Laserfiche WebLink
C� <br />5. It appears that the horizontal shear reinforcement of CMU/BMU details on Sheet S6.1 do not contain <br />hooks around vertical reinforcement where jambs and openings occur. Please verify and revise <br />details as required. TMS 402 7.3.2.6 (d). <br />6. Please provide flexural and P-M design calculations for the special reinforced masonry walls proposed <br />as they appear to be missing from the permit calculations. <br />RESUBMITTAL REQUIREMENTS <br />In order for the processing of your application to continue, it will be necessary to provide the Building <br />Division with the following items: <br />❑ (2) New, complete sets of revised construction documents reflecting the corrections as <br />required. <br />❑ (1) Response letter detailing how the corrections were resolved. <br />All codes cited refer to the 2018 International Building Code (IBC), 2018 International Existing Building <br />Code (IEBC), the 2018 International Fire Code (IFC), the 2018 International Mechanical Code (IMC), <br />and/or the 2018 Washington State Energy Code (WSEC), as amended by the State of Washington and <br />adopted by the City of Everett. The current IBC referenced standard for accessible design is the 2009 <br />"Accessible and Usable Buildings and Facilities" (ICC/ANSI A117.1). Federal ADA regulations and <br />standards may be more restrictive. <br />These comments address building issues only. Additional revisions or additions may be required by <br />other departments (such as Utilities, Traffic, Planning or Fire). All required submittals must be of <br />sufficient detail and information to ensure that the proposed structure will be constructed in <br />compliance with all adopted codes. <br />Sincerely, <br />( --- ee�;;7-e- <br />James Bronder, PE, SE <br />Associate Engineer <br />Plans Examiner <br />Page 2 of 2 <br />