Laserfiche WebLink
b. The common path of travel for southern half of Level P1 is measured at 99' <br /> (verification is required) however the occupant load is greater than 29 persons and <br /> therefore requires two exits from the southern half of the garage. <br /> 3. Please provide the exact floor area (net) of Amenity Room L100. If the occupant load is <br /> 50 or greater, the space will need to comply as an Assembly Occupancy (two means of <br /> egress, panic hardware, exit signs, etc.). Section 1004.1 <br /> 4. Amenity Room L100 has an occupant load greater than 10. A pivoted or side-hinged <br /> swinging door is required. Section 1010.2 <br /> 5. Standby power should be specified on the plans for the elevator. Section 1009.4 <br /> 6. The locations, use-instructions and signage requirements for the two-way communication <br /> system at the elevator landings should be shown on the plans. Section 1009.8 <br /> 7. Emergency egress lighting should be provided at the exterior landings at the exterior exit <br /> doorways. Section 1008.3.2, Item 5 <br /> 8. A sign stating Exit in raised characters and braille and complying with ICC A117.1 should <br /> be shown adjacent to the exterior exit doorways. Section 1013.4 <br /> 9. The stairways and landings in the Type I portion of the building should be constructed of <br /> non-combustible construction. Section 1011.7 <br /> 10.The exit passageway portion of Stair B should be shown with 90-minute doors (101, 102 <br /> & 114) and minimum two-hour walls (wall type C-2-2 is not a two-hour rated wall due to <br /> the one-hour partition on top of the CMU). Section 1023.3 <br /> 11.The lower handrail extensions should be shown to extend a minimum of one tread depth <br /> at the same angle as the handrails on Sheets L4.02 &A-7.2 (vs. horizontal like the upper <br /> extensions). Section 1014.6 <br /> 12. A barrier should be shown in Stairway A that prevents persons from continuing past the <br /> level of exit discharge. Section 1023.8 <br /> 13.The stairway identification signs should be detailed on the plans. Section 1023.9 <br /> 14.The utility rooms on the residential levels should be separated from the corridors by <br /> minimum 30-minute construction and 20-minute doors. Section 1020.1 <br /> Accessibility (Chapter 11 IBC and ICC ANSI A117.1-2009) <br /> 1. Operable parts in the Type A units (lighting controls, electrical panelboards, electrical <br /> switches and receptacle outlets, kitchen exhaust fans, environmental controls, appliance <br /> controls, operating hardware for operable widows, plumbing fixture controls and user <br /> O 3200 Cedar Street © 425.257.8810 O tlee@everettwa.gov <br /> Everett, WA 98201 425.257.8857 fax everettwa.gov <br />