Ms. Dawn Bushnaq <br />Bushnaq Studio Architecture + Design <br />Plan Check Number: B2109-083, First Building Review <br />February 2, 2022 <br />12. The building has wood gravity posts and beam along Grids C and H, and interior beams, that <br />require fire -rated protection per Sections 1/A322 and 1/A324. Other similar framing (e.g, <br />interior wood posts, etc.) may also be proposed. The gravity framing requires a minimum one - <br />hour protection per IBC Table 601 and Section 704.1. Details providing fire -protection should <br />be included in the drawings. Alternatively, calculations demonstrating the minimum fire <br />protection may be submitted for review. See IBC Section 722.6 and AWC NDS-18 Chapter 16. <br />13. Typical details for penetrations through fire -rated assemblies should be provided in the <br />construction drawings. See IBC Sections 107.2.1 and 714. <br />14. Detail 6/A831 appears to show a proposed shaft for the exhaust vents within the floor assembly <br />cavity. The following comments should be addressed: <br />a. The interior of the cavity is required to be lined on all sides with a minimum of two layers of <br />5/8-inch Type "V GWB. Insulation does not provide the required fire protection. See IBC <br />Table 722.6.2. <br />b. The details do not clearly show the cavity being lined along the duct run from the fan to the <br />exterior wall and should be revised. See IBC Section 107.2.1. <br />c. Continuing with the previous two comments, radiation dampers may be specified per IBC <br />Section 717.3.1 Item 4. Dampers are not permitted on kitchen hood ducts and dryer vents <br />per IMC Sections 506.3.11 and 504.2. <br />d. The note references "Assembly per SBC CA 712.4". This is not a recognized standard in the <br />City of Everett and is not approved for use. The note should be removed. <br />15. Kitchen Room 110 and the kitchen in Room 302 will require hoods that must vent to the <br />exterior of the building. It appears that the ducts must be located in shafts extending through <br />the roof. Details for one -hour shaft construction should be included per IBC Section 7163.4. <br />The require one -hour construction including opening protectives per Section 713.11; dampers <br />are not permitted in the ducts to separate the shafts from the rooms. <br />16. The building appears to require mechanical ventilation supplied by ducts per the reflected <br />ceiling plans on Sheets A221 through A223. The ducts will penetrate rated walls and will <br />required dampers per IBC Section 717. The duct and damper requirements may be included in <br />the construction drawings for the mechanical permit drawings. However, shafts required for <br />duct work should be included in the building drawings. The shaft locations should be shown in <br />the plans and details included for the required construction. See IBC Section 713. <br />17. The floor plans do not indicate if the elevator shafts require separate machine rooms. If <br />machine rooms are required, they should be located in fire -rate rooms per IBC Section 3005.4. <br />The locations of the rooms should be shown on the plans. <br />18. The elevator should have a rated lid per IBC Section 713.12 unless the shaft walls extend to the <br />underside of the roof sheathing. The proposed construction is not clear in Sections 4/A312 and <br />6/A711 for the elevator at Grid E/5.5. The design should be clarified and revised as needed. <br />See IBC Sections 107.2.1 and 3002.1. <br />3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br />Everett, WA 98201 425.257.8857 fax everettwa.gov/permits <br />Page 4 of 10 <br />