Laserfiche WebLink
6/16/2022 <br />`' City of Everett Page 3 <br />7:13Y16AM <br />INSPECTION ACTIVITY REPORT <br />4/13/2022 4/13/2022 PLUMB JJM <br />NOT READY <br />(4/13/2022 11:49 AM JJM) <br />03-ROUGH IN <br />Highly recommend calling licensed <br />plumbing contractor to perform <br />repairs/corrections. <br />- Replumb all DWV ABS pipe in <br />crawlspace per 2018 UPC code standards. <br />1.) Currently there is no vent on main bath <br />toilet. <br />- Toilet vents are minimum 2" per code. <br />Plumb vent per UPC 905.2. <br />2.) Make sure legal long sweep fittings <br />and or wye and 1/8th bend fittings are used <br />where needed. Current fittings dont meet <br />drainage fitting requirements. <br />3.) Make sure all horizontal drianage <br />piping is running at minimum 2% slope per <br />code. <br />5.) Cap of abandoned hot and cold water <br />lines for laundry tray behind drywall with <br />approved fittings. <br />6.) Extend AW standpipe to outside of <br />drywall. <br />7.) Move all hot and cold pex water lines <br />in half bath as close as possible to heated <br />envelope of building per code. <br />8.) Make sure all ABS waste piping is <br />supported at proper 4' intervals on the <br />horizontal per code. <br />9.) Make sure all ABS waste fittings are <br />properly glued per code. Several of the <br />current fittings are completely unglued. <br />10.) Lav drain for back bathroom is <br />currently not attached to drainage system <br />and draining directly onto ground in <br />crawlspace <br />11.) Newly installed vent piping for toilet in <br />back bathroom was covered up before <br />rough in inspection approval. <br />12.) Put ABS DWV system on head test <br />through roof vents to proove no leaks on <br />system after corrections are complete. <br />4/15/2022 4/15/2022 PLUMB JJM <br />NOT READY eTRAKiT Inspection <br />4/14/2022 6:41 PM RANDY wiley <br />03-ROUGH IN <br />Request <br />Between 12 and 3 <br />Contact Name: RANDY wiley <br />Site Address: 2916 LEONARD DR <br />Phone:4253591090 <br />e-Mail: wileyloans@gmail.com <br />4/28/2022 4/28/2022 PLUMB JJM <br />NO ACCESS eTRAKiT Inspection <br />4/27/2022 5:38 PM Melissa Mylius <br />03-ROUGH IN <br />Request <br />please call 1 hour before so I can meet to let <br />in. thanks <br />Contact Name: Melissa Mylius <br />Site Address: 2916 LEONARD DR <br />Phone:4252444747 <br />e-Mail: mcm13@rocketmail.com <br />(4/28/2022 11:39 AM JJM) <br />- No access. Call between 7:30 and 8:30 <br />AM M-F to get an arrival window. <br />INSPI2 CIMSYSTEMS <br />