Laserfiche WebLink
HVAC Systems <br />PROJECT: Kimley Horn Everett <br />LOCATION: Everett, WA <br />PROJECT #: 60940287 <br />SYSTEM/UNIT: HVAC-01/(E) HPSM-02 <br />Unit Data <br />Location Ceiling Lv13 <br />Serves Conf 301 <br />Manufacturer McQuay <br />engineered <br />� I systems <br />DATE: 5/10/2023 <br />CONTACT: Steve Lybecker <br />Equipment Data <br />TAB By Kalani Rivera <br />TAB Date 05/08/2023 <br />Design Supply CFM <br />230 CFM <br />Actual Supply CFM <br />359 CFM <br />Design Return CFM <br />230 CFM <br />Actual Return CFM <br />359 CFM <br />Design Minimum Outside CFM <br />0 CFM <br />Actual Minimum Outside CFM <br />0 CFM <br />Log: I <br />HVAC-01/(E) HPSM-02 5/10/2023 Travis Carlson Single speed fan. <br />HVAC-01/(E) HPSM-02 Supply Outlet - Constant Volume Summary <br />System/Unit Type <br />Size AK Design (CFM) Final (CFM) %Final <br />A` <br />• - 1 <br />Totals: <br />1. 11 <br />?30 359 156 <br />SYSTEM/UNIT: HVAC-01/(E) HPSM-03 <br />Location <br />Serves <br />Manufacturer <br />ceumg Lvi3 <br />Off 303, 304 <br />McQuay <br />� w0\ <br />'NO <br />r Equipment Data <br />TAB By Kalani Rivera <br />TAB Date 05/08/2023 <br />Design Supply CFM 230 CFM <br />Actual Supply CFM 268 CFM <br />Design Return CFM 230 CFM <br />Actual Return CFM 268 CFM <br />Design Minimum Outside CFM 0 CFM <br />Actual Minimum Outside CFM 0 CFM <br />Log: HVAC-01/(E) HPSM-03 5/10/2023 Travis Carlson Single speed fan. <br />HVAC-01/(E) HPSM-03 Supply Outlet - Constant Volume Summary <br />System/Unit Type Size AK Design (CFM) Final (CFM) %Final <br />Totals: - - 230 268 117 <br />ACCO Engineered Systems <br />