ig ting, Y otor an• ectrica -equirements ist, pg 5 o 11 <br /> 2018'WSEC Requirements for Commercial Buildings including Group R2,R3&R4 over 3 stories&all R1 -- Administered by©2022 NEEA,All rights reserved <br /> The following information is necessary to check a permit application for compliance with the lighting systems,motors and electrical system requirements in the <br /> Washington State Energy Code,Commercial Provisions. <br /> For questions about this report,contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com <br /> { E i <br /> For building facade and landscape lighting, 1 I <br /> indicate control sequence for shut-off control <br /> is based on dawn-to-dusk and business <br /> J 1 opening/closing schedule;indicate whether <br /> automatic of time switch controls will be ! 4 <br /> I i i provided for this function <br /> C405.5.2 Lighting control of Indicate that exempt exterior lighting and <br /> exempt exterior I lighting located^within exterior areas/surfaces <br /> lighting that eligible for a lighting power exemption <br /> are controlled independently from non- <br /> exempt <br /> exterior lighting <br /> • <br /> —� -- <br /> C405.5 s Exterior gas fired Indicate ignition system is a method other ( ^ ' <br /> i )lighting appliances i then continuously burning pilot light <br /> NO C405.2.7 Area controls- Indicate location(s)of master control general switching <br /> Master control switch(es)intended to control multiple shown-final switching <br /> switches and circuit independent switches;circuit breaker may not by electrical <br /> power limit be used as a master control switch contractor under their <br /> • permit <br /> NO Verify that no 20 amp circuit controlled by a general switching <br /> • single switch or automatic control is loaded shown-final switching <br /> beyond 80% by electrical <br /> contractor under their <br /> permit <br /> ADDITIONAL EFFICIENCY CREDIT-ENHANCED INTERIOR LIGHTING CONTROLS <br /> C406.4 Enhanced digital I To comply with additional efficiency credit, <br /> lighting controls indicate on plans that interior lighting fixtures I j <br /> are configured with all of the following <br /> I control functions,as applicable: 1)Each <br /> fixture is individually addressed,or exception I I <br /> taken:2)Fixtures are configured for , <br /> continuous dimming;3)No more than eight <br /> fixtures are controlled by a single daylight <br /> sensor;4)in enclosed and open office areas, <br /> illumination levels of overhead general area <br /> lighting is configured to be individually <br /> adjusted by occupants <br /> -- j Include calculations that demonstrate the total <br /> I j lighting power of all interior lighting fixtures <br /> configured with enhanced lighting controls is <br /> no less than 90%of the total interior lighting <br /> I i power for the area the enhanced lighting <br /> controls credit is being applied to <br /> INTERIOR LIGHTING POWER&EFFICACY <br /> YES C405.4.1 Total connected Include all luminaires in interior lighting see WSEC form in <br /> C405.4.2 interior lighting fixture schedule;indicate fixture types,lamps, pemrit package <br /> power ballasts,and manufacturer's watts per fixture <br /> for the installed lamp <br /> NO Identify spaces eligible for lighting power didn't apply <br /> exemption on plans and in WSEC interior exemptions <br /> lighting compliance reports;indicate the <br /> exception applied <br /> � 1 <br /> • <br /> Page 5/11 <br />