• S <br /> Mr. Art Skotdal <br /> Skotdal Real Estate <br /> Plan Check Number: B1906-031, Second Building Review- Structural <br /> October 18, 2019 <br /> i. Calculations substantiating the design shall be submitted for review. The <br /> calculations shall include, but are not limited to, the flexural and shear strength of <br /> the slab. <br /> ii. Calculations substantiating the shear connection between the slab and the <br /> supporting beams and other framing. <br /> iii. Details for the connections of the slab to the supporting framing. This is not <br /> provided in Section 1/S3.00. <br /> iv. The supplemental calculations for the design of the beams on Grids 4 and 4.9 <br /> considering torsional effects. Note that the beam on Grid 4.9 has both the loading <br /> and supports on located on opposite faces and eccentric from the beam centerline. <br /> e. Grid F.6-G/4.7-5 on Sheet S2.03. See the previous comment. Note that this area appears <br /> to be stairway per Partial Plan 5/A7.2. <br /> f. Grid E-F/3-3.2 on Sheet S2.01. This area is included in the PT-design calculations, and is <br /> shown with post-tensioning, but the slab area is not shown in the drawings. <br /> g. Grid E-F/3-3.2 on Sheet S2.09. Verify if post-tensioning should extend through this area. <br /> 20. No additional comment. <br /> 21. No additional comment. <br /> 22. No additional comment. <br /> 23.This comment has not been addressed. The original comment is provided below. The response <br /> is not adequate to address the comment. Sheet A-2.2a shows the required step; the structural <br /> drawings should be consistent and indicate slopes where required. The structural calculations <br /> should match the step height as this is the critical condition and represents the effective <br /> member depths that the prestressed tendons must pass through; it is presumed that the slope <br /> is incidental to the design. <br /> The design of the Level 1 slab is shown on Sheets S2.06, 2.07, and A-2.2a. See IBC Section <br /> 107.2.1, 1603.1, and 1604.1. The following comments shall be addressed: <br /> a. Sheet S2.06 appears to show an 8-inch thick depressed slab area between Grids A-B.3 with <br /> a uniform 6-inch step down from east to west. However, Sheet A-2.2a shows typically <br /> shows a 4-inch step, except between Grids 6.4-8 where the step is 3-inches. The drawings <br /> shall be revised for consistency. <br /> b. Continuing with the previous comment, the structural calculations have been performed <br /> considering a 6-inch step. The design shall be revised as needed pending the determination <br /> of the correct step heights. <br /> c. The structural calculations appear to be indicating that the Level 1 PT slab includes a 14- <br /> inch thick region between Grids A and D. This is not indicated in the Plans on Sheets S2.06 <br /> and S2.07. It appears a step is indicated for a portion of this area on Sheet S2.06; an <br /> unknown solid line is obscuring the potential step extent. The note at Grid A-D/1-4 <br /> indicates the slab is only 8 inches thick. The plans shall be revised, or the calculations shall <br /> be revised for consistency with the plans. <br /> O3200 Cedar Street © 425.257.8810 0 everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gCi;age <br /> ov/permits <br /> 7of11 <br />