Laserfiche WebLink
FARRINGTON <br /> AIR QUALITY SERVICES <br /> Air Handling Unit <br /> PROJECT: Ballot Facility TI DATE: 6/17/2024 <br /> LOCATION: Everett,WA CONTACT: JT Parker <br /> PROJECT#: 23-1064 <br /> SYSTEM/UNIT: AHU-01/B-25 Tested By: Chris Brittenham <br /> Date: 6/13/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 625 CFM <br /> Model Number VDDF Actual Max Airflow 610 CFM <br /> Serial Number R23K01760 Max Diff.SP 0.41 in.wc <br /> Box Inlet Size 06/08 Min Design CFM 190 CFM <br /> K Factor 2.1/2.1 Actual Min Airflow 190 CFM <br /> Min Diff.SP 0.04 in.wc <br /> Design Reheat Airflow 435 CFM <br /> Actual Reheat Airflow 420 CFM <br /> Reheat Diff.SP 0.64 in.wc <br /> Log: AHU-01/B-25 6/13/2024 Chris Brittenham Outlets 1 and 2 are missing grills. <br /> AHU-01/B-25 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM <br /> Outlet-01 CD Flowhood 1.00 225 <br /> Outlet-02 CD Flowhood 1.00 150 <br /> Outlet-03 CD Flowhood 1.00 125 <br /> Outlet-04 CD Flowhood 1.00 125 <br /> Totals: - - - - 625 0 0 0 <br /> SYSTEM/UNIT: AHU-01/B-26 Tested By: Eric Liles <br /> Date: 6/13/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 900 CFM <br /> Model Number VDDF Actual Max Airflow 850 CFM <br /> Serial Number R23K01765 Max Diff.SP 0.31 in.wc <br /> Box Inlet Size 10/8 Min Design CFM 270 CFM <br /> K Factor 2.10 Actual Min Airflow 256 CFM <br /> Min Diff.SP 0.29 in.wc <br /> Design Reheat Airflow 630 CFM <br /> Actual Reheat Airflow 610 CFM <br /> Reheat Diff.SP 0.48 in.wc <br /> AHU-01/B-26 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM <br /> Outlet-01 CD 22x22 Flowhood 1.00 900 850 850 94 <br /> Totals: - - - - 900 850 850 94 <br /> Farrington Air Quality Services <br />