Laserfiche WebLink
FIRE CODE ORDINANCE Page 19 of 38 <br /> <br />903.2.1.1 Item 1. Replaced the following language “12,000” with “6,000”. <br /> <br />D. Subsection 903.2.1.3 Item 1 of the IFC, entitled “Group A-3,” is hereby amended: <br /> <br />903.2.1.3 Item 1. Replace the following language “12,000” with “6,000”. <br /> <br />E. Subsection 903.2.1.4 Item 1 of the IFC, entitled “Group A-4,” is hereby amended: <br /> <br />903.2.1.4 Item 1. Replace the following language “12,000” with “6,000”. <br /> <br />F. Subsection 903.2.4 of the IFC, entitled “Group F-1,” is hereby deleted and the following inserted in <br />its place: <br /> <br />903.2.4 Group F-1 & Group F-2. An automatic Sprinkler system shall be provided throughout all <br />buildings containing a Group F-1 or Group F-2 occupancies where one of the following conditions <br />exists: <br />1. A Group F-1 or a Group F-2 fire area exceeds 6,000 square feet. <br />2. A Group F-1 fire area is located more than three stories above grade plane. <br />3. The combined area of all Group F-1 fire areas on all floors, including any mezzanines, <br />exceeds 24,000 square feet. <br /> <br />G. Subsection 903.2.7 Item 1 of the IFC, entitled “Group M,” is hereby amended: <br /> <br />903.2.7 Item 1. Replace the following language “12,000” with “6,000”. <br /> <br />H. Subsection 903.2.9 Item 1 of the IFC, entitled “Group S-1,” is hereby amended: <br /> <br />903.2.9 Item 1. Replace the following language “12,000” with “6,000”. <br /> <br />I. Subsection 903.2.10 of the IFC, entitled “Group S-2 enclosed parking garages,” is hereby amended: <br /> <br />903.2.10 Item 1. Replace the following language “12,000” with “6,000”. <br /> <br />J. Subsection 903.2.13 of the IFC, entitled “Group B,” is hereby added: <br /> <br />903.2.13 Group B and/or Group U. An automatic sprinkler system shall be provided throughout all <br />buildings containing a Group B and/or Group U occupancy where a fire area that exceeds 6,000 <br />square feet. <br /> <br />K. Subsection 903.3.1.2.1 of the IFC, entitled “Balconies and decks,” is hereby deleted and the <br />following inserted in its place: <br /> <br />903.3.1.2.1 Balconies and decks. Sprinkler protection shall be provided for exterior balconies, decks <br />and ground floor patios of dwellings units and sleeping units. Sidewall sprinklers that are used to <br />protect such areas shall be permitted to be located such that their deflectors are within 1 inch to 6