" A FARRINGTON <br /> i _ AIR QUALITY SERVICES <br /> Air Handling Unit <br /> PROJECT: Ballot Facility TI DATE: 6/17/2024 <br /> LOCATION: Everett,WA CONTACT: JT Parker <br /> PROJECT#: 23-1064 <br /> SYSTEM/UNIT: AHU-01/B-07 Tested By: Eric Liles <br /> Date: 6/13/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 700 CFM <br /> Model Number VDDF Actual Max Airflow 696 CFM <br /> Serial Number R23K01747 Max Diff.SP 0.54 in.wc <br /> Box Inlet Size 8"/6" Min Design CFM 210 CFM <br /> K Factor 2.0/2.0 Actual Min Airflow 200 CFM <br /> Min Diff.SP 0.45 in.wc <br /> Design Reheat Airflow 490 CFM <br /> Actual Reheat Airflow 460 CFM <br /> Reheat Diff.SP 0.80 in.wc <br /> AHU-01/B-07 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM <br /> Outlet-01 CD 12" Flowhood 1.00 700 696 696 99 <br /> Totals: - - - - 700 696 696 99 <br /> SYSTEM/UNIT: AHU-01/B-08 Tested By: Eric Liles <br /> Date: 6/13/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 425 CFM <br /> Model Number VDDF Actual Max Airflow 413 CFM <br /> Serial Number R23K01751 Max Diff.SP 0.19 in.wc <br /> Box Inlet Size 8"/6" Min Design CFM 130 CFM <br /> K Factor 2.0/2.0 Actual Min Airflow 134 CFM <br /> Min Diff.SP 0.02 in.wc <br /> Design Reheat Airflow 295 CFM <br /> Actual Reheat Airflow 283 CFM <br /> Reheat Diff.SP 0.30 in.wc <br /> AHU-01/B-08 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM <br /> Outlet-01 CD 10 Flowhood 1.00 250 250 240 96 <br /> Outlet-02 CD 10 Flowhood 1.00 100 100 95 95 <br /> Outlet-03 CD 10 Flowhood 1.00 75 75 75 100 <br /> Totals: - - - - 425 425 410 96 <br /> Farrington Air Quality Services <br />