y • <br /> a. Section C2/A4.01 for Building 1 shows (2)2x6 framing at 24 inches. It is not clear if this <br /> framing is fastened together, and also sistered to existing framing. Fasteners between <br /> the 2x6s, and also to the existing framing if intended, should be specified. <br /> Notes have been added to indicate fastening of the(2)2x6 framing. See updated <br /> C2/A4.01 and CS1.01. <br /> b. Section C2/A4.01 for Building 1 references Detail B3/A8.13 for connection of the 2x6s at <br /> the beams. The detail only shows a Simpson H2.5A for framing coming from the right. It <br /> is not clear if the framing on the left also requires ties, nor if the far ends of the framing <br /> not shown in the detail should similarly be provided with ties. <br /> The detail has been updated to reflect hurricane ties on each side. Notes have <br /> been added indicated that hurricane ties shall be provided at all locations where <br /> there are new rafters or new roof beams installed. See updated detail B3/A8.13 and <br /> notes on CS1.01. <br /> c. Section C2/A4.02 for Building 1 includes a center section that is not shaded, but does not <br /> indicate supplemental framing. Confirm this roof does not require modification. <br /> See A4/A4.02 roof framing plan for required roof framing. This location does <br /> require modification. <br /> Sincerely, <br /> CC: <br /> Letterhead template. <br /> 3 \ 3 <br />