Ms. Dawn Bushnaq <br />Bushnaq Studio Architecture + Design <br />Plan Check Number: B2109-083, First Building Review <br />February 2, 2022 <br />Egress: <br />19. The proposed construction of Stair C is not clear on Sheets A201, A202, and A702. Unclear <br />conditions include but are not limited to the locations of walls, enclosed spaces and reduced <br />head clearance, direction of travel, and access. The proposed construction should be revised. <br />See IBC Sections 107.2.1, 1011.7.3, 1011.13, and 1101.2, and ICC A117.1-09 Section 307.4. <br />20. Continuing with the previous comment, Door 10OC-1 accessing Stairway C provides egress <br />system from Room 141, which has an assembly occupancy, and should swing outward. Room <br />141 should not be used for egress for the stairway. The door swing may reduce the landing <br />width to less than one-half the required width. See IBC Sections 1010.1.2.1 and 1011.6. <br />21. Landings are required at all exterior doors per IBC Section 1010.1.6. It is not clear if this is <br />provided at all doors. Additional landings should be specified in the drawings as needed. <br />22. Door 300B provides egress access from assembly Room 302 to Stair B. The door should swing <br />into the stairway on Sheets G323 and A203. See IBC Section 1010.1.2.1. <br />23. Panic hardware should be specified in the Door Schedule and Hardware Sets schedule on <br />Sheets A620 and A621, respectively, for additional doors including but not limited to 100C-1, <br />100C-2, 108-1, 108-2, 108-3, 108-4, 140-2, 141-3, and 302-1. See IBC Section 1010.1.10. <br />24. The egress plans on Sheets G321 through G323 should specify the locations of maximum <br />occupant load signs per IBC Section 1004.9. The signs should be located near the main exit in <br />each room with an assembly occupancy exceeding 49. <br />25. Additional exit signs should be specified at Doors 101-1, 105, 108-2, 108-4, 140-1, 141-3, and <br />201. Additional signs should also be provided in the central area of Corridors 120 and 220, and <br />Lobby 102, and inside the stairways. See IBC Sections 1010.1 and 1013.1. <br />26. The construction drawings should include a note requiring all exit signs to be connected to the <br />main building power supply and provided with a minimum 90-minute back-up power. See IBC <br />Section 1013.6.3. <br />27. The egress plans on Sheets G321 through G323 should specify the locations of interior and <br />exterior emergency egress lighting for all rooms with assembly occupancies and the continuous <br />egress paths to the exit discharges, including the stairways. The construction drawings should <br />include a note requiring all lights to be connected to the main building power supply and <br />provided with a minimum 90-minute back-up power. See IBC Sections 1008.3, 1008.3.2, and <br />1008.3.4. <br />Accessibility: <br />28. Restrooms 146a, 146b, 246a, and 247a do not appear to provide the required turning space per <br />ICC A117.1-09 Sections 603.2.1 and 304. The design should be revised. See IBC Section <br />1101.2. <br />3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br />Everett, WA 98201 425.257.8857 fax everettwa.gov/permits <br />Page 5 of 10 <br />