Laserfiche WebLink
City of Everett 26 05 73.19 - 7 <br /> Inductive Charging Infrastructure for Everett Transit <br /> 3.4 LABELING <br /> A. Apply one arc-flash label on front cover of each section of equipment and on side or <br /> rear covers with accessible live parts and hinged doors or removable plates for each <br /> equipment included in study. Base arc-flash label data on highest values calculated at <br /> each location. <br /> B. Each piece of equipment listed below not fed by single transformer smaller than <br /> 75 kVA must have arc-flash label applied to it: <br /> 1. Panelboards. <br /> 2. Low voltage transformers. <br /> 3. Safety switches. <br /> C. Note on record Drawings location of equipment where personnel could be exposed to <br /> arc-flash hazard during their work. <br /> 1. Indicate arc-flash energy. <br /> 2. Indicate protection level required. <br /> 3.5 APPLICATION OF WARNING LABELS <br /> A. Install arc-flash warning labels under direct supervision and control of qualified <br /> electrical professional engineer. <br /> END OF SECTION 260573.19 <br /> 26 05 73.19 - 7 ARC-FLASH HAZARD ANALYSIS <br />