Laserfiche WebLink
Mr. Ismail Mohammad <br /> 2713 Maple Street, LLC <br /> Plan Check Number: B2101-051, First Building Review <br /> May 3, 2021 <br /> The proposed building has been adjusted to a Duplex, assemblies and wall details have been <br /> added to Sheet A4 Sections per the IRC. <br /> 11. Detail D2/Sheet 5 shows a step in the Upper Floor assembly. The wall between the floor levels <br /> is required to be a one-hour fire partition. See IBC Section 420.2. <br /> Proposed wall assemblies have been added to Sheet A4 Sections per IRC. <br /> 12.The Upper Floor units require minimum 20-minute fire-rated doors accessing the corridor. See <br /> IBC Table 716.5. <br /> The proposed building has been adjusted to a Duplex; IBC is not applicable. <br /> 13. The following comments should be addressed for the"Floor/Ceiling Wood-Framed"detail on <br /> Sheet 5: <br /> a. Detail D2/Sheet 5 appears to show that the existing Upper Floor framing consists of <br /> manufactured wood joists instead of solid 2x framing. The specified detail is not sufficient <br /> for this condition. An alternate floor assembly is required. <br /> b. The floor assembly is required to comply with the sound transmission requirements of IBC <br /> Sections 1207.2 and 1207.3. The proposed assembly does not comply. <br /> The interior existing Floor/Ceiling Wood-Framed framing will be demolished and replaced by a <br /> proposed floor framing, see Sheet A4 Sections for floor assemblies and Sheet A2 Floor Plans for <br /> proposed framing notes and structural notes. <br /> 14.The building consists of 1-hour floor and walls assemblies supported by other construction. <br /> Note that walls are not continuous to the foundation at multiple locations. The supporting <br /> construction is required to have a minimum 1-hour construction. This includes but is not limited <br /> to walls, posts, beams, and floor joists. The note in the "Floor/Ceiling Wood-Framed"detail <br /> stating "walls, posts, and beams to be 1 hr fire rated" is not sufficient. Details for the required <br /> construction should be provided. Construction requiring 1-hour fire protection should be clearly <br /> shown on the plans. Details should reference listed tested assemblies per IBC Section 703.2 or <br /> should comply with IBC Section 721 or 722.6. See IBC Section 708.4. <br /> Details for the proposed assemblies and 1-hour construction has been added to sheet A4 Sections <br /> and sheet A6 Details per IRC. <br /> 15. Continuing with the previous comment, the stairway and hallway extend over the Lower Floor <br /> bedroom for Unit U1. The required construction, including supporting construction, should be <br /> shown in this area. See IBC Sections 107.2.1, 708.4, and 1011.7.3. <br /> The proposed design layout has been adjusted to a Duplex, see sheet A2 Floor Plans for structural <br /> and construction notes. <br /> O3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br /> Everett, WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 3 . <br />