a. The occupant load of the deck and 3rd story are added to the 'served' area as they exit <br /> through that space. Section 1004.7 <br /> b. The addition of the bar changes the Occupant Load Factor from 100 to 15 (or even 7 or <br /> 5). Section 1004.5 <br /> 6. The occupant load of the second floor now exceeds 50 persons.A minimum of two exits is required <br /> from that story. Section 1006.3.3 <br /> 7. The addition of the kitchen will trigger the installation of a grease interceptor. Everett Public Works <br /> Industrial Pre-Treatment should be contacted to verify sizing and location requirements. <br /> 8. The New Main Room requires two exits. Section 1006.2.1 <br /> 9. Exit signs, emergency egress lighting, panic hardware and maximum occupant load signs should be <br /> shown on the plans for the building. Chapter 10 <br /> 10. The occupant loads for each space should be shown on the plans. Section 107.2.3 <br /> 11. The minimum number of required plumbing fixtures should be justified on the plans. Section <br /> 2902.1 <br /> 12. The IEBC compliance method for the existing 3-story stairway(enclosure) should be shown. Note <br /> that the existing, non-complying stair enclosure is being altered/removed by this proposal. IEBC <br /> Section 303.1 <br /> 13. It should be specified how the accessible route of travel to the primary function areas will be <br /> upgraded (to include the existing non-accessible restroom) with the required 20% as specified in <br /> IEBC section 305.7 <br /> 14. The deck and stair guards should be shown at a minimum of 42" high. Section 1015.3 <br /> 15. The guard construction should be detailed on the plans. Section 1011 <br /> 16. The rise/run and width of the new stairs should be detailed on the plans. Section 1011 <br /> 17. Stair handrails (to include extensions) should be shown on the plans. Section 1011.11 <br /> 18. Solid risers should be shown on the new stairs. Section 1011.5.5 <br /> 19. A landing should be shown at the bottom of the stairs. Section 1011.6 <br /> STRUCTURAL <br /> 1. The proposed changes to the interior of the space meet the requirements of an A2 occupancy. <br /> The design loading per IBC 1607 requires the design live load to meet the applicable <br /> requirements of assembly areas per Table 1607.1. Please verify with revised calculations <br /> E Page 2 of 4 <br />