66. Garages - Install a portable fire extinguisher with a minimum U.L. rating of 2-A:40-8:C within 30 feet <br />travel distance of all portions of this building. 2015 IFC, Table 906.3(2). Shop area. <br />67. Fire Alarm System - An approved automatic fire detection system shall be provided as required by City <br />Ordinance No. 3021-07, Chapter 16.76, of the Everett Municipal Code. <br />Plans for such system shall be submitted to the City of Everett Permit Services at 3200 Cedar Street 2nd <br />Floor, Everett, WA for review and approval prior to installation. Submittal shall include cut sheets of all <br />equipment intended for use. Appropriate trip tests, witnessed by a Fire Department Inspector, shall be <br />performed, along with a certificate of completion, prior to final acceptance of the system. <br />Fire alarm systems shall be installed according to NFPA Chapter 72, 2013 Edition. Installation of fire <br />alarm components, including basic wiring, may not commence before plans are approved by the Fire <br />Department Plan Reviewer. Fire alarm drawings must be professionally rendered, in sufficient detail, <br />and must be internally consistent. Riser diagrams must match installation plans and load calculations. <br />Components must be listed and approved for use together. Changes to plans must include new <br />drawings and calculations and must be approved by the Fire Department Plan Reviewer prior to <br />installation. Fire alarm installation is subject to field inspection by a Fire Department Inspector. An <br />approved set of plans and the City of Everett Permit Services electrical permit must be present for any <br />installation inspection. <br />Fire alarm systems shall be installed under permit of the City of Everett Permit Services. Electrical <br />inspections and approval are required prior to calling for acceptance tests. Call (425) 257-8810 for <br />permit information. <br />The absence of monitoring for the alarm system will be cause for postponing Fire Department <br />inspection and testing and shall result in denial of occupancy. <br />A copy of NFPA 72 Record of Completion form must be filled out prior to final occupancy (NFPA 72, 2013 <br />Edition, Chapter 7, pages 107-147). 2015 IFC, 907.7.2 <br />Call for design requirements per Authority Having Jurisdiction. <br />Automatic smoke detection is required. <br />Place annunciator panel in main lobby area. <br />68. Fire Suppression (Sprinkler) System - An approved automatic suppression system shall be provided as <br />required by City Ordinance No. 3021-07, EMC, Chapter 16.76. <br />Plans for any such system shall be submitted to the City of Everett Permit Services at 3200 Cedar Street <br />2"d Floor, Everett, WA for examination and approval. Such plans shall include plans for the underground <br />mains that will supply the sprinkler system. <br />The type of sprinkler to be installed will be determined by the Fire Marshal and Building Official. It may <br />be an NFPA 13, NFPA 13R, or NFPA 13D system depending upon several factors. Sprinkler installation <br />shall not begin without an approved and stamped set of plans from the City of Everett Permit <br />Services. The Fire Department will also review the plans and shall field inspect the installation based <br />only on approved plans that must be on site. Changes to plans must be approved by both Permit <br />Services and the Fire Departments. <br />Aboveground sprinkler piping shall be hydrostatically tested as established in NFPA Standard 13. <br />Underground piping shall be hydrostatically tested and flushed as established in NFPA Standard 24 for <br />private fire mains. (Below -ground piping must be Installed by Washington State licensed <br />Underground Sprinkler line certified "U" Installers. For further information, contact the State Fire <br />Marshal's Office at (360) 596-3900 or contact the Everett Fire Department at (425) 257-8124.) All such <br />tests shall be witnessed by a Fire Department inspector. Call (425) 257-8104 or (425) 257-8120 to make <br />an appointment for inspection. <br />Contractors' materials and test certificates shall be submitted to the Everett Fire Department prior to <br />issuance of any Certificates of Occupancy. 2015 IFC, WA State Amendment 903.3.5.3, Page 111. <br />Page 9 of 1 <br />SEPA18-004 <br />