My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
2923 COLBY AVE 2024-10-24
>
Address Records
>
COLBY AVE
>
2923
>
2923 COLBY AVE 2024-10-24
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
10/24/2024 1:15:37 PM
Creation date
6/24/2024 10:31:11 AM
Metadata
Fields
Template:
Address Document
Street Name
COLBY AVE
Street Number
2923
Imported From Microfiche
No
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
144
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
• • <br /> Mr. Matt Schreifels <br /> 2812 Architecture <br /> Plan Check Number: B2208-005, Second Building Review <br /> March 1, 2023 <br /> 6. The following comments should be addressed for the emergency means-of-egress illumination: <br /> a. The lighting shall specify a minimum 90-minute uninterrupted supply power per IBC Section <br /> 1008.3.4. <br /> b. Exterior lights should be shown at all exits per IBC Section 1008.3.2(5). An additional light <br /> at the main entrance of the Main Floor should be provided. <br /> c. Egress lighting should be consistently shown in the Occupancy Plans on Sheet A2.0 with the <br /> Floor Plans on Sheet A2.2. <br /> 8. The original comment addressed the assembly aisle requirements per IBC Section 1029. See <br /> IBC Section 1029.9.1. The following comments should be addressed: <br /> a. The Main Floor Plan on Sheet A2.2 should provide a minimum 55-inch clearance between <br /> the stair guard and the bar, including the 19-inch allowance per IBC Section 1029.13.1. <br /> b. The Main Floor Plan on Sheet A2.2 should provide a minimum 31-inch clearance between <br /> the stair guard and the bar per IBC Section 1029.13.1.1, including the 19-inch allowance per <br /> Section 1029.13.1. It is noted that the required minimum width may be 30 inches per <br /> Section 1029.9.1(5) plus the 19-inch allowance. <br /> c. The Lower Floor Plan on Sheet A2.2 should provide a minimum 55-inch clearance between <br /> the stair guard and the bar, including the 19-inch allowance per IBC Section 1029.13.1. <br /> This minimum clearance should be specified along the south side of the stairway, and <br /> between the stairway and the Bar and table nearest the bottom of the stairs. <br /> d. Other routes other than aisle accessways (i.e., between tables against the wall) should <br /> provide a minimum 30-inch clearance plus 19 inches on each side where chairs occur. <br /> Accessibility: <br /> 9. Documentation substantiating that accessibility improvements have been performed should be <br /> submitted per IEBC Section 305.7. The Lower Floor modifications and associated egress routes, <br /> and changes to already accessible components at the Main Floor (e.g., main entrance, etc.) do <br /> not qualify as improvements. It is noted that the Main Level bathrooms do not appear to <br /> provide accessible ingress per ICC A117.1-09 Figure 404.2.3.2(g); it is presumed a latch and <br /> closer are provided. Where parking is provided on-site, accessible parking should also be <br /> addressed. <br /> 11.The original comment stated that both levels require two exits that must have accessible egress <br /> per IBC Section 1009.1. The Main Floor has been modified to convert an existing door to <br /> Sprinkler Room 111 and remove an exterior door. The removed door appears to provide an <br /> accessible entrance and egress path, whereas the exit door to remain does not. At a minimum, <br /> the door being removed is more accessible than the remaining door. An accessible door for <br /> both ingress and egress is required. See IBC Sections 1009.1 and 1104.3., and IEBC Section <br /> 305.3. <br /> Energy: <br /> 14.This comment has not been addressed. Energy credits for the new conditioned space in the <br /> basement should be specified per WSEC-18 Section C406.1. The performance requirements <br /> should be specified in the drawings. <br /> 0 3200 Cedar Street 425.257.8810 0 everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 3 of 4 <br />
The URL can be used to link to this page
Your browser does not support the video tag.