECTRONICALLY COMMUTATED (ECM) MOTORS AS REQUIRED BY 2015 WSEC SECTION C405.6
<br />FOR FRACTIONAL HORSEPOWER FAN MOTORS THAT ARE
<br />1 /12 HORSEPOWER AND
<br />LARGER,
<br />HVAC DUCT SPECIFICATION SCHEDULE
<br />HVAC DUCT SPECIFICATION NOTES:
<br />1.
<br />ALL DUCTWORK TO CONSTRUCTED TO 2015 IMC REQUIREMENTS,
<br />SMACNA SEAL CLASS A STANDARDS, ALL TRANSVERSE JOINT,
<br />DUCT SYSTEM
<br />SMACNA PRESSURE
<br />MATERIALS
<br />CLEANLINESS
<br />AND USE
<br />SEISMIC
<br />NOTES:
<br />LONGITUDINAL SEAMS AND DUCT WALL PENETRATIONS TO BE SEALED.
<br />OR SECTION
<br />CLASS
<br />(DUCT, LINING, INSULATION)
<br />DURING
<br />CONSTRUCTION
<br />HVAC SUPPLY
<br />LOW PRESSURE
<br />GALVANIZED METAL DUCT
<br />FOLLOW BASIC
<br />LEVEL
<br />A SMACNA CLEANLINESS GUIDELINES.
<br />APPROVAL OF
<br />1, 2, 3,
<br />4,
<br />2.
<br />DUCT WORK SHALL BE INSULATED AND PROVIDED WITH VAPOR BARRIER
<br />ATTACHMENTS TO
<br />5
<br />AS REQUIRED BY 2015 WSEC SECTION C403.2.8 AND AS FOLLOWS:
<br />HEATING AND COOLING
<br />SP :� 2" WG, RTU TO DIFFUSERS
<br />ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS
<br />AND DUCT
<br />ONLY OK TO USE TEMPORARY HEAT AND VENTILATION WITH
<br />STRUCTURE BY OTHERS
<br />WALL PENETRATIONS SEALED TO SMACNA SEAL
<br />CUSS A.
<br />CONSTRUCTION
<br />FILTER
<br />INSTALLED
<br />AND UNIT IN 100% OSA
<br />TYPE LOCATION R—VALUE
<br />MAINS <1500 FPM. BRANCHES
<br /><1200
<br />MODE,
<br />OS AIR >2500 CFM IN CONDITIONED SPACE 19
<br />FPM. BRANCH TO DIFFUSER
<br /><600 FPM
<br />INSULATION PER NOTE 2
<br />OS AIR <2800 CFM IN CONDITIONED SPACE 7
<br />SUPPLY OR RETURN IN UNCONDITIONED SPACE 6
<br />HVAC RETURN
<br />LOW PRESSURE
<br />GALVANIZED METAL DUCT
<br />FOLLOW BASIC
<br />LEVEL
<br />A SMACNA CLEANLINESS GUIDELINES.
<br />APPROVAL OF
<br />1, 2, 3,
<br />4,
<br />SUPPLY OF RETURN OUTSIDE BUILDING
<br />[1 ]
<br />ATTACHMENTS TO
<br />5
<br />HEATING AND COOLING
<br />SP < 2" WG, RETURN TO
<br />RTU
<br />ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS
<br />AND DUCT
<br />RELIEVE AIR THROUGH
<br />DOORS AND WINDOWS
<br />STRUCTURE BY OTHERS
<br />3.
<br />ALL DUCTWORK SPECIFIED SHALL BE CLASSIFIED AS LOW PRESSURE
<br />WALL PENETRATIONS SEALED TO SMACNA SEAL
<br />CLASS A.
<br />AND SHALL BE INSTALLED IN ACCORDANCE WITH 2O15 IMC
<br />MAINS <1500 FPM. BRANCHES
<br /><1200
<br />REQUIREMENTS AND SMACNA STANDARD FOR 2" WG, UNLESS HIGHER
<br />FPM. BRANCH TO DIFFUSER
<br /><600 FPM
<br />INSULATION PER PER NOTE 2
<br />STATIC PRESSURE ARE INDICATED ON DRAWINGS.
<br />TOILET EXHAUST
<br />LOW PRESSURE
<br />GALVANIZED METAL DUCT
<br />FOLLOW BASIC
<br />LEVEL
<br />A SMACNA CLEANLINESS GUIDELINES.
<br />APPROVAL OF
<br />1, 2, 3,
<br />4
<br />4.
<br />ALL DIMENSIONS SHOWN ON PLANS ARE INSIDE CLEAR DIMENSIONS,
<br />ATTACHMENTS TO
<br />GENERAL EXHAUST
<br />SP � 2" WG, EXIT GRILLE
<br />TO FAN
<br />ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS
<br />AND DUCT
<br />RELIEVE AIR THROUGH
<br />DOORS AND WINDOWS
<br />STRUCTURE BY OTHERS
<br />5.
<br />SUPPLY AND RETURN AIR DUCTWORK OFF THE AIR HANDLING UNIT CAN
<br />WALL PENETRATIONS SEALED TO SMACNA SEAL
<br />CLASS A.
<br />BE UP TO 3" WG STATIC PRESSURE, DEPENDING ON FINAL DUCT
<br />VELOCITY <600 FPM
<br />ROUTING THROUGH STRUCTURE. DUCT SHALL BE CONSTRUCTED TO
<br />INSULATION PER NOTE 2
<br />SMACNA STANDARD TO SUPPORT THAT PRESSURE CLASSIFICATION.
<br />[1]
<br />DUCT ON THE ROOF SHALL BE INSULATED TO A VALUE OF R-8 IN
<br />KEEPING WITH CLIMATE ZONE 4 PER C403.2.6.2 OF THE 2015 WSEC.
<br />COPYRIGHT NOTICE
<br />THIS LAYOUT/DESIGN IS A
<br />COPYRIGHTED WORK OWNED BY
<br />COMFORT SYSTEMS USA
<br />(NORTHWEST), INC. ("COMFORT
<br />SYSTEMS NORTHWEST") AND
<br />COMFORT SYSTEMS NORTHWEST
<br />HEREBY RESERVES ITS RIGHT TO
<br />PREVENT UNAUTHORIZED COPYING,
<br />PUBLICATION OR USE OF THIS
<br />LAYOUT/DESIGN AND TO OBTAIN
<br />DAMAGES THEREFORE.
<br />SIGNED: 12/11/2020
<br />VKMIN,
<br />1. PERMIT SET 12-11-2020
<br />2. -
<br />3. o
<br />4. m
<br />5. a
<br />SHEET NUMBER
<br />MOmO4
<br />SHEET 4 OF 22