Ms. Corrie Stark <br /> Plan Check Number: B2006-047, Second Building Review <br /> November 24, 2020 <br /> supported on the existing slab-on-grade (SOG), walls supported on the new floor or the SOG, <br /> and new framing and foundations to support the new framing above. A minimum of one full <br /> building section parallel to the GLB should be provided. A perpendicular section at the water <br /> heater should also be provided to show the supporting framing. Additional sections should be <br /> provided as needed to show the proposed work. See Section R106.1.1. <br /> Architectural <br /> 1. The kitchen should be provided with local exhaust per IRC Section R303.4. <br /> 2. The location, type, size, and swing of all doors should be specified. The minimum clearance for <br /> all doors should be 6'-8" per IRC Section R305.1. <br /> 3. Provide exterior doors and landings per IRC Sections R311.1 through R311.3. Threshold steps <br /> should comply with Section R311.3.1 or R311.3.2. <br /> 4. The "New Floor Plan" on Sheet Al includes a new glulam beam (GLB). The minimum 7-foot <br /> clearance to the beam should be shown in the building section. See Section R305.1. <br /> 5. Roof ventilation should be specified complying with IRC Section R806; a minimum 1" air gap <br /> should be provided between the insulation and roof sheathing per Section R806.3. <br /> 6. Sections 1/A-1 and 2/A-1 specify R-21 batt insulation in nominal 4-inch exterior walls. The R-21 <br /> insulation requires a minimum 5.5-inch wall cavity. The wall cavity should be increased or the <br /> insulation revised to achieve the minimum required thermal rating. See WSEC Section R503.1 <br /> and Table R402.1.1. <br /> 7. Section 2/A-1 specifies R-30 batt insulation. The R-30 insulation requires a minimum 9.25-inch <br /> cavity. The depth of the framing is not specified; structural comments below. The depth <br /> should be sufficient for the insulation and to provide a gap between the insulation and the slab- <br /> on-grade. See WSEC Section R503.1 and Table R402.1.1. <br /> 8. The thermal rating (i.e., Rmin, Umax) should be specified for the exterior doors and windows per <br /> WSEC Tables R402.1.1 or R402.1.3. <br /> 9. The building should be designed to comply with the additional energy efficiency requirements of <br /> WSEC Section R406. The construction drawings should include a schedule listing the selected <br /> energy credits for the proposed project. <br /> 10. The building should specify a whole house ventilation system complying with See IRC Section <br /> M1507.3. The drawings should state compliance with one of the systems specified in Sections <br /> M1507.3.4 through M1507.3.7; the requirements for the selected system should be specified in <br /> the plans. See IRC Section R303.4 (WAC). Where an exhaust fan is required, the location and <br /> exhaust rate should be specified in the plans; the fan should not be located in room that can be <br /> sealed (i.e., closed door) from the majority of the dwelling space. <br /> 3200 Cedar Street © 425.257.8810 0everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 3 of 6 <br />