CONCRETE, FOUNDATIONS.AND REINFORCING STEEL: 16. ELECTRICAL METALLIC TUBING(EMT)OR METAL-CLAD CABLE(MC) SHALL BE USED FOR CONCEALED INDOOR LOCATIONS. -
<br /> 1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACI 301.ACI 318,ACI 336,ASTM A184, ASTM A185 AND THE DESIGN 17, SCHEDULE 40 PVC UNDERGROUND ON STRAIGHTS AND SCHEDULE 80 PVC FOR ALL ELBOWS/90s AND ALL APPROVED ABOVE
<br /> AND CONSTRUCTION SPECIFICATION FOR CAST-IN-PLACE CONCRETE. GRADE PVC CONDUIT.
<br /> v
<br /> 2. UNLESS NOTED OTHERWISE, SOIL BEARING PRESSURE USED FOR DESIGN OF SLABS AND FOUNDATIONS IS ASSUMED TO BE 1000 18 LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT(LIQUID-TITE FLEX)SHALL BE USED INDOORS AND OUTDOORS,WHERE VIBRATION SINES h
<br /> Psf_ OCCURS OR FLEXIBILITY IS NEEDED.
<br /> 3. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (f'c)OF 3000 psi AT 28 DAYS, UNLESS NOTED OTHERWISE. NO 19. CONDUIT AND TUBING FITTINGS SHALL BE THREADED OR COMPRESSION-TYPE AND APPROVED FOR THE LOCATION USED. SET wireless_
<br /> MORE THAN 90 MINUTES SHALL ELAPSE FROM BATCH TIME TO TIME OF PLACEMENT UNLESS APPROVED BY THE ENGINEER OF RECORD. SCREW FITTINGS ARE NOT ACCEPTABLE.
<br /> TEMPERATURE OF CONCRETE SHALL NOT EXCEED 90'f AT TIME OF PLACEMENT.
<br /> 4. CONCRETE EXPOSED TO FREEZE-THAW CYCLES SHALL CONTAIN AIR ENTRAINING ADMIXTURES.AMOUNT OF AIR ENTRAINMENT TO BE 20. CABINETS, BOXES AND WIRE WAYS SHALL BE LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, AL,ANSI/IEEE AND THE 5701 SOUTH SANTA FE DRIVE
<br /> NEC. LITTLETON,CO B0120
<br /> BASED ON SIZE OF AGGREGATE AND F3 CLASS EXPOSURE (VERY SEVERE).CEMENT USED TO BE TYPE II PORTLAND CEMENT WITH A
<br /> MAXIMUM WATER-TO-CEMENT RATIO(W/C)OF 0.45. 21. WIREWAYS SHALL BE METAL WITH AN ENAMEL FINISH AND INCLUDE A HINGED COVER, DESIGNED TO SWING OPEN DOWNWARDS
<br /> (WIREMOLD SPECMATE WIREWAY).
<br /> 5. ALL STEEL REINFORCING SHALL CONFORM TO ASTM A615.ALL WELDED WIRE FABRIC (WWF)SHALL CONFORM TO ASTM A185.ALL SPLICES SHALL BE CLASS "B"TENSION SPLICES. UNLESS NOTED OTHERWISE.ALL HOOKS SHALL BE STANDARD 90 DEGREE HOOKS, 22 SLOTTED WIRING DUCT SHALL BE PVC AND INCLUDE COVER(PANDUIT TYPE E OR EQUAL).
<br /> /'(C
<br /> UNLESS NOTED OTHERWISE.YIELD STRENGTH (Fy)OF STANDARD DEFORMED BARS ARE AS FOLLOWS: 23. CONDUITS SHALL BE FASTENED SECURELY IN PLACE WITH APPROVED NON-PERFORATED STRAPS AND HANGERS. EXPLOSIVE ``
<br /> #4 BARS AND SMALLER 40 ksi DEVICES(i.e. POWDER-ACTUATED)FOR ATTACHING HANGERS TO STRUCTURE WILL NOT BE PERMITTED.CLOSELY FOLLOW THE LINES OF
<br /> THE STRUCTURE, MAINTAIN CLOSE PROXIMITY TO THE STRUCTURE AND KEEP CONDUITS IN TIGHT ENVELOPES.CHANGES IN DIRECTION TO
<br /> #5 BARS AND LARGER 60 ksl ROUTE AROUND OBSTACLES SHALL BE MADE WITH CONDUIT OUTLET BODIES.CONDUIT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE CAMP+
<br /> MANNER. PARALLEL AND PERPENDICULAR TO STRUCTURE WALL AND CEILING LINES.ALL CONDUIT SHALL BE FISHED TO CLEAR
<br /> 6 THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL UNLESS SHOWN OTHERWISE ON OBSTRUCTIONS. ENDS OF CONDUITS SHALL BE TEMPORARILY CAPPED FLUSH TO FINISH GRADE TO PREVENT CONCRETE. PLASTER OR DIRT ASSOCIATES
<br /> DRAWINGS: FROM ENTERING.CONDUITS SHALL BE RIGIDLY CLAMPED TO BOXES BY GALVANIZED MALLEABLE IRON BUSHING ON INSIDE AND GALVANIZED
<br /> • CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3" MALLEABLE IRON LOCKNUT ON OUTSIDE AND INSIDE. 19515 N.CREEK PKWY,SUITE 220
<br /> B24. EQUIPMENT CABINETS,TERMINAL BOXES,JUNCTION BOXES AND PULL BOXES SHALL BE GALVANIZED OR EPDXY-COATED SHEET PHONE.
<br /> 4o11
<br /> • CONCRETE EXPOSED TO EARTH OR WEATHER: P ONE1 -W92
<br /> STEEL. SHALL MEET OR EXCEED UL 50 AND BE RATED NEMA 1 (OR BETTER)FOR INTERIOR LOCATIONS AND NEMA 3(OR BETTER) FOR WWW.GAMP25)7ASS0ASSOC.COTS
<br /> • #6 BARS AND LARGER 2" EXTERIOR LOCATIONS.
<br /> • #5 BARS AND SMALLER 1-1/2" 25. METAL RECEPTACLE, SWITCH AND DEVICE BOXES SHALL BE GALVANIZED, EPDXY-COATED OR NON-CORRODING,SHALL MEET OR
<br /> EXCEED UL 514A AND NEMA OS 1 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED(WP OR
<br /> • CONCRETE NOT EXPOSED TO EARTH OR WEATHER: BETTER) FOR EXTERIOR LOCATIONS.
<br /> • SLAB AND WALLS 3/4" 26. NONMETALLIC RECEPTACLE,SWITCH AND DEVICE BOXES SHALL MEET OR EXCEED NEMA OS 2 (NEWEST REVISION)AND BE RATED � G
<br /> 'SJ:+_"
<br /> • BEAMS AND COLUMNS 1-1/2" NEMA 1 (OR BETTER)FOR INTERIOR LOCATIONS AND WEATHER PROTECTED(WP OR BETTER) FOR EXTERIOR LOCATIONS. t� ed 1','�•
<br /> 7. A TOOLED EDGE OR A 3/4"CHAMFER SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE, UNLESS NOTED OTHERWISE, 27. THE CONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE CARRIER AND/OR DISH Wireless L.L.C.AND iy�
<br /> IN ACCORDANCE WITH ACI 301 SECTION 4.2.4. TOWER OWNER BEFORE COMMENCING WORK ON THE AC POWER DISTRIBUTION PANELS. 1�0
<br /> 28. THE CONTRACTOR SHALL PROVIDE NECESSARY TAGGING ON THE BREAKERS. CABLES AND DISTRIBUTION PANELS IN ACCORDANCE i '
<br /> WITH THE APPLICABLE CODES AND STANDARDS TO SAFEGUARD LIFE AND PROPERTY. ,pt
<br /> FI FCTRICAL INSTAI I ATION NOTES'
<br /> 1, ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, NEC AND ALL APPLICABLE 29. INSTALL LAMICOID LABEL ON THE METER CENTER TO SHOW"DISH Wireless L.L.C.
<br /> FEDERAL, STATE,AND LOCAL CODES/ORDINANCES. 30. ALL EMPTY/SPARE CONDUITS THAT ARE INSTALLED ARE TO HAVE A METERED MULE TAPE PULL CORD INSTALLED.
<br /> 2. CONDUIT ROUTINGS ARE SCHEMATIC. CONTRACTOR SHALL INSTALL CONDUITS SO THAT ACCESS TO EQUIPMENT IS NOT BLOCKED 7 IS A VIOLATION OF LAW EON ANY PERSON.
<br /> AND TRIP HAZARDS ARE ELIMINATED. of A UCENSED
<br /> ENGINEER.
<br /> TD ALTER THIS DOCUMENT.
<br /> 3. WIRING, RACEWAY AND SUPPORT METHODS AND MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF THE NEC.
<br /> DRAWN BY: CHECKED BY:APPROVED BY,
<br /> 4. ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS REQUIRED BY THE NEC,
<br /> 4.1. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OF APPROVAL,AND SHALL CONFORM TO REQUIREMENT OF JAC JAC JAC
<br /> THE NATIONAL ELECTRICAL CODE. REDS REV/. ---
<br /> 4.2. ALL OVERCURRENT DEVICES SHALL HAVE AN INTERRUPTING CURRENT RATING THAT SHALL BE GREATER THAN THE SHORT CIRCUIT
<br /> CURRENT TO WHICH THEY ARE SUBJECTED. 22,000 AIC MINIMUM.VERIFY AVAILABLE SHORT CIRCUIT CURRENT DOES NOT EXCEED THE CONSTRUCTION
<br /> RATING OF ELECTRICAL EQUIPMENT IN ACCORDANCE WITH ARTICLE 110.24 NEC OR THE MOST CURRENT ADOPTED CODE PRE THE DOCUMENTS
<br /> GOVERNING JURISDICTION.
<br /> 5. EACH END OF EVERY POWER PHASE CONDUCTOR,GROUNDING CONDUCTOR,AND TELCO CONDUCTOR OR CABLE SHALL BE SUBMITTALS
<br /> LABELED WITH COLOR-CODED INSULATION OR ELECTRICAL TAPE (3M BRAND, 1/2"PLASTIC ELECTRICAL TAPE WITH LA'PROTECTION, OR REV DATE DESCRIPTION
<br /> EQUAL).THE IDENTIFICATION METHOD SHALL CONFORM WITH NEC AND OSHA. • SIONS
<br /> 10/i3/2022 E
<br /> 6. ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH LAMICOID TAGS SHOWING THEIR RATED VOLTAGE, PHASE A 1O/26/2022 ISSUED FOR EX.,
<br /> CONFIGURATION,WIRE CONFIGURATION, POWER OR AMPACITY RATING AND BRANCH CIRCUIT ID NUMBERS (i.e. PANEL BOARD AND CIRCUIT A Ti/0T/2022 ISSUED FOR PER.,
<br /> ID'S). 2/11/ COMMENTS FRO31 IVO COT
<br /> A c/1s/RARmz a ME Rs w EOUENr LOw1roN
<br /> •
<br /> 7. PANEL BOARDS (ID NUMBERS) SHALL BE CLEARLY LABELED WITH PLASTIC LABELS. A 9/22/202R ISSUED FOR ERA,
<br /> 8. TIE WRAPS ARE NOT ALLOWED. A 0ry7/2022 5531E0 FOR FINAL
<br /> 9. ALL POWER AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE SINGLE COPPER CONDUCTOR(#14 OR LARGER) A&E PROJECT NUMBER
<br /> WITH TYPE THHW,THWN,THWN-2,XHHW,XHHW-2,THW,THW-2, RHW,OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED, SESEA00377C
<br /> 10. SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE COPPER CONDUCTOR(#6 OR LARGER)WITH DISH Wireless L.L.C.
<br /> TYPE THHW,THWN,THWN-2,XHHW, XHHW-2,THW,THW-2, RHW,OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED. PROJECT INFORMATION
<br /> 11. POWER AND CONTROL WIRING IN FLEXIBLE CORD SHALL BE MULTI-CONDUCTOR,TYPE SOOW CORD (#14 OR LARGER) UNLESS SESEA00377C
<br /> OTHERWISE SPECIFIED. 2930 WETMORE AVENUE
<br /> 12. POWER AND CONTROL WIRING FOR USE IN CABLE TRAY SHALL BE MULTI-CONDUCTOR,TYPE TC CABLE(#14 OR LARGER),WITH EVERETT, WA 98201
<br /> TYPE THHW,THWN,THWN-2,XHHW, XHHW-2,THW,THW-2, RHW,OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
<br /> 13. ALL POWER AND GROUNDING CONNECTIONS SHALL BE CRIMP-STYLE,COMPRESSION WIRE LUGS AND WIRE NUTS BY THOMAS AND SHEET TITLE
<br /> BETTS(OR EQUAL). LUGS AND WIRE NUTS SHALL BE RATED FOR OPERATION NOT LESS THAN 75'C (90' C IF AVAILABLE). GENERAL NOTES
<br /> 14. RACEWAY AND CABLE TRAY SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL,ANSI/IEEE AND
<br /> NEC. SHEET NUMBER
<br /> 15. ELECTRICAL METALLIC TUBING(EMT), INTERMEDIATE METAL CONDUIT(IMC),OR RIGID METAL CONDUIT(RMC) SHALL BE USED FOR
<br /> EXPOSED INDOOR LOCATIONS. GN-3
<br /> DISH Wireless L.L C.TEMPUTE VERSION 15-10/29/2021