Laserfiche WebLink
Data Sheet Enphase IQ 7 and IQ 7+ Microinverters <br /> Enphase Microinverters INPUT DATA(DC) IQ7-60-2-US IQ7PLUS-72-2-US <br /> Region:AMERICAS <br /> Commonly used module pairings' 235W-350W+ 235 W-440 W+ <br /> Module compatibility 60-cell PV modules only 60-cell and 72-cell PV modules <br /> Maximum input DC voltage 48V 60V <br /> Peak power tracking voltage 27 V-37 V 27V-45V <br /> Operating range 16V-48V 16 V-60 V <br /> Min/Max start voltage 22V/48V 22 V/60 V <br /> Max DC short circuit current(module Isc) 15A 15A <br /> Enphase The high-powered smart grid-ready Overvoltage class DC port II II SYSTEM INFO. <br /> Enphase IQ 7 Micro"and Enphase IQ 7+Micro DC port backfeed current 0 A 0 A (20)HANWHA Q CELL Q.PEAK DUO BLK <br /> p p <br /> PV array configuration 1 x 1 ungrounded array;No additional DC side protection required; ML-G10+10+(400 W) <br /> Q7 and IQ 7+ dramatically simplify the installation process while AC side protection requires max 20A per branch circuit (20)ENPHASE IQ7PLUS-72-2-US(240V) <br /> achieving the highest system efficiency. OUTPUT DATA(AC) IQ 7 Microinverter IQ 7+Mlcrolnverter DC SYSTEM SIZE:6.00 KWDC <br /> Microinverters Peak output power 250 VA 295 VA AC SYSTEM SIZE:5.90 KWAC <br /> Part of the Enphase IQ System,the IQ 7 and Maximum continuous output power 240 VA 290 VA <br /> IQ 7+Microinverters integrate with the Enphase Nominal(L-L)voltage/range2 240 V/ 208V/ 240 V/ 208V/ REVISIONS <br /> 9 P 211-264 V 183-229 V 211-264 V 183-229 V DESCRIPTION DATE REV <br /> IQ Envoy", Enphase IQ Battery'",and the Enphase Maximum continuous output current 1.0 A(240 V) 1.15 A(208 V) 1.21 A(240 V) 1.39 A(208 V) <br /> Enlighten" monitoring and analysis software. Nominal frequency 60 Hz 60 Hz <br /> Extended frequency range 47-68 Hz 47-68 Hz <br /> IQ Series Microinverters extend the reliability AC short circuit fault current over 3cycles 5.8 Arms 5.8 Arms <br /> Maximum units per 20 A(L-L)branch circuit3 16(240 VAC) 13(208 VAC) 13(240 VAC) 11(208 VAC) Signature with Seal <br /> standards set forth by previous generations and Overvoltage class AC port III III <br /> undergo over a million hours of power-on testing, AC port backfeed current OA OA <br /> Power factor setting l.o l.o <br /> enabling Enphase to provide an industry-leading <br /> Power factor(adjustable) 0.85 leading...0.85 lagging 0.85 leading...0.85 lagging <br /> warranty of up to 25 years. EFFICIENCY @240 V @208 V @240 V @208 V <br /> Peak efficiency 97.6% 97.6% 97.5% 97.3% <br /> CEC weighted efficiency 97.0% 97.0% 97.0% 97.0% <br /> MECHANICAL DATA <br /> Ambient temperature range -40°C to+65*C <br /> Relative humidity range 4%to 100%(condensing) <br /> Easy to Install Connector type(IQ7-60-2-US&IQ7PLUS-72-2-US) MC4(or Amphenol H4 UTX with additional Q-DCC-5 adapter) PROJECT NAME&ADDRESS <br /> Dimensions(WxHxD) 212 mm x 175 mm x 30.2 mm(without bracket) <br /> Lightweight and simple <br /> Weight 1.08 kg(2.38 lbs) <br /> Faster installation with improved,lighter two-wire cabling Cooling Natural convection-No fans <br /> Built-in rapid shutdown compliant(NEC 2014&2017) Approved for wet locations Yes z <br /> Pollution degree PD3 O CO OM <br /> Enclosure Class II double-insulated,corrosion resistant polymeric enclosure U) W O T_ <br /> Productive and Reliable W W U N O <br /> Environmental category/UV exposure rating NEMA Type 6/outdoor Q 0 O <br /> Optimized for high powered 60-cell and 72-cell*modules FEATURES w z JJ a C:)More than a million hours of testing Communication Power Line Communication(PLC) J w > NT <br /> Class II double-insulated enclosure Monitoring Enlighten Manager and MyEnlighten monitoring options. Q U > O <br /> Both options require installation of an Enphase IQ Envoy. (' <br /> UL listed =Disconnecting means The AC and DC connectors have been evaluated and approved by UL for use as the load-break Z O <br /> ' disconnect required by NEC 690. Q w Y W O <br /> Compliance CA Rule 21(UL 1741-SA) <br /> w <br /> Smart Grid Ready UL 62109-1,UL1741/IEEE1547,FCC Part 15 Class B, ICES-0003 Class 13, O W <br /> CAN/CSA-C22.2 NO.107.1-01 z (0 > <br /> Complies with advanced grid support,voltage and This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC-2014 and z W Z Z <br /> frequency ride-through requirements NEC-2017 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems,for AC Q <br /> Remotely updates to respond to changing and DC conductors,when installed according manufacturer's instructions. J <br /> grid requirements <br /> Configurable for varying grid profiles <br /> Meets CA Rule 21(UL 1741-SA) DATE:03/31/2022 <br /> SHEET NAME <br /> U * <br /> The IQ 7+Micro is required to support 72-cell modules. <br /> ` 1.No enforced DC/AC ratio.Seethe compatibility calculator at https,//enphase.com/en-us/support/module-compat6bility. EQUIPMENT <br /> 2.Nominal voltage range can be extended beyond nominal if required by the utility. SPECIFICATION <br /> 3.Limits may vary.Refer to local requirements to define the number of microinverters per branch in your area. <br /> SHEET SIZE <br /> ENP HAS E. To learn more about Enphase offerings,visit enphase.com ENP HAS E. <br /> To learn more about Enphase offerings,visit enphase.com �� ©2019 Enphase Energy.All rights reserved.All trademarks or brands used are the property of Enphase Energy,Inc. " ANSI B <br /> 2019-3-26 <br /> 11" X 17" <br /> SHEET NUMBER <br /> PV-7 <br />