Mr. Eric Evans <br />Shelter Holdings <br />Plan Check Number: B1912-032, First Structural Review <br />January 3, 2020 <br />Schedule Note 2 references Section 06100 "Rough Framing on Sheet S1.00 for the framing <br />species and grade, which specifies hem -fir (HF) framing for the 4-inch studs. Sheets S3.9113 <br />and S3.9213 appear to indicate that many of the shear walls will be 4-inch walls. The notes <br />should be revised to consistently specify DFL-framing. Alternatively, the calculations should be <br />revised to reduce the shear wall capacities for HF-framing. See IBC Sections 1603.1 and <br />2306.1, and AWC SDPWS-15 Table 4.3A Footnote 3. <br />21. The structural calculations for the wood shear wall holdowns include a calculation for the side - <br />face blowout mechanism per ACI 318-14 Section 17.4.4. The calculations appear to indicate <br />that the anchor tensile capacity for this mechanism is less than required by Section <br />17.2.3.4.3(a), and instead are proposing supplemental hairpins to prevent the blowout <br />mechanism. ACI 318-14 Chapter 17 does not recognize providing hairpins as an alternative to <br />satisfying Section 17.4.4. It is not clear how the submitted calculation substantiates an <br />alternative method. Revised documentation that more clearly substantiates the proposed <br />design should be submitted for review. See IBC Sections 104.11 and 1901.2. <br />22. The design for the shear wall sill plate anchor bolts does not appear to be provided in the <br />structural calculations. The earthquake component of the shear forces exceeds 20% of the <br />total shear (i.e., the earthquake force is 100% of shear force). The earthquake component <br />shall be increased per the provisions of ACI 318-14 Section 17.2.3.5.3. Revised calculations <br />substantiating the anchor bolt design should be submitted for review. Alternatively, it appears <br />the design may satisfy the IBC Section 1905.1.8 amendments to ACI 318-14 Section 17.2.3.5.2. <br />Some revisions may be required, including increasing the minimum anchor bolt length to 7 <br />inches in Note 10 of Detail S1.02. The design load shall be determined per ASCE 7-10 Section <br />12.4.3.2 Equation 7. See IBC Sections 1604.10, 1613.1, and 1901.2. <br />This review has been performed for general compliance with the building codes as adopted and <br />amended by the state of Washington and the city of Everett. Corrections and comments made <br />during the review process do not relieve the project from compliance with code and permit <br />requirements. The designers -of -record are responsible for a complete design in accordance with <br />the laws of the state of Washington. <br />If you have any questions or require additional clarification, please contact us. <br />Respectfully, <br />Drew Martin, P.E., S.E. <br />Associate Engineer / Commercial Plans Examiner <br />(425)257-8813 <br />dmartin@everettwa.gov <br />S:\BMartin\2019\Bl9l2-032—Rl-STR.docx <br />3200 <br />dar <br />0 Everett WAStreet98201 O 425.257.88577 fax O everett asgov/permitgov s <br />Page 7 of 7 <br />