Laserfiche WebLink
• <br /> • • • <br /> 12. A barrier should be shown in Stairway A that prevents persons from continuing past the <br /> level of exit discharge.Section 1023.8 Response: Gates have been added to Stairs A and C. <br /> See the revised sheets A-2.1,A-2.2 and A-2.7. <br /> 13.The stairway identification signs should be detailed on the plans.Section 1023.9 Response: <br /> See the revised sheet A-0.2- Building Code Note and A-7.3 Stairway Details with stairway sign <br /> information and stairway section with the dimensions and the location of sign. <br /> 14.The utility rooms on the residential levels should be separated from the corridors by <br /> minimum 30-minute construction and 20-minute doors.Section 1020.1 Response: all <br /> corridor walls are one hour fire rating in order to simplify drywall purchasing during <br /> construction. See the sheet of wall types- A-9.1- Wood Framing and Floor/Ceiling types for one <br /> hour rating information. The utility entry doors are 20 minutes. See the revised door schedule- <br /> A-2.7. <br /> Accessibility (Chapter 11 IBC and ICC ANSI A117.1-2009) <br /> 1. Operable parts in the Type A units (lighting controls,electrical panelboards,electrical <br /> switches and receptacle outlets,kitchen exhaust fans,environmental controls,appliance <br /> controls,operating hardware for operable widows,plumbing fixture controls and user <br /> controls for security or intercom systems) should be shown to comply with ANSI Section <br /> 309.ANSI Section 1003.9.Response: See added note on sheet A-0.2 under Accessibility notes. <br /> 2. The cabinetry in the Type A units under the toilet room lavatories (ANSI Sections <br /> 1003.11.2.2 & 1003.11.2.4.4): <br /> a. Should be shown a minimum of 18"away from the centerline of the toilets, Response: <br /> See revised sheets A-6.0 and A-6.1. Dimension from cabinets have been added. <br /> b. Should be shown to be able to be removed without removal of the lavatory, Response: <br /> See revised sheets A-6.0 and A-6.1. Note indicating removable casework has been added. <br /> c. The floor finish should extend under the cabinetry,and Response: See revised sheets A- <br /> 6.0 and A-6.1. Note has been added. <br /> d. The walls behind the cabinetry should be finished. <br /> Response: See revised sheets A-6.0 and A-6.1. Notes have been added. <br /> 3. The bottom edge of the mirrors Type A units should be dimensioned on the plans (40"max <br /> AFF).ANSI Section 1003.11.2.3 Response: See revised sheets A-6.0 and A-6.1.The elevations <br /> are dimensioned to show maximum height above finished floor of the mirror bottom edge. <br /> 4. The top of the toilet seats in the Type A units should be shown to be between 15-19".ANSI <br /> Section 1003.11.2.4.5 Response: See revised sheets A-6.0 and A-6.1.The elevations are <br /> dimensioned to show maximum height above finished floor of the toilet seat top surface. <br /> 5. Standard accessible details and clearances,grab bar locations (reinforcement) and clear <br /> floor spaces should be provided and dimensioned in plan and elevation for the Type B toilet <br /> rooms to include the path of compliance (Option A or Option B).ANSI Section 1004.11 <br /> Response: See new sheets A-6.2-A-6.6 with labels, grab bar locations,clearances and <br /> dimensions on the plans and interior elevations. <br />