Laserfiche WebLink
CONTROL SYSTEM GUIDELINES AND SPECIFICATIONS - VERTICAL PAINT BOOTH <br />GENERAL: <br />REFER TO DRAWING M310 FOR CONTROL DIAGRAM ASSOCIATED WITH THESE <br />GUIDELINES AND SPECIFICATIONS. ALSO REFER TO SPECIFICATION SECTION <br />15975 FOR ADDITIONAL REQUIREMENTS. <br />HEATING AND VENTILATING EQUIPMENT ASSOCIATED WITH THIS BOOTH SHALL <br />BE CONTROLLED BY A PROGRAMMABLE LOGIC CONTROLLER (PLC). CONTROL <br />DECISIONS SHALL BE MADE AT THE PLC BASED ON INPUT SIGNALS RECEIVED <br />FROM SENSORS LOCATED IN THE SYSTEM. OUTPUT SIGNALS FROM THE PLC <br />SHALL ENERGIZE, DEENERGIZE OR MODULATE CONTROLLED DEVICES TO <br />MAINTAIN PROGRAMMED SET POINTS OR CONDITIONS. ANALOG AND DIGITAL <br />INPUT AND OUTPUT SIGNALS SHALL BE UTILIZED BY THE CONTROLLER. <br />DIGITAL INPUT OR OUTPUT SIGNALS SHALL BE USED FOR TWO POSITION <br />CONTROL MODES. ANALOG INPUT OR OUTPUT SIGNALS SHALL BE USED FOR ALL <br />OTHER CONTROL MODES. <br />EQUIPMENT OPERATIONAL STATUS SHALL BE INDICATED AT THE PLC AS <br />SENSED BY CURRENT RELAYS (XM) AT EACH MOTOR AS INDICATED ON THE <br />CONTROL DIAGRAM. <br />RUN LIGHTS (XI) SHALL BE PROVIDED ADJACENT TO THE OPERATIONAL MODE <br />PUSHBUTTONS AT THE OPERATORS CONTROL PANEL AS SHOWN ON THE CONTROL <br />DIAGRAM TO INDICATE THE MODE OF OPERATION THE SYSTEM IS OPERATING <br />IN. RUN LIGHTS SHALL BE RED. <br />BOOTH EXHAUST FAN (EF) <br />GENERAL: <br />EACH VERTICAL PAINT BOOTH HAS TWO EXHAUST FANS (EF). THE CONTROL <br />DIAGRAM AND THE FOLLOWING SEQUENCE DESCRIBE OPERATIONS FOR ONLY ONE <br />FAN SYSTEM, BUT ARE TYPICAL FOR BOTH UNLESS OTHERWISE NOTED. <br />THE EF SHALL BE EITHER MANUALLY OR AUTOMATICALLY STARTED THROUGH <br />THE H-O-A SWITCH (HS-2XXO1) LOCATED AT THE MOTOR CONTROL CENTER. <br />MANUAL ACTIVATION SHALL OCCUR IN THE HAND POSITION. AUTOMATIC <br />ACTIVATION SHALL OCCUR THROUGH THE PLC WHEN THE H-O-A SWITCH IS <br />POSITIONED IN THE AUTO POSITION. THE SWITCH SHOULD NORMALLY BE <br />POSITIONED IN THE AUTO POSITION. <br />WHEN THE EF IS EITHER MANUALLY OR AUTOMATICALLY STARTED, THE <br />SOLENOID VALVES ON THE PLANT COMPRESSED AIR LINES SERVING THE FANS <br />AUTOMATIC DAMPER (SnV-2XX01) AND THE BOOTH SPRAY GUN (SnV-OXX01 AND <br />OXXO2) SHALL BE ENERGIZED. WHEN ENERGIZED, THESE VALVES SHALL ALLOW <br />90 PSIG AIR TO THE AUTOMATIC AIR DAMPER AND THE BOOTH DISTRIBUTION <br />SYSTEM SERVING THE SPRAY GUN AIR OUTLETS. THE 90 PSIG AIR SHALL <br />OPEN THE NORMALLY CLOSED (N.C.) AUTOMATIC AIR DAMPER. WHEN THE EF <br />IS DEACTIVATED FOR ANY REASON THE SOLENOID VALVES SHALL BE <br />DEENERGIZED, ALLOWING PLANT AIR TO BLEED OFF THE SYSTEMS. THIS <br />SHALL DEACTIVATE THE SPRAY GUNS AND ALLOW THE AUTOMATIC DAMPER TO <br />RETURN TO ITS FAIL SAFE (NORMAL) POSITION. <br />AIR FLOW CONTROL: <br />THE EF VARIABLE FREQUENCY DRIVE (VFD) SHALL CONTROL EXHAUST SYSTEM <br />AIR FLOW BASED ON PREDETERMINED AIR FLOW SETTINGS (SEE DRAWING M3) <br />IN RESPONSE TO PLC COMMANDS. THE CONTROL SYSTEM INSTALLER AND THE <br />HVAC BALANCING CONTRACTOR SHALL WORK TOGETHER TO ESTABLISH THESE <br />SET POINTS AS REQUIRED TO OBTAIN THE VARIOUS AIR FLOWS DESCRIBED <br />BELOW UNDER OPERATIONAL MODES A, B, AND C. THESE SET POINTS SHALL <br />BE DISPLAYED AND SHALL BE ADJUSTABLE FROM THE PLC STATION. ACCESS <br />TO CHANGE THESE SET POINTS SHALL BE PASSWORD PROTECTED. CONTROL OF <br />EACH OF THE THREE MODES SHALL BE AT THE LOCAL CONTROL STATION AND <br />SHALL BE REMOTELY INDICATED AT THE PLC STATION. <br />ON A CHANGE IN AIR FLOW (OPERATIONAL MODE CHANGE), THE PLC SHALL <br />RAMP -UP THE FAN VARIABLE FREQUENCY DRIVE. THE RAMP -UP DURATION FROM <br />NO -FLOW TO FULL -FLOW SHALL BE IN EQUAL INCREMENTS FOR A 90 SECOND <br />TIME PERIOD (ADJUSTABLE). THE SAME STEPS ESTABLISHED FOR THE NO - <br />FLOW TO FULL -FLOW RAMP -UP SHALL BE USED FOR RAMP -UP FROM ANY AIR <br />FLOW MODE TO A HIGHER AIR FLOW MODE. <br />WHEN THE SYSTEM IS OPERATING IN THE MANUAL MODE OF CONTROL (HAND <br />POSITION AT THE H-O-A SWITCH), THE FAN SHALL NOT BE UNDER CONTROL <br />OF THE PLC AND AIR FLOW SHALL FAIL TO THE FULL FLOW (OPERATIONAL <br />MODE B) SETTING. <br />FAN SAFETY CONTROLS: <br />WHEN THE EF IS OPERATING IN EITHER THE MANUAL OR AUTOMATIC MODE AND <br />SMOKE IS DETECTED BY THE DUCT SMOKE DETECTOR (AS-2XX01), THE <br />EXHAUST FAN SHALL BE DEENERGIZED AND CONTROLLED COMPONENTS SHALL <br />RETURN TO THEIR FAIL SAFE POSITIONS. SMOKE DETECTOR ALARMS, AS WITH <br />OTHER SUMMARY ALARMS, SHALL BE REGISTERED AT THE EVERETT DISPATCH <br />CENTER THROUGH THE EXISTING FACILITY ENERGY MANAGEMENT SYSTEM <br />STATION. SUMMARY ALARMS SHALL BE ENTERED IN ONE OF THE LOCAL 40-51 <br />'EXCEL' PANELS FOR FORWARDING TO THE EXISTING FACILITY ENERGY <br />MANAGEMENT SYSTEM. UPON RECEIPT OF A MALFUNCTION, DISPATCH SHALL <br />NOTIFY THE COGNIZANT MAINTENANCE SUPERVISOR, WHO WILL, IN TURN, <br />SEND THE APPROPRIATE MAINTENANCE PERSON WHO WILL DETERMINE THE <br />EXACT NATURE OF THE SYSTEM MALFUNCTION AT THE 40-51 PLC STATION. <br />INDIVIDUAL SYSTEM STATUS AND ALARMS SHALL BE REGISTERED AND <br />DISPLAYED AT THE PLC STATION. <br />WHEN THE EXHAUST FAN THE ASSOCIATED <br />BOOTH SUPPLY FAN �SI LL BE <br />DEENERGIZED AND TH IR ETURN TO <br />THEIR FAIL SAFE POSITIONS. MMEM <br />IF EXHAUST AIR FLOW IS NOT PROVEN BY PRESSURE DIFFERENTIA <br />TRANSMITTER (PdT-2XX01), THE EXHAUST FAN MOTOR SHALL BE DEENERGIZED <br />WHICH SHALL DEENERGIZE THE SOLENOID VALVES (SnV-OXX01 AND OXXO2) <br />SERVING THE PAINT BOOTH SPRAY GUNS AND (SnV-2XX01) SERVING THE <br />N.C.-AAD. THIS ALARM CONDITION SHALL BE INDICATED AT THE EXISTING <br />FACILITY ENERGY MANAGEMENT SYSTEM. <br />FILTER BANK: <br />PRESSURE DROP ACROSS THE FILTER BANK SHALL BE MONITORED AT THE <br />LOCAL PRESSURE DIFFERENTIAL INDICATOR TRANSMITTER (PdIT-2XXO1) <br />LOCATED ON THE BOOTH CONTROL PANEL. WHEN THE DIFFERENTIAL PRESSURE <br />ACROSS THE FILTERS EXCEEDS THE FILTER CHANGE OUT SET POINT, THIS <br />INFORMATION SHALL BE REGISTERED AT THE EVERETT DISPATCH CENTER <br />THROUGH THE FACILITY ENERGY MANAGEMENT SYSTEM STATION. SUMMARY <br />ALARMS SHALL BE ENTERED IN ONE OF THE LOCAL 40-51 'EXCEL' PANELS <br />FOR FORWARDING TO THE FACILITY ENERGY MANAGEMENT SYSTEM. UPON <br />RECEIPT OF A MALFUNCTION, DISPATCH SHALL NOTIFY THE COGNIZANT <br />MAINTENANCE SUPERVISOR, WHO WILL, IN TURN, SEND THE APPROPRIATE <br />MAINTENANCE PERSON WHO WILL DETERMINE THE EXACT NATURE OF THE <br />SYSTEM MALFUNCTION AT THE 40-51 PLC STATION. INDIVIDUAL SYSTEM <br />STATUS AND ALARMS SHALL BE REGISTERED AND DISPLAYED AT THE PLC <br />STATION. <br />ACCESS TO CHANGE THE FILTER DIFFERENTIAL PRESSURE DESIGN SET POINT <br />SHALL BE PASSWORD PROTECTED SO AS TO BE ACCESSIBLE TO HVAC <br />MAINTENANCE PERSONNEL ONLY. <br />GENERAL: <br />EACH VERTICAL PAINT BOOTH HAS TWO SETS OF TWO SUPPLY FANS (SF) g <br />EACH. THE CONTROL DIAGRAM AND THE FOLLOWING SEQUENCE DESCRIBE <br />OPERATIONS FOR ONLY ONE FAN SYSTEM BUT, ARE TYPICAL FOR BOTH UNLESS <br />OTHERWISE NOTED. <br />THE SF SHALL BE EITHER MANUALLY OR AUTOMATICALLY STARTED THROUGH <br />THE H-O-A SWITCH (HS-5XX01) LOCATED AT THE MOTOR CONTROL CENTER. <br />MANUAL ACTIVATION SHALL OCCUR IN THE HAND POSITION. AUTOMATIC <br />ACTIVATION SHALL OCCUR THROUGH THE PLC WHEN THE H-O-A SWITCH IS <br />POSITIONED IN THE AUTO POSITION. THE SWITCH SHOULD NORMALLY BE <br />POSITIONED IN THE AUTO POSITION. <br />WHEN THE SF IS EITHER MANUALLY OR AUTOMATICALLY STARTED, THE 3-WAY <br />SOLENOID VALVES ON THE PLANT COMPRESSED AIR LINE SERVING THE FAN'S <br />AUTOMATIC DAMPER (SnV-5XX01), THE PREHEAT COIL'S FACE & BY-PASS <br />DAMPER (SnV-3XX02), AND ON THE INSTRUMENT AIR LINE SERVING THE <br />VARIOUS SYSTEM CONTROL VALVES (SnV-3XX01) SHALL BE ENERGIZED. WHEN <br />ENERGIZED, THESE VALVES SHALL ALLOW 90 PSIG AIR TO THE AUTOMATIC <br />AIR DAMPER AND THE I/P SERVING THE FACE & BY-PASS DAMPER (I/P- <br />3XX03) AND 20 PSIG INSTRUMENT AIR TO THE I/P SERVING EACH CONTROL <br />VALVE(I/P-3XX01, 3XX02 AND 7XX01). THE 90 PSIG AIR SHALL OPEN THE <br />NORMALLY CLOSED (N.C.) AUTOMATIC AIR DAMPER. WHEN THE SF IS <br />DEACTIVATED FOR ANY REASON THE SOLENOID VALVES SHALL BE <br />DEENERGIZED, ALLOWING PLANT AND INSTRUMENT AIR TO BLEED OFF THE <br />SYSTEMS. THIS SHALL ALLOW THE AUTOMATIC AIR DAMPER, FACE & BY-PASS <br />DAMPER, AND THE CONTROL VALVES TO RETURN TO THEIR FAIL SAFE <br />(NORMAL) POSITIONS. <br />AIR FLOW CONTROL: <br />THE SF VARIABLE FREQUENCY DRIVE (VFD) SHALL CONTROL SUPPLY SYSTEM <br />AIR FLOW BASED ON PREDETERMINED AIR FLOW SETTINGS (SEE DRAWING M3) <br />IN RESPONSE TO PLC COMMANDS. THE CONTROL SYSTEM INSTALLER AND THE <br />HVAC BALANCING CONTRACTOR SHALL WORK TOGETHER TO ESTABLISH THESE <br />SET POINTS AS REQUIRED TO OBTAIN THE VARIOUS AIR FLOWS DESCRIBED <br />BELOW UNDER OPERATIONAL MODES A, B, AND C. THESE SET POINTS SHALL <br />BE DISPLAYED AND SHALL BE ADJUSTABLE FROM THE PLC STATION. ACCESS <br />TO CHANGE THESE SET POINTS SHALL BE PASSWORD PROTECTED. CONTROL OF <br />EACH OF THE THREE MODES SHALL BE AT THE LOCAL CONTROL STATION AND <br />SHALL BE REMOTELY INDICATED AT THE PLC STATION. THE AIR FLOW TO <br />THE BOOTH SHALL BE REDUCED BELOW THE PREDETERMINED QUANTITIES BY <br />THE PLC UPON INDICATION OF EXCESSIVE POSITIVE STATIC PRESSURE <br />INSIDE THE BOOTH AS INDICATED BY THE DIFFERENTIAL PRESSURE <br />INDICATING TRANSMITTER (PdIT-5XXO2) INSTALLED ACROSS THE VERTICAL <br />PAINT BOOTH WALL. <br />ON A CHANGE IN AIR FLOW (OPERATINAL MODE CHANGE), THE PLC SHALL <br />RAMP -UP THE FAN VARIABLE FREQUENCY DRIVE. THE RAMP -UP DURATION FROM <br />NO -FLOW TO FULL -FLOW SHALL BE IN EQUAL INCREMENTS FOR A 90 SECOND <br />TIME PERIOD (ADJUSTABLE). THE SAME STEPS ESTABLISHED FOR THE NO - <br />FLOW TO FULL -FLOW RAMP -UP SHALL BE USED FOR RAMP -UP FROM ANY AIR <br />FLOW MODE TO A HIGHER AIR FLOW MODE. <br />WHEN THE SYSTEM IS OPERATING IN THE MANUAL MODE OF OPERATION (HAND <br />POSITION AT THE H-O-A SWITCH), THE FAN SHALL NOT BE UNDER CONTROL <br />OF THE PLC AND AIR FLOW SHALL FAIL TO THE FULL FLOW (OPERATIONAL <br />MODE B) SETTING. <br />PREHEAT CONTROL: B <br />STEAM FLOW TO THE PREHEAT COIL SHALL BE CONTROLLED BY NORMALLY <br />CLOSED (N.C.), TWO -POSITION TEMPERATURE CONTROL VALVE (TCV-3XX01). <br />THE LC SH L E HE TCV EN HE OUTSIDE AIR T P T DROPS <br />0 H ET P AT Y UT E <br />TEMPERATURE TRANSMITTER (TT-3XX03). THE PE6 SIIAEE meDUEATE TIIE <br />PRE' TEAT GGI' 'S INTEGRAL <br />FAGS 0. RV PAS DAMPERS TO MAINTAIN PRE' TEAT <br />nn'.- -EI.NG AIR <br />DESIGN _T PONT <br />TEMPERATURE <br />EMPERTRE AS SENSED BY D' nr <br />A <br />..OF <br />- - -- - - -- <br />.. . . . . .. <br />I <br />��s T( / I IAnI/ 1E T"E I II IAAInIrI AT'On' n'TPO' PET PO'n'TP "^ E HOA'S ARE IN THE AUTO POSITIONS, THE PLC SHALL AUTOMATI <br />MA D nnnTrOTrD C T nr AOOrc E' E T AAa'n'TE" ^"vrOT ST FANS (EF), SUPPLY FANS (SF), g <br />rE�nl�l�� -- @B>4 <br />OR EACH OF THE SELECTED SYSTEMS SHALL BE AS <br />WHEN THE SF IS OPERATING IN EITHER THE MANUAL OR AUTOMATIC MODE AND PREVIOUSLY DESCRIBED WITH THE FOLLOWING MODE SPECIFIC REQUIREMENTS. <br />BOOTH SMOKE IS DETECTED BY THE DUCT SMOKE DETECTOR (AS-5XX01), THE SUPPLY SETTING. <br />EXHAUST FANS (EF) SHALL OPERATE IN THE 64,000 CFM (EACH) <br />FAN SHALL BE DEENERGIZED AND ASSOCIATED CONTROL COMPONENTS SHALL BOOTH SUPPLY FANS (SF) SHALL OPERATE IN THE 64,000 CFM (PER SET OF <br />RETURN TO THEIR FAIL SAFE POSITIONS. SMOKE DETECTOR ALARMS, AS WITH 2) SETTING. TWO STAGE HEATING TI ATED. PREHEAT HEATING <br />OTHER SUMMARY ALARMS, SHALL BE REGISTERED AT THE EVERETT DISPATCH SHALL NORMALLY BE DE (U ESS 0 D <br />CENTER THROUGH THE EXISTING FACILITY ENERGY MANAGEMENT SYSTEM DEGREES F OR LOWER) g <br />STATION. SUMMARY ALARMS SHALL BE ENTERED IN ONE OF THE LOCAL 40-51 OPERATIONAL MODE C - <br />'EXCEL' PANELS FOR FORWARDING TO THE EXISTING FACILITY ENERGY WHEN OPERATIONAL MODE C PUSH BUTTON HS-OXX04 IS SELECTED AND THE <br />MANAGEMENT SYSTEM. UPON RECEIPT OF A MALFUNCTION, DISPATCH SHALL B( ) <br />NOTIFY THE COGNIZANT MAINTENANCE SUPERVISOR, WHO WILL, IN TURN, HOA'S ARE IN THE AUTO POSITIONS, THE PLC SHALL AUTOMAT <br />SEND THE APPROPRIATE MAINTENANCE PERSON WHO WILL DETERMINE THE C A ST FANS (EF), SUPPLY FANS (SF <br />EXACT NATURE OF THE SYSTEM MALFUNCTION AT THE 40-51 PLC STATION. REe <br />. FOR EACH OF THE SELECTED SYSTEMS SHALL BE AS <br />INDIVIDUAL SYSTEM STATUS AND ALARMS SHALL BE REGISTERED AND PREVIOUSLY DESCRIBED WITH THE FOLLOWING MODE -SPECIFIC REQUIREMENTS. <br />DISPLAYED AT THE PLC STATION. B THERE ARE FOUR PHASES WITHIN THIS OPERATING MODE: PURGE, RAMP -UP, STEADY <br />WHEN THE LOW LIMIT TEMPERATURE SENSOR (TSL-5XX01) SENSES A LEAVING TA AND AMP -DOWN. THE HA ES AR PROG S BAS ON N <br />HEATING COIL TEMPERATURE OF 40 DEGREES F, THE SUPPLY FAN SHALL BE A S IN L H E E T <br />DEENERGIZED AND CONTROLLED COMPONENTS SHALL RETURN TO THEIR FAIL FUNCTION SHALL BE ACTIVE. THE <br />nnr"rnT EI InI TI nl nl PREVENT <br />THE <br />SAFE (NORMAL) POSITIONS. THE PLC SHALL INDICATE SYSTEM SHUTDOWN ATE- PREHEAT - - `��R� <br />TEMPERATURE <br />OE THE <br />S P' Y AIR ENTERING <br />THE <br />''EAT IA I IEE' ERem BEING <br />THE EXISTING FACILITY ENERGY MANAGEMENT SYSTEM. EESS THAN 2 DEGREES I <br />WHEN THE SUPPLY FAN ASSOCIATED DUE TO THE EXPANSIO G <br />BOOTH EXHAUST FAN �EF LL BE AND I'UNI'DIEI/ ATION, E DIFFERENTIAL PRESSURE INDICATING <br />DEENERGIZED AND TH R THEIR S 1 XX02) MOUNTED ACROSS THE BOOTH WALL SHALL <br />FAIL SAFE (NORMAL) POSITIONS. g M NI R H R ATIVE PRESSURIZATION OF THE BOOTH. THE PLC SHALL <br />IF SUPPLY AIR FLOW IS NOT PROVEN BY PRESSURE DIFFERENTIAL CONTROL THE PRESSURIZATION UTILIZING N VFD S. <br />TRANSMITTER (PdT-5XX01), THE SUPPLY FAN MOTOR SHALL BE DE RGIZED PURGE PHASE: BEFORE ANY TEMPERATUR A - OCCUR, THE <br />WHICH SHALL DEENERGIZE THE ASSOCIATED EXHAUST FAN AND THE SOLENOID VALVE (SnV-OXX01) SERVING THE PAINT BOOTH SPRAY GUN. THIS CONDITION BOOTH SHALL BE VENTILATED FOR 10 MIN B <br />SHALL BE INDICATED AT THE EXISTING FACILITY ENERGY MANAGEMENT RAMP -UP S OF A DR B TEMPERATURE <br />SYSTEM. RAMP-FeEEeWED BY A HUMIDITY RAMP UP.-0 RAMP -UP PHASE, THE <br />FOLLOWI N <br />FILTER BANK: BOOTH EXHAUST FANS EF) SHALL OPERATE IN TH 0 CFM (EACH) <br />PRESSURE DROP ACROSS THE FILTER BANK SHALL BE MONITORED AT THE SETTING. <br />LOCAL PRESSURE DIFFERENTIAL INDICATOR TRANSMITTER (PdIT-5XXO1) BOOTH SUPPLY FANS (SF) SHALL OPERATE IN THE 25,000 CFM (PER SET OF <br />LOCATED ON THE BOOTH CONTROL PANEL. WHEN THE DIFFERENTIAL PRESSURE 2) SETTING. BOTH STAGES OF HEATING CONTROL SHALL BE ACTIVATED. <br />ACROSS THE FILTERS EXCEEDS THE FILTER CHANGE OUT SET POINT, THIS B PREHEAT CONTROL SHALL BE ACTIVATED. DURING THE DRY BULB TEMPERATURE <br />INFORMATION SHALL BE REGISTERED AT THE EVERETT DISPATCH CENTER RAMP -UP THE TEMPERATURE OF THE BOOTH SHALL BE ELEVATED FROM T <br />THROUGH THE FACILITY ENERGY MANAGEMENT SYSTEM STATION. SUMMARY S.--AT- <br />ALARMS SHALL BE ENTERED IN ONE OF THE LOCAL 40-51 'EXCEL' PANELS <br />FOR FORWARDING TO THE FACILITY ENERGY MANAGEMENT SYSTEM. UPON BE ISTIA /ATED DURING <br />TI IE I II MIDIEI( ATION RAAAP UP <br />PERIOD TI IE BGGT-I I <br />RECEIPT OF A MALFUNCTION, DISPATCH SHALL NOTIFY THE COGNIZANT IIIJIII TAEE T WISE^ SED FRem TI IE <br />Is IeeNTRIO rn EVE Te Fe <br />MAINTENANCE SUPERVISOR, WHO WILL, IN TURN, SEND THE APPROPRIATE ; EReENT IN n PERIOD OF 39 AIC � <br />MAINTENANCE PERSON WHO WILL DETERMINE THE EXACT NATURE OF THE(qTNF>IIIIIIII�TE PHASE: AFTER THE RA P PERIOD IS OVER AND SPACE CURE <br />SYSTEM MALFUNCTION AT THE 40-51 PLC STATION. INDIVIDUAL SYSTEM TEMPERATU ^"'n H M616'T\/ EA/EI ABILIZE THE PLC SHALL CONTROL <br />STATUS AND ALARMS SHALL BE REGISTERED AND DISPLAYED AT THE PLC THE OPERATI E OMPONENTS TO <br />STATION. g MAINTAIN THE CURE MODE TEMPERATUR N OOTH FOR <br />ACCESS TO CHANGE THE FILTER DIFFERENTIAL PRESSURE DESIGN SET POINT THE SELECTED PERIOD OF TIME. <br />SHALL BE PASSWORD PROTECTED SO AS TO BE ACCESSIBLE TO HVAC <br />1i P111,,,,,,E, l,,,,, RAMP -DOWN PHASE: AFTER THE END OF THE CURE HOLD PrRIOD, THE RAMP- <br />PROTECTED SO AS TO BE ACCESSIBLE TO HVAC MAINTENANCE PERSONNEL <br />0 N LY. <br />HEATING CONTROL (FIRST STAGE): <br />UNIT nOTI IAI I V1_1 PI IQ/ I IACIEn <br />APPLYG THE <br />liu� <br />STEAM FLOW RATE FOR THE FIRST STAGE HEATING SHALL BE CONTROLLED BY <br />NORMALLY CLOSED (N.C.) TEMPERATURE CONTROL VALVE (TCV-3XX02). THE <br />WHEEL SPEED BETWEEN 2U 1/4 RPM MINIMUM TO MAINTAIR <br />PLC SHALL MODULATE THE TCV TO MAINTAIN THE SPACE DESIGN SET POINT <br />1\1 lvi IVI�AIVI�Ivl AND <br />TEMPERATURE AS SENSED BY SPACE TEMPERATURE TRANSMITTER (TT-3XXO1). <br />ACCESS TO CHANGE THE HEATING CONTROL (FIRST STAGE) SET POINTS SHALL <br />BE PASSWORD PROTECTED SO AS TO BE ACCESSIBLE TO HVAC MAINTENANCE <br />PERSONNEL ONLY. <br />HEATING CONTROL (SECOND STAGE): <br />Gn ER AT1ON. I ( DRING TI IE C I AAAEn IkA SPEED <br />MODE OF OPERATION TI'E I IRW WI 'EEL <br />1`1 1`13 ` <br />STEAM FLOW RATE FOR THE SECOND STAGE HEATING SHALL BE CONTROLLED BY <br />BE EUU ITS MINIMUM SPEED Te KEEP FRE)M TRANSFERRING <br />NORMALLY CLOSED (N.C.) TEMPERATURE CONTROL VALVE (TCV-3XX03). THE <br />S1IAEE <br />nITED EPOAA TI IE EVI InI IC T Aln C TnEAAA T TI IE C l lnnl V Aln C TnEAAA <br />PLC SHALL MODULATE THE TCV TO MAINTAIN THE SPACE DESIGN SET POINT <br />BE RRIDDEN THE 6jREnI( <br />TEMPERATURE AS SENSED BY SPACE TEMPERATURE TRANSMITTER (TT-3XX01). <br />REO lIN <br />AITInI E V <br />IZING <br />�fAI�L REVERT TOMAXIM• <br />THE HIGH TEMPERATURE TRANSMITTER (TT-3XX02) LOCATED DOWNSTREAM OF <br />WHEN THE 'IRW IS GPERATING IN THE MANUAL MODE OF GONTIRGE (''AND <br />THE HEATING COIL SHALL PREVENT OVER HEATING OF THE SUPPLY AIR <br />I ITS <br />STREAM. WHEN EXCESSIVE TEMPERATURE IS SENSED, THE PLC SHALL REDUCE <br />FA TO MAXI 1\1 lvi <br />c rTT'n'O <br />STEAM FLOW TO THE HEATING COIL AS REQUIRED TO MAINTAIN TT-3XX02 <br />HIGH TEMPERATURE SET POINT. ONCE THE SPACE TRANSMITTER DEMAND DROPS <br />BELOW THE DUCT TRANSMITTER, THE SPACE TRANSMITTER SIGNAL SHALL BE <br />WHEN OPERATIONAL MODE A PUSH BUTTON (HS-OXX02) IS SELECTED AND THEE <br />USED BY THE PLC TO RESUME CONTROL. <br />HOA'S ARE IN THE AUTO POSITIONS, THE PLC SHALL AUTO MATI <br />ACCESS TO CHANGE THE HEATING CONTROL (SECOND STAGE) SET POINTS UST FANS (EF), SUPPLY FANS (SF), ^" „EAT <br />SHALL BE PASSWORD PROTECTED SO AS TO BE ACCESSIBLE TO HVAC g <br />. EQUENCE OF OPERATION FOR EACH <br />P S L <br />D Y BE AS PREVIOUSLY DESCRIBED WITH THE <br />FOLLOWING MODE SPECIFIC REQU REMENTS.BOOTH EXHAUST FANS (EF SHALL <br />SURESTEAA II <br />OPERATE IN THE 25,000 CFM (EACH) SETTING.BOOTH SUPPLY FANS SF) <br />PATE T(� TI IE I' IA AI DIEIEP rl IAI nE (�(�nlTn/�I En nV nl/�nAAAI V <br />FLOW <br />SHALL OPERATE IN THE 25,000 CFM (PER SET OF 2) SETTING. TWO STAGE <br />HEATING SHALL BE ACT AT . PREHEAT HEATING SHALL NORMALLY BE <br />meDIJbkTE THE N16V Te MAINTAIN THE SPAISE DESIGN SET Paw <br />T 0 0 T DEGREES F OR LOWER). <br />.. <br />Lft <br />Mai - .- <br />- -' -- <br />WHEN OPERATIONAL MODE B PUSH BUTTON (HS-OXX03) IS SELECTED AND THE <br />E INDOOR <br />AMBIENT TEMPERATURE OVER A PERIOD OF 40 MINUTES. V g <br />VERTICAL PAINT BOOTH LID AND DOOR CONTROL <br />THE BOOTH CLOSURE LID AND HORIZONTAL SLIDING DOOR CONTROLS WILL BE <br />PROVIDED BY THE VERTICAL PAINT BOOTH SUPPLIER. OPERATIONAL MODES A, <br />B AND C SHALL NOT BE ALLOWED TO OPERATE UNTIL A SIGNAL IS RECEIVED <br />FROM THE WING PREPARATION AND PAINT CONTROL PLC, SUPPLIED BY THE <br />BOOTH VENDOR, INDICATING THE LID AND SLIDING DOORS ARE COMPLETELY <br />CLOSED. <br />THE PREVIOUSLY MENTIONED WING PREPARATION AND PAINT CONTROL PLC <br />WILL NOT ALLOW WING PREPARATION ACTIVITIES OR PAINTING ACTIVITIES <br />TO BEGIN UNTIL THE LID AND SLIDING DOORS ARE COMPLETELY CLOSED AND <br />THE APPROPRIATE OPERATIONAL MODE IS PROVEN. PROVIDE A SIGNAL TO THE <br />WING PREP AND PAINT CONTROL PLC INDICATING THE SYSTEMS ARE <br />OPERATING IN THE APPROPRIATE OPERATIONAL MODE. <br />THE CONTROL SYSTEM SUPPLIER AND THE VERTICAL PAINT BOOTH SUPPLIER <br />SHALL WORK TOGETHER TO COORDINATE INTERFACE REQUIREMENTS BETWEEN <br />THE WING PREPARATION AND PAINT CONTROL PLC AND THE HVAC SYSTEM <br />CONTROL PLC. <br />EMERGENCY SHUTDOWN - VENTILATION SYSTEM EMERGENCY SHUTOFF <br />WHEN THE EMERGENCY SHUTDOWN SWITCH (HS-OXXO1 , BREAK GLASS TYPE) IS <br />SELECTED, THE PLC SHALL AUTOMATICALLY OVERRIDE ALL OTHER MODES OF <br />OPE <br />�SF HAUST FANS (EF), SUPPLY FANS <br />WHEN THESE SYSTEMS ARE <br />EA OMPONENTS (AUTOMATIC AIR <br />DAMPERS, TEMPERATURE CONTROL VALVES, . SHALL RETURN TO THEIR <br />FAIL SAFE (NORMAL) POSITIONS. D <br />OFF MODE - BOOTH VENTILATION SYSTEM L� <br />WHEN THE OFF MODE PUSH BUTTON HS-OXX05) IS SELECTED AND THE HOA'S <br />ARE IN THE AUTO POSITIONS, THE PLC SHALL AUTO <br />T B 0 AUST FANS (EF), SUPPLY FANS (SF AND IIEAT- REOOvrnv <br />WHEN THESE SYSTEMS ARE DEACTIVA!� <br />0 C ONENTS (AUTOMATIC AIR DAMPERS, TEMPERATURE CONTROL B <br />VA VE E C.) SHALL RETURN TO THEIR FAIL SAFE (NORMAL) POSITIONS. <br />g EQUIPMENT START-UP PRIORITY <br />THE START-UP SEQUENCE FOR EQUIPMENT ASSOCIATED WITH THIS BOOTH <br />SHALL BE AS LISTED IN THE START-UP PRIORITY LIST THAT FOLLOWS. ONCE <br />A COMMAND IS ISSUED TO INITIATE A PARTICULAR OPERATIONAL MODE, THE <br />FIRST SYSTEM SHALL BE ENERGIZED. THE SUBSEQUENT SYSTEMS SHALL BE <br />SEQUENTIALLY ENERGIZED AS LISTED IN THE START-UP PRIORITY LIST WITH <br />A MINIMUM 5 SECOND TIME DELAY (ADJUSTABLE) BETWEEN EACH GROUPING OF <br />EQUIPMENT FOR THAT PARTICULAR OPERATIONAL MODE. ALL AUTOMATIC <br />SHUTDOWN SAFETIES SHALL BE OVERRIDDEN FOR 90 SECONDS (ADJUSTABLE) <br />TO ALLOW THE SYSTEM TO STABILIZE. <br />START-UP PRIORITY LIST: <br />1 - BOOTH EXHAUST FANS (EC"3R Y. <br />2 - BOOTH SUPPLY FANS (SF BOTH SETS <br />DB PtENGI14EERS <br />ISSUED FOR CONSTRUCTIONMW F-)PROFESSIONAL STAMP &SIGNATURE <br />APPLIES TO WORK WITHIN THE CLOUDED Seattle H Spokane H Baltimore DESIGN BY `Si DATE 06.27.2022 <br />REVISION AREAS ONLY AS INDICATED <br />SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE UINAWN UMIL SUISHILLVERTICAL PAINT BOOTH UUKKtNI KtVISIUN 1711UL unit <br />RECORD DWG. — LOCKWOOD GREENE 03/94 \ Cy ACCEPTABILITY C.TOLLIVECKEDER 6-19-92 <br />C� q0 THIS DESIGN AND/OR CHECKED ER 06.27.2022 <br />tiP1f" i SPECIFICATION IS APPROVED R. RODEMS 8-92 SYST. GUIDELINES & SPECS. - REMOVAL SHEET <br />A 767 VERTICAL PAINT BOOTH VENTILATION W5523782 FSi KMC 06.18.2021 ® W " TITLE 767 VERTICAL PAINT BOOTH VENTILATION -PHASE 2 M310aR <br />BO�,w� APPROVED BY DEPT. DATE K.STUCKWISH 6-19-92 <br />B 767 VERTICAL PAINT BOOTH VENTILATION — PHASE 2 W5523782 FSi KMC 06.27.2022 CHECKED <br />Az, �R7 D.8-19-92 BUILDING 40-051 <br />/ST N �`� APPROVED JOB NO. COMP NO. <br />�S3/ONAL ENS\I IJ.S HOPKINS 1 9-11-92 1 94049.01/31329.04 <br />"�°�' HLRCROTZER 9-11-92 MECHANICAL MASTER COL. EVERETT, INq Dwc Na. 40-051-M310aR <br />.27 <br />