Laserfiche WebLink
HVAC Systems <br />PROJECT: Kimley Horn Everett <br />LOCATION: Everett, WA <br />PROJECT #: 60940287 <br />SYSTEM/UNIT: HVAC-01/(E) HPSM-04 <br />Unit Data <br />Location Ceiling LA3 <br />Serves Off 305,307 <br />Manufacturer McQuay <br />engineered <br />� I systems <br />DATE: 5/10/2023 <br />CONTACT: Steve Lybecker <br />Equipment Data <br />TAB By Kalani Rivera <br />TAB Date 05/08/2023 <br />Design Supply CFM <br />230 CFM <br />Actual Supply CFM <br />355 CFM <br />Design Return CFM <br />230 CFM <br />Actual Return CFM <br />355 CFM <br />Design Minimum Outside CFM <br />0 CFM <br />Actual Minimum Outside CFM <br />0 CFM <br />Log: I <br />HVAC-01/(E) HPSM-04 5/10/2023 Travis Carlson Single speed fan. <br />HVAC-01/(E) HPSM-04 Supply Outlet - Constant Volume Summary <br />SYSTEM/UNIT: HVAC-01/(E) HPSM-05 <br />Unit ... Equipment ... . <br />Location Ceiling LA3 'd TAB By Kalani Rivera <br />Serves Off 308 Production - TAB Date 05/09/2023 <br />Manufacturer McQuay <br />O` r Design Supply CFM 800 CFM <br />Actual Supply CFM 1028 CFM <br />Design Return CFM 800 CFM <br />Actual Return CFM 1028 CFM <br />Design Minimum Outside CFM 0 CFM <br />` Actual Minimum Outside CFM 0 CFM <br />Log: <br />HVAC-01/(E) HPSM-05 Supply Outlet - Constant Volume Summary <br />System/Unit <br />Outlet-01 <br />Type <br />CD <br />Size <br />2408 <br />Design (CFM) <br />135 <br />141 <br />%Final <br />104 <br />Outlet-02 <br />CD <br />2408 <br />165 <br />202 <br />122 <br />Outlet-03 <br />CD <br />2408 <br />165 <br />233 <br />141 <br />Outlet-04 <br />CD <br />2408 <br />165 <br />207 <br />125 <br />Outlet-05 <br />CD <br />2408 <br />170 <br />:0i ME <br />245 <br />1028 ME <br />144 <br />129 <br />ACCO Engineered Systems <br />