Laserfiche WebLink
:, Lighting, Motor and Electrical Requirements List, pg 2 of 10 <br /> 2018 WSEC Requirements for Commercial Buildings including Group R2,R3&R4 over 3 stories&all R1 -- Administered by©2022 NEEA,All rights reserved <br /> The following information is necessary to check a permit application for compliance with the lighting systems,motors and electrical system requirements in the <br /> Washington State Energy Code,Commercial Provisions. <br /> For questions about this report,contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport©waenergycodes.com <br /> NA C405.2.1.2 Occupant sensor Indicate each aisleway and corridor within a <br /> controls-warehouses warehouse space are designated as separate <br /> spaces zones that are independently controlled <br /> NA Indicate occupant sensors are configured to <br /> automatically reduce lighting power by 50% <br /> when the zone is unoccupied and 100%off <br /> after the zone is unoccupied for over 20 <br /> minutes;indicate controls are configured to <br /> automatically restore lighting to full power <br /> when the zone or space is occupied <br /> NA C405.2.1.3 Occupant sensor For open plan office areas larger than 300 sf, <br /> controls-open plan indicate general lighting is provided with <br /> office areas vacancy controls that reduce lighting power by <br /> not less than 80%and are configured to turn <br /> luminaires 100%off when the space is <br /> unoccupied;indicate that no individual control <br /> zone area exceeds 600 sf <br /> C405.2.1.4 Occupant sensor indicate parking garage general lighting is <br /> controls-parking provided with vacancy controls that reduce <br /> garages bilking power by not less than 30'c and are <br /> configured to turn luminaires 100rb off when <br /> no vehicles or pedestrians are present,unless <br /> eligible for an exception;indicate that no <br /> individual control zone area exceeds 3.600 sf <br /> NA C405.2.1.5 Occupant sensor Indicate stairway lighting is provided with <br /> controls-enclosed vacancy controls that reduce lighting power by <br /> fire-rated stairwells not less than 50%when the stairway in <br /> unoccupied <br /> NA C405.2.2.1 Automatic time Indicate spaces on plans where time switch <br /> switch controls controls turn luminaires 100%off during <br /> unoccupied hours <br /> YES Indicate spaces on plans where time switch Elec Sheets <br /> controls are configured to turn on lighting to <br /> full power versus 50%power <br /> NA Indicate locations of override switches on <br /> plans and the lighting zone(s)served;indicate <br /> that the area(s)served by each override switch <br /> does not exceeds 5,000 sf <br /> NA C405.2.1, Digital timer switch Indicate digital timer switch control includes: <br /> Exception 3 manual on/off,time delay,audible and visual <br /> indication of impending time-out <br /> NA C405.2.4.2 Daylight zones- Indicate primary and secondary sidelit <br /> C405.2.4.3 Sidelit and toplit daylight zone floor areas on plans <br /> NA Indicate toplit daylight zone floor areas on <br /> plans <br /> NA For small vertical fenestration assemblies <br /> (rough opening less than 10 percent of <br /> primary daylight zone floor area)where <br /> daylight responsive controls are not required, <br /> provide fenestration area to daylight zone <br /> floor area calculation(s) <br /> Page 2/10 <br />