GENERAL NOTES <br /> 1. CONDUIT: 1/2" MINIMUM, 3/4" MINIMUM FOR ALL <br /> HOMERUNS UNLESS OTHERWISE NOTED. 3/4" FLEX <br /> WITH GROUND WIRE. <br /> 2. CONDUCTORS SHOWN: #12 AWG, STRANDED COPPER, <br /> INSULATION TYPE THHN/THWN, UNLESS OTHERWISE <br /> TOOL SHED TOOL SHED NOTED. <br /> BLDG 45-280 BLDG 45-281 <br /> 3. COLOR CODE CONDUCTORS: IDENTIFY CONDUCTORS <br /> WHICH DO NOT HAVE APPROPRIATELY COLORED <br /> INSULATION WITH COLOR TAPE WHEREVER CONDUCTORS <br /> ARE ACCESSIBLE. IDENTIFY INSULATED GROUND <br /> CONDUCTORS IN ACCORDANCE WITH THE LATEST NEC <br /> (USING TAPE). COLOR CODE AS FOLLOWS: <br /> 45-280 SMK NORTH 45-281 SMK NORTH 120V 277V <br /> BLAC208YBRO <br /> ZONE #:14, L1:14 ZONE #:16, L1:16 A0 (LEFT BUS IN PNL) BLACK BROWN <br /> B0 (CENTER BUS IN PNL) RED ORANGE <br /> s s C� (RIGHT BUS IN PNL) BLUE YELLOW <br /> NEUTRAL WHITE GRAY <br /> 1 EQUIPMENT GROUND GREEN GREEN <br /> ISOLATED GROUND GRN/YEL* GRN/YEL* <br /> *GREEN WITH YELLOW TRACER <br /> 4. DYMO LABEL EACH RECEPTACLE, JUNCTON/OUTLET BOX <br /> AND SWITCH WITH CIRCUIT IDENTIFICATION. <br /> 1/2"C 2#16 1/2"C 2#16 5. POST NEW OR REVISED PANEL SCHEDULES UPON <br /> COMPLETION OF JOB. <br /> CONSTRUCTION NOTES <br /> INSTALL SMOKE DETECTORS (QTY. 4) WITH <br /> ADDRESSABLE SMOKE DETECTORS COMPATIBLE <br /> WITH THE 45-244 BUILDING FACP. WIRE TO <br /> 45-280 SMK SOUTH 3 45-244 BUILDING FACP. <br /> ZONE #:15, L1:15 s s 45-281 SMK SOUTH <br /> ZONE #:17, L1:17 P::� UTILIZE EXISTING UNISTRUT SUPPORT FOR <br /> 3/4"C 2#16 CONDUIT BETWEEN 45-280 AND 45-244. <br /> USE UNISTRUT TO SUPPORT CONDUIT OVER <br /> BUILDING GAP AND CONNECT BACK TO 45-244 <br /> BUILDING . USE EXITING UNISTRU <br /> 3/4"C 2#16 SSTRUCTUREABETW EN 455280 AND 45-244 AS <br /> REFERENCE. <br /> REFERENCE DRAWINGS <br /> 45-244-1E260 45-244 FIRE ALARM PLAN <br /> 2 <br /> TO FIRE ALARM PANEL LOCATED <br /> IN BLDG 45-244 (1E1260) <br /> CREW SHELTER <br /> BUILDING 45-244 <br /> TOOL SHED E IRE ALARM PEAN PROJECT SITE <br /> � FUEL DOCK <br /> SCALE: 1 /4" <br /> — 1 '—O" VV <br /> o �I� <br /> KFYF AN <br /> 4' 2' 0 2' 4' 8' <br /> mm <br /> SCALE: 1/4"=1'-0" <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE ACCEPTABILITY DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL <br /> NEW <br /> DATE <br /> NEW FACP REPLACEMENT 27851053 DA EM MDK 08.29.22 THIS DESIGN AND/OR CHECKED POSITIONS F-4 AND F-5 27851053 04.28.23 <br /> SPECIFICATION IS APPROVED SHEET <br /> A SHOP DRAWINGS AGOW/JS 04.28.23 BOE//VG® m APPRovED BY DEPT. DATE TITLE 1 E261 <br /> CHECKED <br /> e..e <br /> Min BUILDING 45-280 & 281 DB Na. DMP ND. <br /> APPROVED <br /> 45-280-1E260 g <br /> APPROVED ELECTRICAL MASTER EVERETT, WA DWG No. 45-280-1E260 <br />