LONGITUDE <br /> ONE I WENT Y' <br /> ENGINEERING&DESIGN <br /> 6.) See Detail 14 on Sheet SD-2. It appears that the new RB-1 beam has a tapered end with a 0-inch <br /> depth at the end of the taper. Calculations should be updated to reflect the detail or detail <br /> should be updated.Adjustments to strength should be taken into consideration. Note that the <br /> current calculations do not include the dead load from the ceiling framing. <br /> Response: Beam has been tapered at end for aesthetics per arch. The beam performs as a <br /> cantilever section at tapered end with perpendicular joists @ 16" o.c. across the beam. The last <br /> joist can be conservatively assumed that it will be placed at 16"from end of 0in depth cantilever. <br /> If beam has constant slope from 18" to 0" over a 48" long cantilever, then at 16"from end, beam <br /> depth will be 12". <br /> Based on limitations of software, tapered end analysis is not permitted. However, an isolated <br /> analysis at the cantilever end with a 12" deep section and uniform loading, is a conservative and <br /> similar analysis method.Thus, please reference revised RB-1 calculations. <br /> 7.) Continuing with the previous comment, it is not clear if the connection from the 2x bracing is to <br /> the roof rafters or 2x ridge board. Provide additional details showing the connection, length of <br /> braces,and height from the ceiling to roof. Provide calculations substantiating the design. <br /> Response: Detail 14/sd-2 5„L,vs that Li ie 2x bracing ,s to be •..onnected to the rafters with 10d toe <br /> nails at each brace end. Additional note stating max length of braces to be 5ft max (per site <br /> conditions) has been added. Detail already shows max brace span of 5ft. Detail shows sufficient <br /> information for construction. <br /> 8.) Continuing with the previous comment, calculations should be submitted for review of the <br /> existing 2x ridge board. It appears the 2x ridge board is spanning 60 inches due to the spacing <br /> of the bracing. <br /> Response:2x braces shall be no more than 5ft long. Similarly the ridge board is shown as 5ft max <br /> with 5ft of tributary area. As noted in updated attached calculations,all members are sufficient. <br /> 9.) See Sheet S-5. Plans should provide a detail for Beam RB-3.The notes on the plans are not <br /> clear. R106.1.1 <br /> Response:Note specified at beam RB-3 is sufficient for construction.The note states that the beam <br /> shall be located above the roof joists, but below the rafters(essentially within the attic space).The <br /> ceiling joists (running perpendicular) are then to be hung from the new beam with H2.5A clips at <br /> each joists as it runs past the new LVL. If upon discovery during the remodel, it is found that there <br /> are existing braces in the way of the new LVL, the braces are to be relocated above the LVL <br /> (instead of on the existing ceiling joists). New LVL beam will have diagonal kickers at end supports <br /> to help brace/stabilize the member. If conditions are different in the field, then an RFI letter will be <br /> issued with an alternate solution as required. <br />