William Velasco <br /> Plan Check Number: B2202-028, First Building Review <br /> March 10, 2022 <br /> Section R311.7. The stair detail should also show a thrust block or kicker plate and the <br /> connections to the existing concrete slab. <br /> 8. Smoke and CO alarms should be provided per IRC Sections R314 and R315. The locations of all <br /> alarms should be shown on the plans. The alarms should be hardwired, interconnected, and <br /> provided with back-up battery power as required. <br /> 9. The project involves increasing the conditioned space at the basement level. Energy credits are <br /> required per WSEC Section R406. The required number of credits should be normalized per <br /> Table R406.2. A schedule of the selected credits should be included in the drawings. The <br /> performance requirements for the selected credits should be specified. <br /> 10. Continuing with the previous comment, the basement level walls should be updated to comply <br /> with the 2018 WSEC. Below grade walls should be insulated per Table R402.1.1 unless <br /> modifications are required per selected energy credits. Basement level walls may have to be <br /> furred out in order to comply with the WSEC. <br /> 11. The loft and main level bathroom appear to be previously remodeled without permits. This <br /> includes exposing the exterior envelope cavities. The building is required to be insulated per <br /> WSEC Section R503.1.1. Where required, insulation complying with current code should be <br /> provided per Table R402.1.1. Attics should be provided with ventilation baffles per Section <br /> R402.2.3. <br /> 12. The attic spaces in the loft should be provided with access openings per IRC Section R807. <br /> 3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 3 of 5 <br />
The URL can be used to link to this page
Your browser does not support the video tag.